13
6. Setting from GX Developer
In the intelligent function module switch setting, set the redundant system
support function or QJ71PB92D-compatible function of the QJ71PB92V.
The following setting should be made only when using the redundant system
support function or QJ71PB92D-compatible function.
When setting the intelligent function module switch, select either (1) or (2)
shown below.
The redundant system support function cannot be used together with the
QJ71PB92D-compatible function.
(1) For the redundant system support function
(2) For the QJ71PB92D-compatible function
Table 6.1 Intelligent function module switch
(For the redundant system support function)
Switch No.
Description
Switch 1
Set the standby master FDL address when the QJ71PB92V
is mounted in a redundant system.
Disabled: No setting (blank)
Enabled : Refer to the following (Set only when using the
redundant system support function)
Switch 2
No setting (blank)
If any setting exists, delete it.
Switch 3
Switch 4
Switch 5
Table 6.2 Intelligent function module switch
(For the QJ71PB92D-compatible function)
Switch No.
Description
Switch 1
Set whether to continue or stop the I/O data communication
with the DP-Slave when the CPU stop error occurs.
Continue : No setting (blank)
Stop : 0001
H
Switch 2
9244
H
Switch 3
No setting (blank)
If any setting exists, delete it.
Switch 4
Switch 5
1
Standby master FDL address
Setting range: 0
H
to 7D
H
(0 to 125)
0
H