9 - 20 9 - 20
MELSEC-Q
9 PROGRAMMING
(3) Auto refresh setting
Make auto refresh setting from the Auto refresh setting screen of GX
Configurator-MB.
Set the following items for the program example.
Setting Item
Module side
Transfer word count
Module side
Buffer offset
PLC side
Device
Automatic communication function buffer input area
64
256(100
H
) D4096
Automatic communication function buffer output area
100
2560(A00
H
) D5000
Automatic communication operation status
D4092
(4) Automatic communication function
For a program example for error code acquisition at an automatic communication
error, refer to <<Handling of automatic communication error>> in (5).
POINT
The automatic communication error code can be monitored on the "Automatic
communication status" screen of GX Configurator-MB.