9 - 14 9 - 14
MELSEC-Q
9 PROGRAMMING
(2) Parameter setting details
The following table gives the setting details of the parameters set in the program
example.
(a) Basic parameters
Setting Item
Buffer Memory Address
Set Value
TCP ULP timer value
0000
H
(0)
60 (30s)
TCP zero window timer value
0001
H
(1)
20 (10s)
TCP resend timer value
0002
H
(2)
20 (10s)
TCP end timer value
0003
H
(3)
40 (20s)
IP reassembly timer value
0004
H
(4)
10 (5s)
TCP/UDP/IP
monitoring timer
Split reception monitoring timer value
0005
H
(5)
60 (30s)
KeepAlive 0006
H
(6)
1 (Used)
KeepAlive start timer value
0007
H
(7)
1200 (600s)
KeepAlive interval timer value
0008
H
(8)
20 (10s)
KeepAlive
KeepAlive resend count
0009
H
(9)
3
Router relay function
000A
H
(10)
0 (Not used)
Subnet mask pattern
000B
H
to 000C
H
(11 to 12)
FFFFFF00
H
(255.255.255.0)
Default router IP address
000D
H
to 000E
H
(13 to 14)
00000000
H
(0.0.0.0)
Number of routers set
000F
H
(15)
0
Subnet address
0010
H
to 0011
H
(16 to 17)
00000000
H
(0.0.0.0)
Routing information
Router
information 1
Router IP address
0012
H
to 0013
H
(18 to 19)
00000000
H
(0.0.0.0)
GX Developer
connection
information setting
Number of TCP connectors for GX
Developer connection
0030
H
(48)
1
Local slave station port No.
0110
H
(272)
502
Target slave port No. for automatic
communication function
0111
H
(273)
502
CPU response monitoring timer value
0114
H
(276)
10
IP address
0115
H
to 0116
H
(277 to 278)
C0010002
H
(192.1.0.2)
MODBUS
R
/TCP
setting
Preferred node
specification 1
Number of connections
0117
H
(279)
2