Hardware test checks the hardware inside the CC-Link IE controller network module.
(1) System configuration and parameter setting for other than redundant
systems
(a) System configuration
Connect GX Developer to the CPU module.
Do not connect optical fiber cables to the CC-Link IE controller network module.
(b) Setting network parameters in GX Developer
1) Setting the hardware test mode.
After setting the following network parameters in GX Developer, write them to
the programmable controller.
Figure 5.7 System configuration
Figure 5.8 Network parameters in GX Developer
Table 5.4 Network parameter setting items of GX Developer
Item
Set value
Network type
CC IE Control (Normal station)
Starting I/O No.
0000
Network No.
1
Group No.
0
Station No.
4
Mode
H/W test
GX Developer
Normal station
No.4
Summary of Contents for QJ71GP21-SX