background image

29

E9

Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)

1

Abnormal if “0” receiving is detected 
30 times continuously though outdoor 
controller circuit board has transmitted “1”.

2

  Abnormal if outdoor controller 

circuit board could not find blank of 
transmission path for 3 minutes.

1

 Indoor/ outdoor unit connecting 

wire has contact failure. 

2

 Defective communication circuit 

of outdoor controller circuit board

3

 Noise has entered power supply.

4

 Noise has entered indoor/ 

outdoor unit connecting wire.

1

 Check disconnection or looseness of indoor/

outdoor unit connecting wire.

2

~

4

  Turn the power off, and on again to 

check. Replace outdoor controller circuit 
board if abnormality is displayed again.

EF

Non defined error code

This code is displayed when non defined 
error code is received.

1

 Noise has entered transmission 

wire of remote controller.

2

 Noise has entered indoor/ 

outdoor unit connecting wire.

3

 Outdoor unit is not inverter 

models.

4

 Model name of remote 

controller is PAR-S25A.

12

 Turn the power off, and on again to check.   

Replace indoor controller board or outdoor 
controller circuit board if abnormality is 
displayed again.

3

 Replace outdoor unit with inverter type 

outdoor unit.

4

 Replace remote controller with MA remote 

controller.

E8

Indoor/outdoor unit communication error
(Signal receiving error) (Outdoor unit)

Abnormal if outdoor controller circuit board 
could not receive anything normally for 3 
minutes.

1

 Contact failure of indoor/

outdoor unit connecting wire

2

 Defective communication circuit 

of outdoor controller circuit board

3

 Defective communication circuit 

of indoor controller board

4

 Noise has entered into indoor/ 

outdoor unit connecting wire.

1

 Check disconnection or looseness of indoor/ 

outdoor unit connecting wire of indoor or 
outdoor units.

2

~

4

  Turn the power off, and on again to 

check. Replace indoor controller board 
or outdoor controller circuit board if 
abnormality is displayed again.

E3

or

E5

Remote controller transmission error (E3)/
signal receiving error (E5)

1

 Abnormal if remote controller could not 

find blank of transmission path for 6 
seconds and could not transmit.

(Error code: E3)

2

 Remote controller receives transmitted 

data at the same time, compares the 
data, and when detecting it, judges 
different data to be abnormal 30 
continuous times. (Error code: E3) 

1

 Abnormal if indoor controller board could 

not find blank of transmission path.

(Error code: E5)

2

 Indoor controller board receives 

transmitted data at the same time, 
compares the data, and when detecting 
it, judges different data to be abnormal 
30 continuous times. (Error code: E5)

1

 Set a remote controller to main, and the 

other to sub.

2

 Remote controller is connected with only one 

indoor unit.

3

 The address changes to a separate setting.

4

~

Diagnose remote controller.

a) When “RC OK” is displayed, remote 

controllers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace 
indoor controller board.

b) When “RC NG” is displayed, replace 

remote controller.

c) When “RC E3” or “ERC 00-66” is 

displayed, noise may be causing 
abnormality.

1

 2 remote controller are set as 

“main.”

(In case of 2 remote controllers)

2

 Remote controller is connected 

with 2 indoor units or more.

3

 Repetition of refrigerant 

address

4

 Defective transmitting receiving 

circuit of remote controller

5

 Defective transmitting receiving 

circuit of indoor controller board

6

 Noise has entered into 

transmission wire of remote 
controller.

* Check LED display on the outdoor controller 

circuit board. (Connect A-control service tool, 
PAC-SK52ST.)

1

 Check disconnection or looseness of 

Interface unit/Flow temp. controller or 
outdoor unit connecting wire of Interface 
unit/Flow temp. controller or outdoor unit.

2

~

4

Turn the power off, and on again to check. 

If abnormality generates again, replace 
Interface unit/Flow temp. controller or 
outdoor controller circuit board.

Interface unit/Flow temp. controller 
or outdoor unit communication error 
(Signal receiving error)

1

 Abnormal if Interface unit/Flow temp. 

controller cannot receive any signal 
normally for 6 minutes after turning the 
power on.

2

 Abnormal if Interface unit/Flow temp. 

controller cannot receive any signal 
normally for 3 minutes.

1

 Contact failure, short circuit 

or, miswiring (converse wiring) 
of Interface unit/Flow temp. 
controller or outdoor unit 
connecting wire

2

 Defective transmitting receiving 

circuit of outdoor controller 
circuit board

3

 Defective transmitting receiving 

circuit of Interface unit/Flow 
temp. controller

4

 Noise has entered into Interface 

unit/Flow temp. controller or 
outdoor unit connecting wire.

E6

Error Code

Abnormal point and detection method

Judgment and action

Case

Ed

Serial communication error

1

Abnormal if serial communication between 
outdoor controller circuit board and 
outdoor power circuit board is defective.

1

 Breaking of wire or contact 

failure of connector CN2 
between the outdoor controller 
circuit board and the outdoor 
power circuit board

2

 Breaking of wire or contact 

failure of connector CN4 
between the outdoor controller 
circuit board and the outdoor 
power circuit board

3

 Defective communication circuit 

of outdoor power circuit board

4

 Defective communication circuit 

of outdoor controller circuit board 
for outdoor power circuit board

12

 Check connection of each connector CN2 

and CN4 between the outdoor controller 
circuit board and the outdoor power circuit 
board.

3

 Replace outdoor power circuit board.

4

 Replace outdoor controller circuit board.

OCH533A

Summary of Contents for PUHZ-SW100VHA-BS.UK

Page 1: ...of model PUHZ SW75VHA BS PUHZ SW100VHA BS PUHZ SW100YHA BS PUHZ SW120VHA BS PUHZ SW120YHA BS Note This manual describes only service data of the outdoor units PUHZ SW75VHA BS UK PUHZ SW100VHA BS UK PU...

Page 2: ...20X VM6B EHPT20X YM9B EHST20C VM6HB UK EHST20C YM9HB UK EHST20C VM6B UK EHST20C YM9B UK EHST20C VM6EB UK EHST20C YM9EB UK EHST20C VM6SB UK EHPT20X VM2HB UK EHPT20X VM6HB UK EHPT20X YM9HB UK EHPT20X VM...

Page 3: ...rench Gas leak detector Charge hose Tools for R410A Contamination inside refrigerant piping can cause deterio ration of refrigerant oil etc If dirt dust or moisture enters into refrigerant cycle that...

Page 4: ...7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1 Perform service after recovering the refrigerant left in unit...

Page 5: ...ery device to collect the refrigerant Use new pipes for SW75 SW100 and SW120 models The existing pipe thickness does not meet speci cations or the pipes are damaged 2 4 PRECAUTIONS FOR SALT PROOF TYPE...

Page 6: ...29 0 17 0 22 0 24 0 27 0 36 0 Nominal dimensions inch Flare nut dimensions Outside diameter Dimension B mm R410A R22 Gauge manifold Charge hose Gas leak detector Refrigerant recovery equipment Refrige...

Page 7: ...nt level regardless of the length 10m max and 5m min of piping The additional refrigerant charging work during installation often causes prob lems Heretofore it is completely eliminated This unique sy...

Page 8: ...C 45 C Cooling A35 W7 Outside air temperature Dry bulb 35 C Outside air temperature Wet bulb 24 C Water temperature inlet outlet 12 C 7 C Cooling A35 W18 Outside air temperature Dry bulb 35 C Outside...

Page 9: ...Single 50Hz 230V OUTDOOR UNIT REFRIGERANT PIPING 1 3 19 A kW W kW min CFM dB dB mm in mm in mm in kg lbs kg lbs L mm in mm in Power supply phase cycle voltage Max current External finish Refrigerant c...

Page 10: ...ower supply phase cycle voltage Max current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger Fan Fan drive No Fan motor...

Page 11: ...PUHZ SW120VHA BS UK PUHZ SW120YHA UK PUHZ SW120YHA BS UK 4 6 4 8 5 0 5 6 6 2 6 8 7 5 4 6 U V U W W V Service Ref Compressor model Winding Resistance ANB33FNEMT at 20 C 0 19 0 19 0 19 PUHZ SW100VHA UK...

Page 12: ...500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 bar NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 PUHZ SW100VHA UK PUHZ SW100VHA BS...

Page 13: ...kout Front trunking hole Knockout Power supply wiring hole 2 27Knockout 9 2 40 45 65 92 27 55 23 73 63 Rear piping hole Knockout Rear trunking hole Knockout Power supply wiring hole 2 27Knockout 9 2 E...

Page 14: ...27Knockout W 92 92 65 45 40 27 55 23 73 63 Front piping hole Knockout Front trunking hole Knockout Power supply wiring hole 2 W27Knockout W 9 2 145 145 220 30 145 81 219 71 71 Bottom piping hole Knock...

Page 15: ...F1 F2 F3 F4 X51 X52 X54 Switch Function Switch Model Select Switch Model Select Switch Function Switch Switch Function Switch Switch Function Switch Switch Pump Down Connector Emergency Operation Con...

Page 16: ...n Connector Emergency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option LED Oper...

Page 17: ...witch Pump Down Connector Emergency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for O...

Page 18: ...e NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device S1 S2 S3 S1 S2 S...

Page 19: ...flow in heating Pressure sensor 63HS Low pressure switch 63L PUHZ SW100VHA PUHZ SW100VHA BS PUHZ SW100YHA PUHZ SW100YHA BS PUHZ SW75VHA UK PUHZ SW75VHA BS UK PUHZ SW120VHA PUHZ SW120VHA BS PUHZ SW120...

Page 20: ...tch to ON again 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation is completed LED1 off LED2 lit be sure to quickly close the gas stop valve If L...

Page 21: ...heck the symptom and check the installation environment refrigerant amount weather when the trouble occurred matters related to wiring and etc 2 Reset error code logs and restart the unit after nishin...

Page 22: ...ard V the noise filter Y Refer to 10 7 4 Check connection of reactor DCL or ACL SW75VHA Check connection of LO and NO on the outdoor noise filter circuit board Check connection of R and S on the outdo...

Page 23: ...oor unit connecting wire Total wiring length 80m including wiring connecting each indoor unit and between indoor and outdoor unit Also check if the connection order of flat cable is S1 S2 S3 3 Check t...

Page 24: ...minutes after and during defrosting 1 Disconnection or contact failure of connector TH4 TH34 on the outdoor controller circuit board 2 Defective thermistor 3 Defective outdoor controller circuit board...

Page 25: ...rd U6 Power module Check abnormality by driving power module in case overcurrent is detected UF or UP error condition 1 Outdoor stop valve is closed 2 Decrease of power supply voltage 3 Looseness disc...

Page 26: ...wiring SW VHA 4 Replace outdoor power circuit board SW VHA 5 Replace outdoor power circuit board SW100 120V YHA 6 Replace outdoor noise filter circuit board SW75VHA 7 Replace outdoor converter circui...

Page 27: ...1 Disconnection of compressor wiring 2 Defective circuit of current sensor on outdoor power circuit board 3 Decrease of power supply voltage 1 Correct the wiring U V W phase to compressor Refer to 10...

Page 28: ...ng abnormality If the unit is not normal after replacing indoor controller board in group control indoor controller board of address 0 may be abnormal 1 Contact failure at transmission wire of remote...

Page 29: ...the other to sub 2 Remote controller is connected with only one indoor unit 3 The address changes to a separate setting 4 6 Diagnose remote controller a When RC OK is displayed remote controllers hav...

Page 30: ...detects Tcond C or more and compressor operation frequency is less than or equal to 25 Hz Detection is inoperative during defrosting 1 Overcharge of refrigerant 2 Defective refrigerant circuit clogs...

Page 31: ...perature adjuster turns on the compressor will not stop operating even if tem perature adjuster is turned off Compressor stops operating immediately when turning off by the remote controller 12Normal...

Page 32: ...nnot be set Are timer settings invalid If the timer can be set WEEKLY SIMPLE or AUTO OFF appears in the remote controller display PLEASE WAIT appears in the remote controller display The initial setti...

Page 33: ...after turning on the main power Normal The start up diagnosis will be over in around 2 minutes Miswiring of indoor outdoor connecting wire Breaking of indoor outdoor connecting wire S3 Defective indoo...

Page 34: ...oard are blown Check the wiring of the outdoor unit Check if the wiring is bad Check if the fuses are blown The fuses on the outdoor controller circuit board will be blown when the indoor outdoor conn...

Page 35: ...oor controller circuit board Replace the outdoor controller circuit board Normal Only the unit which has the refrigerant address 0 supplies power to the remote controller Set the refrigerant address t...

Page 36: ...act of the remote controller wire Check the voltage of the terminal block TB5 connecting the remote controller wire If it is not between DC 10V and DC16V the indoor controller board must be defective...

Page 37: ...r FILTER from the display See the operation manual that came with the product for how to clean the filters STANDBY is displayed on the screen This is displayed when the unit starts HEAT operation when...

Page 38: ...r unit is controlling the airflow amount in order to keep the optimum operating condition A sound similar to water flowing is heard from the unit This is not a malfunction This is the sound which is h...

Page 39: ...airflow direction doesn t change Up down vane left right louver 1 Check if the vane is set to a fixed position Check if the vane motor connector is removed 2 Check if the air conditioner has a functio...

Page 40: ...100YHA BS UK PUHZ SW120YHA BS UK 1 2 3 4 5 M Gray Orange Red Yellow Black Parts name Check points Disconnect the connector then measure the resistance with a tester At the ambient temperature 10 30 Th...

Reviews: