17
8
WIRING SPECIFICATIONS
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity
*1
Main switch (Breaker)
Outdoor unit power supply
Indoor unit-Outdoor unit
*2
Indoor unit-Outdoor unit earth
*2
Remote controller-Indoor unit
*3
Outdoor unit L-N (single)
*4
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
*4
Indoor unit-Outdoor unit S2-S3
*4
Remote controller-Indoor unit
*4
Wir
ing
Wire No
.
o
siz
e (mm
2
)
Circuit rating
SP100, 125V
SP140V
~/N (single), 50 Hz,
~/N (single), 50 Hz,
230 V
230 V
32 A
40 A
3
o
Min. 4
3
o
Min. 6
3
o
1.5 (Polar)
3
o
1.5 (Polar)
1
o
Min. 1.5
1
o
Min. 1.5
2
o
0.3 (Non-polar)
2
o
0.3 (Non-polar)
230 V AC
24 V DC
SP100/125/140Y
3N~ (3ph,4-wires),
50Hz, 400 V
16 A
5
o
Min. 1.5
3
o
1.5 (Polar)
1
o
Min. 1.5
2
o
0.3 (Non-polar)
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker(NV).
*2. Refer to “8-3. INDOOR – OUTDOOR CONNECTING CABLE”.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always necessarily the voltage to ground.
S3 terminal has 24 V DC
against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line
and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is
energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
Power supply
Isolator
A-Control
Indoor Unit
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
230 V AC
230 V AC
230 V AC
230 V AC
230 V AC
24 V DC
24 V DC
12 V DC
12 V DC
12 V DC
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L
B
N
B
Earth leakage breaker
C
wiring circuit breaker or
isolating switch
C