91
OPERATING PROCEDURE
PHOTOS
Photo 4
4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Disconnect the connector TH7/6 (red), on the
controller circuit board in the electrical parts box.
(4)
Loosen the 2 wire clamps on top of the electrical parts box.
(5) Pull out the thermistor <Outdoor 2-phase pipe> (TH6)
from the sensor holder.
Note: In case of replacing thermistor <Outdoor 2-phase
pipe> (TH6), replace it together with thermistor
<Outdoor> (TH7) since they are combined together.
Refer to No.6 below to remove thermistor <Outdoor>.
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Disconnect the connector TH7/6 (red) on the controller
circuit board in the electrical parts box.
(4) Loosen the 2 wire clamps on top of the electrical parts box.
(See Photo 4)
(5) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Note: In case of replacing thermistor <Outdoor> (TH7),
replace it together with thermistor <Outdoor 2-
phase pipe> (TH6), since they are combined together.
Refer to No.5 above to remove thermistor <Outdoor
2-phase pipe>.
Photo 6
Clamp
Thermistor
<Outdoor 2-phase pipe>
(TH6)
6. Removing the thermistor <Outdoor pipe> (TH3) and ther-
mistor <Discharge> (TH4)
(1) Remove the service panel. (See Figure 1)
(2) Disconnect the connectors, TH3 (white) and TH4 (white)
on the controller circuit board in the electrical parts box.
(3) Loosen the clamp for the lead wire in the rear of the elec-
trical parts box.
(4) Remove the soundproof cover (upper) for compressor.
(5) Pull out the thermistor <Discharge> (TH4) from the ther-
mo-holder of the compressor shell.
(6) Pull out the thermistor <Outdoor pipe> (TH3) from the
sensor holder.
Electrical parts box
Photo 5
Soundproof
cover(upper) for
compressor
Thermistor <Outdoor pipe>
(TH3)
Compressor
(MC)
Lead wire of thermistor
<Outdoor>
(TH7)
Sensor holder