38
2-3 HEAT operation
Minimum 3 minutes
w
2
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Booster heater
Compressor
Power ON lamp
STAND BY lamp
ON
ON
LOW or HIGH
LOW or HIGH
ON
ON
OFF
OFF
OFF
OFF
Horizontal
Horizontal
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Extra LOW
w
1
Extra LOW 1
Hot adjustment
From POWER ON until
warm begins to blow
Hot adjustment
Depends on remote
controller setting
Depends on remote
controller setting
w
1 Changeable by indoor
dipswitch SW1- 5
and SW1- 6 .
OFF during thermostat OFF
hot adjustment
defrosting
LOW
Operation starts by
P O W E R b u t t o n
ON.
Operation stops by
P O W E R b u t t o n
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
falls below set tem-
perature.
w
2 Even if the room temperature falls below the set temperature during this period, the compressor will not start until this period
has ended.
<HEAT operation time chart>
<How to operate>
1
Press POWER ON/OFF button.
2
Press the
button to display “
”
3
Press the
TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the
or
button is pressed one time.
Heating 17 to 28°C
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed from the time the heating
operation starts until the heated air begins to blow.
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
AM
PM
TEST RUN
FUNCTION
˚C
TEMP.
WIRED REMOTE
CONTROLLER
WIRELESS REMOTE
CONTROLLER
PLH-3AK.UK
PLH-3AKH.UK
PLH-4, 5, 6AKS.UK
PLH-4, 5, 6AKHS.UK
PLH-3AK
1
.UK
PLH-3AKH
1
.UK
PLH-4, 5, 6AKS
1
.UK
PLH-4, 5, 6AKHS
1
.UK
OC211-A--2.qxp 04.9.28 4:41 PM Page 38