9
Cooling
34,100
10,000(5,000~11,400)
10,000(4,900~11,400)
2.93
0.11
0.52
0.90
Heating
38,200
11,200(5,600~14,000)
11,200(4,500~14,000)
3.25
0.11
0.52
0.90
Single phase, 50Hz, 220-230-240V
Munsell 3.4Y 7.7/0.8
Plate fin coil
Line flow (direct) x 2
0.070
22-28(780-990)
0(direct blow)
Wireless remote controller & built-in
41-46
26(1)
1,680(66-1/8)
235(9-1/4)
340(13-3/8)
28(62)
PUHZ-RP4VHA
PUHZ-RP4VHA
1
PKA-RP4FAL
PKA-RP4FAL
Service Ref.
Item
Btu/h
W
W
kW
kW
A
A
kW
K
/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Operation control & Thermostat
Noise level(Low-High)
Unit drain pipe O.D.
Dimensions
Weight
W
D
H
INDOOR UNIT
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Outdoor
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor
: D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
4. Above data based on indicated voltage
Indoor Unit Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref.
OUTDOOR
UNIT
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
3. Guaranteed voltage
198~264V, 50Hz
PUHZ-RP4VAH
PUHZ-RP4VAH
1
OC301B--1.qxp 13.8.20 3:16 PM Page 9
OC301B