28
Refrigerant piping length (one way)
80m
70m
60m
55m
50m
40m
30m
20m
10m
5m
1.00
1.00
1.00
0.992
0.988
0.985
0.976
0.966
0.957
0.962
0.946
0.931
0.949
0.929
0.908
0.936
0.913
0.886
0.930
0.905
0.876
—
—
0.865
—
—
0.846
—
—
0.829
80m
70m
60m
55m
50m
40m
30m
20m
10m
5m
1.00
1.00
1.00
0.997
0.997
0.997
0.991
0.991
0.991
0.985
0.985
0.985
0.979
0.979
0.979
0.973
0.973
0.973
0.970
0.970
0.970
—
—
0.967
—
—
0.961
—
—
0.955
Service Ref.
PKA-RP3FAL
PKA-RP2.5FAL
Cooling capacity correction factors
Heating capacity correction factors
PKA-RP4FAL
Refrigerant piping length (one way)
Service Ref.
PKA-RP3FAL
PKA-RP2.5FAL
PKA-RP4FAL
Cooling capacity correction factors
Heating capacity correction factors
Service Ref.
PKA-RP2.5FAL
PKA-RP3FAL
PKA-RP4FAL
Refrigerant piping length(one way)
5m
10m
20m
30m
40m
50m
1.00
1.00
1.00
0.989
0.981
0.989
0.970
0.952
0.970
0.950
0.925
0.950
0.930
0.900
0.930
0.910
0.874
0.910
Service Ref.
PKA-RP2.5FAL
PKA-RP3FAL
PKA-RP4FAL
Refrigerant piping length(one way)
5m
10m
20m
30m
40m
50m
1.00
1.00
1.00
0.998
0.998
0.998
0.993
0.993
0.993
0.988
0.988
0.988
0.983
0.983
0.983
0.978
0.978
0.978
5-3. Correction factors
PKA-RP•FAL / PUHZ-RP•VHA
PUHZ-RP•VHA
1
PKA-RP•FAL / PUH-P•VGAA
PUH-P•YGAA
PUH-P•VGAA.UK
PUH-P•YGAA.UK
PU-P•VGAA
PU-P•YGAA
PU-P•VGAA.UK
PU-P•YGAA.UK
PUH-P•VGAA
1
.UK PUH-P•YGAA
1
.UK
PU-P•VGAA
1
.UK
PU-P•YGAA
1
.UK
OC301B--1.qxp 13.8.20 3:16 PM Page 28
OC301B