OC275-25
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con-
troller. Also, the fan runs on LOW speed when the pipe temperature is 43°F or more, or the compressor is OFF and the
pipe temperature is below 43°F.
(a)During compressor OFF
●
When the indoor coil temperature is 43°F or above, the indoor fan will stop.
●
When the indoor coil temperature is below 43°F, the indoor fan will run on LOW speed.
(b)During compressor ON
●
The indoor fan runs on LOW speed.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
(3) Auto vane control
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
Compressor OFF
43
°
F or more
Below 43
°
F
STOP
Pipe temp.
Fan
LOW
All
LOW
Compressor ON
Fan control in DRY operation.
OC275--1.qxp 01/12/14 3:06 PM Page 25