35
Type
Rated current
I
n (A)
Rated insulation voltage Ui (V) AC
Low-inst
Standard
Mag-Only
(
I
nst trip only)
Generator
690V
500V
440V
400V
230V
Frame (A)
AC Breaking
capacity (kA rms)
I
EC60947-2
I
cu/
I
cs
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Solid-state
Adjustable ampere rating
Adjustable short time delay pick up
Fixed instantaneous pick up
Short time delay pick up current
Variation is within
±
10% of the setting current
3-4.5-6
I
n
800
2400-3600-4800
1000
3000-4500-6000
1200
3600-5400-7200
1400
4200-6300-8400
1500
4500-6750-9000
1600
4800-7200-9600
Instantaneous pick up current
20000
NF1600-SS
1600
800-1000-1200-1400-1500-1600
690
25/13
65/33
85/43
85/43
125/63
3
4
3
4
Solid-state
Adjustable ampere rating
Adjustable instantaneous pick up
3
4
Variation is within
±
10% of the setting current
3-4.5-6
I
n
2-3-4
I
n
800
2400-3600-4800
1600-2400-3200
1000
3000-4500-6000
2000-3000-4000
1200
3600-5400-7200
2400-3600-4800
1400
4200-6300-8400
2800-4200-5600
1500
4500-6750-9000
3000-4500-6000
1600
4800-7200-9600
3200-4800-6400
Solid-state
Adjustable ampere rating
Adjustable instantaneous pick up
Variation is within
±
10% of the setting current
3-4.5-6
I
n
2-3-4
I
n
800
2400-3600-4800
1600-2400-3200
1000
3000-4500-6000
2000-3000-4000
1200
3600-5400-7200
2400-3600-4800
1400
4200-6300-8400
2800-4200-5600
1500
4500-6750-9000
3000-4500-6000
1600
4800-7200-9600
3200-4800-6400
3
4
Solid-state
Adjustable ampere rating
Adjustable instantaneous pick up
Variation is within
±
10% of the setting current
3-4.5-6
I
n
800
2400-3600-4800
1000
3000-4500-6000
1200
3600-5400-7200
1400
4200-6300-8400
1500
4500-6750-9000
1600
4800-7200-9600
+4000