26
Type
Low-inst
Standard
Mag-Only
(Inst trip only)
Generator
690V
500V
440V
400V
230V
Frame (A)
Rated insulation voltage Ui (V) AC
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
400A
NF400-SEP
200 ~ 400
adjustable
3
4
Electronic trip relay
Adjustable ampere rating
Adjustable long time delay
operating time, short time delay
pick up and instantaneous
Short time delay pick up current
Variation is within
±
15% of
setting current
2 to 10
I
r
200
400-500-600-700-800-
1000-1200-1400-1600-
2000
225
450-562.5-675-787.5-
900-1125-1200-1500-
1800-1350-1575-1800-
2250
250
500-625-750-875-1000-
1250-1500-1750-2000-
2500
300
600-750-900-1050-1200-
1500-1800-2100-2400-
3000
350
700-875-1050-1225-
1400-1750-2100-2450-
2800-3500
400
800-1000-1200-1400-
1600-2000-2400-2800-
3200-4000
Instantaneous pick up current
Variation is within
±
15% of
setting current
4
I
n ~ 16
I
n
1600 ~ 6400
690
10/10
30/30
42/42
45/45
85/85
Rated current
I
n (A)
AC Breaking
capacity (kA rms)
I
EC60947-2
I
cu/
I
cs
NF400-CP
2
3
Thermal, magnetic
Fixed ampere rating and
instantaneous
250, 300, 350, 400
600
–
15/8
25/13
36/18
50/25
250
2500
±
500
300
3000
±
600
350
3500
±
700
400
4000
±
800
2
3
Thermal, magnetic
Fixed ampere rating and
instantaneous
6
I
n
4
I
n
250 1500
±
300
1000
±
200
300 1800
±
360
1200
±
240
350 2100
±
420
1400
±
280
400 2400
±
480
1600
±
320
2
3
Magnetic
Fixed ampere rating and
instantaneous
250
2500
±
500
300
3000
±
600
350
3500
±
700
400
4000
±
800
–
–
–
NF400-SP
2
3
4
Thermal, magnetic
Fixed ampere rating and
instantaneous
250, 300, 350, 400
690
10/10
30/30
42/42
45/45
85/85
250
3500
±
700
300
4200
±
840
350
4900
±
980
400
5600
±
1120
2
3
4
Magnetic
Fixed ampere rating and
instantaneous
250
2500
±
500
300
3000
±
600
350
3500
±
700
400
4000
±
800
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–