64
E
E
How to check inverter/ compressor
• When heating, room does not get warm.
• When cooling, room does not get cool.
No
No
Yes
Yes
Yes
No
Yes
No
Disconnect the terminal of the compressor.
3 minutes after turning ON the power supply, start
EMERGENCY OPERATION.
Is output balanced?
Clarify the causes by counting time until the inverter stops.
0 to 10 seconds: compressor layer short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
Measure the voltage between each
lead wire leading to the compressor.
U (BLK) - V (WHT)
V (WHT) - W (RED)
W (RED) - U (BLK)
Output voltage
COOL: 150V(48Hz) HEAT: 170V(64Hz)
Is voltage output?
W
1,
W
2
Turn OFF the power supply of indoor and
outdoor unit, and measure the compressor
winding resistance between the compressor
terminals.
Is the resistance between each terminal normal?
Is the input voltage to the outdoor electronic
control P.C. board 370V or more?
Reconnect the lead wire of compressor, and turn ON
the power supply to indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.
Replace the
compressor.
Replace the power board.
W
1 • After the outdoor fan starts running, wait for 1 minute
or more before measuring the voltage.
• The output voltage values have the tolerance of
i
20%.
W
2 • The output differs depending on the capacity or the
number of indoor units to be operated.
OB444C--3.qxp 07.10.18 2:25 PM Page 64
Summary of Contents for MXZ-2A20NA
Page 25: ...25 WIRING DIAGRAM 6 MXZ 2A20NA...
Page 26: ...26 MXZ 2A20NA 1...
Page 27: ...27 MXZ 3A30NA...
Page 28: ...28 MXZ 3A30NA 1...
Page 101: ...101...