4
R410A tools
Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing
gauges.
Hose material has been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
1/4in. and 3/8in.
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use
vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the
refrigerant bubbles due to high pressure and high-speed vaporization.
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Flare gauge
Vacuum pump
adapter
Electronic scale for
refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No
1/2in. and 5/8in.
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
New Specification
Current Specification
The incompatible refrigeration oil easily separates from
refrigerant and is in the upper layer inside the suction muffler.
Raising position of the oil back hole enables to back the
refrigeration oil of the upper layer to flow back to the
compressor.
Since refrigerant and refrigeration oil are compatible,
refrigeration oil goes back to the compressor through the
lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigeration oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigeration oil /Refrigerant
Compressor
-22
-4
14
32
50
68
86
104 122 140
-73
0
73
145
218
290
363
435
508
580
(PSIG)
R410A
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(
-
F
)
OB444C--1.qxp 07.10.18 2:17 PM Page 4
Summary of Contents for MXZ-2A20NA
Page 25: ...25 WIRING DIAGRAM 6 MXZ 2A20NA...
Page 26: ...26 MXZ 2A20NA 1...
Page 27: ...27 MXZ 3A30NA...
Page 28: ...28 MXZ 3A30NA 1...
Page 101: ...101...