background image

33

2. Flow chart of the detailed outdoor unit failure mode recall function

Operational procedure

Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
        2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

W

2.Blinking pattern when outdoor unit is abnormal:

Yes

(Blinks)

No

(OFF)

ON

OFF

No beep

Beeps

Repeated cycle

2.5-second OFF

3-second ON

Blinking at 0.5-
second interval

No beep

Beeps

Repeated cycle

2.5-second OFF

3-second ON

Blinking at 0.5-

second interval

Repeated cycle

W

1. Regardless of normal or abnormal, 2 short

       beeps are emitted as the signal is received.

Does left lamp of OPERATION INDICATOR lamp 
on the indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal.
            Beep are emitted at the same 
            timing as the blinking of the left lamp of 
            OPERATION INDICATOR lamp. 

W

2

Deleting the abnormal memorized condition

1

After repairing the unit, recall the failure mode again according to

    "Setting up the failure mode recall function" mentioned above.

2

Press OPERATE/STOP(ON/OFF) button of the remote controller  (the set temperature is displayed) 

    with the remote controller headed towards the indoor unit.

3

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.

4

Release the failure mode recall function according to "Releasing the failure mode recall function" 

    mentioned above.

Repair the defective parts.

With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 77ºF 

W

1

The outdoor unit is normal.

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures. 
• Turn OFF the power supply and turn it ON again.
• Press RESET button of the remote controller.

The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the
outdoor unit failure mode table (Refer to 10-2.3.).
Make sure to check at least two consecutive blinking cycles.   

W

2

Release the failure mode recall function according 
to the left mentioned procedure.

Confirm that the remote controller is in the failure mode recall
function.

The outdoor unit might be abnormal.
Confirm if outdoor unit is abnormal according to the following procedures.

OB451--2.qxp  06.3.29 9:49 AM  Page 33

Summary of Contents for MUY-A15NA

Page 1: ...K PAGE Wireless type Models MUZ A09NA MUZ A09NA MUZ A12NA MUZ A12NA MUZ A15NA MUZ A15NA MUZ A17NA MUZ A17NA MUZ A24NA MUZ A24NA MUY A15NA MUY A17NA MUY A24NA U1 U1 U1 U1 U1 No OB451 SPLIT TYPE HEAT PU...

Page 2: ...e MUZ09UN MUZ A09NA MUZ12UN MUZ A12NA MUH15TN MUZ A15NA MUH17TN MUZ A17NA MUH24WN MUZ A24NA MU15TN MUY A15NA MU17TN MUY A17NA MU24WN MUY A24NA 1 Outdoor unit model has been changed 2 Control method be...

Page 3: ...le for R410A Yes Substitutable for R410A No 1 2in and 5 8in 1 Tools dedicated for the air conditioner with R410A refrigerant The following tools are required for R410A refrigerant Some R22 tools can b...

Page 4: ...m liquid phase of the gas cylinder If the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the...

Page 5: ...CTIONS 2 Air outlet Drain outlet Piping Drain hose Air inlet back and side MUZ A09NA MUZ A15NA MUY A15NA MUZ A12NA MUZ A17NA MUY A17NA MUZ A24NA MUY A24NA Piping Air outlet Drain hose Drain outlet Air...

Page 6: ...transformer REFRIGERANT PIPING Refrigerant pipe size Min wall thickness Connection method Between the indoor outdoor units Refrigerant charge R410A Refrigerating oil Model Btu h Btu h Btu h W W W V ph...

Page 7: ...indoor outdoor units Refrigerant charge R410A Refrigerating oil Model Btu h Btu h Btu h W W W V phase Hz A A F L A R L A L R A in in in Ib in in ft ft cc 16 200 3 100 16 200 2 070 210 2 070 7 8 16 0...

Page 8: ...transformer REFRIGERANT PIPING Refrigerant pipe size Min wall thickness Connection method Between the indoor outdoor units Refrigerant charge R410A Refrigerating oil Model Btu h Btu h Btu h W W W V p...

Page 9: ...rature Heating at rated compressor Speed Max temperature Heating at minimum compressor Speed High temperature Heating at minimum compressor Speed Frost Accumulation at rated compressor Speed Test Indo...

Page 10: ...re Open two sides of left right or rear side Unit inch MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA MUZ A24NA MUY A24NA 3 0 3 5 6 1 28 3 17 32 7 25 32 1 9 16 20 9 32 11 25 32 2 19 32 2...

Page 11: ...11 WIRING DIAGRAM 5 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA...

Page 12: ...12 MUY A15NA MUY A17NA...

Page 13: ...13 MUZ A24NA...

Page 14: ...14 MUY A24NA...

Page 15: ...00 Expansion valve Ambient temperature thermistor RT65 Muffler Muffler Muffler Unit inch MUZ A09NA MUZ A15NA MUY A15NA MUZ A12NA MUZ A17NA MUY A17NA MUZ A24NA Outdoor heat exchanger Flared connection...

Page 16: ...in cooling Compressor Service port Service port 4 way valve Refrigerant pipe 5 8 with heat insulator Refrigerant pipe 1 4 with heat insulator LEV Muffler 100 Strainer 100 Receiver Outdoor heat exchan...

Page 17: ...10 3 9 4 13 8 12 8 11 7 14 9 13 9 12 6 20 2 18 8 17 2 4 8 5 5 5 9 6 4 7 3 7 9 7 1 8 3 9 2 7 7 9 0 9 9 10 1 11 9 13 1 0 79 0 77 0 73 1 35 1 30 1 24 1 94 1 88 1 79 2 38 2 30 2 19 3 31 3 20 3 05 IWB F 7...

Page 18: ...1 15 1 86 1 83 1 77 2 24 2 19 2 13 2 44 2 40 2 33 12 4 12 7 13 0 15 5 15 8 16 2 20 5 21 0 21 4 22 9 23 4 23 9 26 4 27 0 27 6 0 93 0 91 0 89 1 25 1 23 1 21 1 93 1 90 1 86 2 32 2 28 2 24 2 54 2 49 2 44...

Page 19: ...relationships between frequency and capacity 71 67 63 71 67 63 Outdoor intake air DB temperature F SHF at rating condition 0 71 275CFM Airflow 6 8 7 9 10 11 12 0 9 65 75 85 95 105 115 0 7 0 6 0 8 Ind...

Page 20: ...5 80 85 90 95 100 105 F 90 95 100 105 110 115 120 125 130 135 140 145 150 PSIG Condensing pressure 86 80 75 70 Suction pressure Outdoor ambient temperature Indoor DB temperature F PSIG 86 80 75 70 68...

Page 21: ...95 100 105 F 260 300 340 380 420 460 500 540 580 Indoor DB temperature F Outdoor ambient temperature MSZ A17NA MSY A17NA PSIG Condensing pressure 86 80 75 70 68 70 75 80 85 90 95 100 105 F 80 85 90 95...

Page 22: ...emperature F 75 70 65 PSIG PSIG Condensing pressure Outdoor ambient temperature 14 20 25 30 35 40 45 50 55 60 65 70 F 260 220 180 140 100 300 340 380 460 420 500 540 580 620 Indoor DB temperature F 75...

Page 23: ...20 25 30 35 40 45 50 55 58Hz 58Hz 60 65 70 F 70 60 50 80 90 100 110 120 130 140 150 160 Indoor DB temperature F 75 70 65 PSIG PSIG Condensing pressure Outdoor ambient temperature 14 20 25 30 35 40 45...

Page 24: ...G F F F F ft F F F F rpm CFM F F rpm CFM Cooling 9 000 0 71 0 690 50 0 674 2 80 2 53 363 144 145 107 55 140 80 67 57 56 1 080 275 Wet 95 840 1 094 Cooling 12 000 0 70 1 170 76 1 149 5 08 4 59 395 124...

Page 25: ...flow Unit Btu h kW Hz kW A A kW A A PSIG PSIG F F F F ft F F F F rpm CFM F F rpm CFM Cooling 16 200 0 65 2 07 89 2 040 9 43 8 52 442 106 189 120 40 167 80 67 52 51 1 300 342 Wet 95 950 1 249 Heating 2...

Page 26: ...Comp shell bottom temp Ref pipe length Refrigerant charge R410A Intake air temperature Discharge air temperature Fan speed High Airflow High Intake air temperature Fan speed Airflow Unit Btu h kW Hz k...

Page 27: ...phase 60Hz 2 OPERATION 78 Function Cooling Heating Standard temperature Maximum temperature Minimum temperature Maximum humidity Standard temperature Maximum temperature Minimum temperature DB F 80 95...

Page 28: ...on of Heating capacity Capacity correction factors The operational frequency of compressor Input correction factors MUZ A09NA MUZ A12NA 0 50 100 150 Hz 0 0 0 5 1 0 1 5 0 50 100 150 Hz 0 0 0 5 1 0 1 5...

Page 29: ...tion of Cooling total input The operational frequency of compressor Correction of Heating total input The operational frequency of compressor Correction of Heating capacity The operational frequency o...

Page 30: ...of the compressor ON OFF ON OFF Outdoor fan motor Compressor 5 seconds 15 seconds ON OFF Compressor Outdoor fan motor R V coil MUZ A09 12 15 17 ON OFF ON OFF COOL 5 seconds HEAT 5 seconds ON or OFF O...

Page 31: ...efer to 10 2 and 10 3 10 1 Cautions on troubleshooting 1 Before troubleshooting check the following 1 Check the power supply voltage 2 Check the indoor outdoor connecting wire for mis wiring 2 Take ca...

Page 32: ...e abnormal point with the indoor unit failure mode table Refer to indoor unit service manual Make sure to check at least two consecutive blinking cycles W2 Turn ON the power supply Preparation of the...

Page 33: ...e recall function mentioned above 2Press OPERATE STOP ON OFF button of the remote controller the set temperature is displayed with the remote controller headed towards the indoor unit 3Press EMERGENCY...

Page 34: ...tempe rature thermistor has been 122 F 50 or less for 20 minutes When DC voltage of inverter cannot be detected normally When each phase current of compre ssor cannot be detected normally When 24A A0...

Page 35: ...hree times within 3 minutes after start up When thermistor shorts or opens during compressor running When 28A current flow into intelligent power module When the outdoor heat exchanger temperature exc...

Page 36: ...ompressor is operating When a failure is detected in the operation of the converter during operation When the bus bar voltage exceeds 400V or falls to 200V or below during compressor operating When th...

Page 37: ...compressor Refer to 10 5 G Check of outdoor thermistors Check stop valve Reconnect connector of compressor Refer to 10 5 A How to check inverter compressor Replace inverter P C board Check refrigeran...

Page 38: ...ture protection High pressure protection 8 times Goes out Converter protection Replace the power board Bus bar voltage protection 1 Replace the power board Bus bar voltage protection 2 13 times Goes o...

Page 39: ...following points Check if indoor filters are clogged Check if refrigerant is short Check if indoor outdoor unit air circulation is short cycled Twice Lighting Once Lighting When the discharge tempera...

Page 40: ...ltage 1 Inverter P C board the chart of thermistor Refer to 10 6 Test point diagram and voltage 1 Inverter P C board the chart of thermistor Color of the lead wire Color of the lead wire Discharge tem...

Page 41: ...stance using a tester Part temperature 14 F 104 F R V coil MUZ Measure the resistance using a tester Part temperature 14 F 104 F Linear expansion valve LEV WHT RED YLW BRN ORN BLU Color of lead wire N...

Page 42: ...on the power supply start EMERGENCY OPERATION Is output balanced Clarify the causes by counting time until the inverter stops 0 to 10 seconds compressor rare short 10 to 60 seconds compressor lock 60...

Page 43: ...lligent power module Measurement point at 6 points BLK WHT WHT BLK BLK RED RED BLK WHT RED RED WHT Judgement Infinite Normal 0 dozens of Abnormal short ohmmeter indication Normal infinite Abnormal 0 d...

Page 44: ...A15 17 MUZ A09 12 15 17 MUY A15 17 Check of outdoor thermistors G When OPERATION INDICATOR lamp flashes 6 time The thermistors in the outdoor unit are abnormal Measure the resistance between CN641 1...

Page 45: ...mistor Normal Replace the outdoor electronic control P C board Check of R V coil H Disconnect connector CN61 between the compressor and intelligent power module Turn ON the power supply and press EMER...

Page 46: ...filter P C board Is there normal resistance to R V coil 1 Disconnect the lead wire leading to the compressor 2 3 minutes after turning on the power supply start EMERGENCY OPERATION in COOL mode Is the...

Page 47: ...r fan motor CN931 CN932 Inverter P C board Solder side Turn ON the power supply I I Check of outdoor fan motor Fan motor does not operate or stops operating shortly after starting the operation Yes Ye...

Page 48: ...MUZ A24 MUY A24 MUZ A09 12 15 17 MUY A15 17 Check of power supply J Inverter does not operate Disconnect the connector CN61 between compressor and intelligent power module Turn ON power supply and pre...

Page 49: ...limiting resistor is open the rush current limiting relay X64 may not work properly Outdoor unit does not operate at all or stops immediately due to overcurrent Check of current limiting resistor K C...

Page 50: ...e expansion valve Yes No No Properly fix the LEV to the expansion valve Replace the inverter P C board This figures show about MSZ A09 12 15 17 Turn ON the power supply Preparation of the remote contr...

Page 51: ...hting Lighting 6 time Goes out Check of inverter P C board M Outdoor fan motor does not operate or stops immediately after starting up Yes 10 times flash Yes Check the LED indication on the inverter P...

Page 52: ...r supply Check once more if the indoor outdoor connecting wire is not mis wiring Short circuit outdoor terminal block S2 and S3 W1 B Turn ON the power supply Check the wiring Make them correct Turn OF...

Page 53: ...tdoor unit of the air conditioner indoor outdoor wiring grounding wire antennas wiring from antennas receiver 5 Electric field intensity of the broadcast station affected by the electromagnetic noise...

Page 54: ...rature thermistor RT64 CN642 Ambient temperature thermistor RT65 CN643 Discharge temperature thermistor RT62 CN641 Defrost thermistor RT61 CN641 LEV connector CN724 208 230V AC DB61 Connecting wire wi...

Page 55: ...8 230V AC Back side of unit MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA Front side of unit Connecting wire with inverter P C board CN726 208 230V AC Varistor NR63 Varistor NR62 Varisto...

Page 56: ...ulse wave GND power board CN781 CN795 12V DC pulse wave LEV 4 14 32 10 20 30 40 100 90 80 70 60 50 40 30 20 10 0 32 50 68 84 104 122 140 158 176 200 180 160 140 120 100 80 60 40 20 0 Resistance k Resi...

Page 57: ...208 230V AC 60Hz Input 208 230V AC 60Hz Output CN901 To electronic control P C board MUZ A24NA MUY A24NA F64 FUSE 2A 250V F911 FUSE 1A 250V 4 Noise filter P C board CN902 To power board CN903 To powe...

Page 58: ...ction Connect to the noise filter CN2 Connect to the controller board 1 5 Signal transmission To electronic control P C board 5V DC pulse wave 2 5 Zero cross signal 3 4 Not used 6 5 15V 7 5 15V Signal...

Page 59: ...check if there is a locking lever or not 2 The terminal with this connector has the locking mechanism 1Slide the sleeve 2Pull the terminal while pushing the locking lever 1Hold the sleeve and pull out...

Page 60: ...board CN721 4 way valve coil Inverter P C board CN931 CN932 Fan motor CN641 Defrost thermistor and discharge temperature ther mistor CN643 Ambient temperature thermistor CN724 LEV 4 Remove the compre...

Page 61: ...oving the compressor and 4 way valve 1 Remove the top panel cabinet and service panel Refer to 1 2 Disconnect the power supply and indoor outdoor connecting wire and remove the back panel Refer to 1 3...

Page 62: ...p panel 6 Remove the valve cover 7 Remove the screws of the cabinet 8 Remove the cabinet 9 Remove the screws of the back panel 10 Remove the back panel Photo 2 Photo 1 Photo 3 Screw of the top panel S...

Page 63: ...Remove the inverter assembly 7 Disconnect all connectors and lead wires on the electronic control P C board 8 Remove the electronic control P C board from the inverter assembly 9 Remove the screws fix...

Page 64: ...rature thermistor and ambient temperature thermistor 1 Remove the top panel cabinet and service panel Refer to 1 2 Remove the back panel Refer to 1 3 Remove the inverter assembly Refer to 2 4 Pull out...

Page 65: ...s until the pressure gauge shows 0 PSIG 5 Detach the welded part of the suction and the discharge pipe connected with compressor Photo 9 6 Remove the compressor nuts 7 Remove the compressor 8 Detach t...

Page 66: ...RTS LIST 1 OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS 12 1 PARTS LIST non RoHS compliant 1 2 15 17 12 10 11 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 3 4 5 6 7 8 16 14 18 19...

Page 67: ...STOP VALVE LIQUID SERVICE PANEL BACK PANEL EXPANSION VALVE EXPANSION VALVE COIL 4 WAY VALVE 4 WAY VALVE CONDENSER NET SEPARATOR MOTOR SUPPORT TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER O...

Page 68: ...68 2 OUTDOOR UNIT ELECTRICAL PARTS 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 3 5 6 7...

Page 69: ...7 8 Symbol in Wiring Diagram Q ty unit MUZ MUY A09NA A12NA A15NA A17NA A15NA A17NA DEFROST DISCHARGE 2P 3P Including heat sink and RT64 Including heat sink and RT64 Including heat sink and RT64 Includ...

Page 70: ...70 4 18 1 12 8 10 2 5 7 6 16 14 19 20 21 22 23 28 29 30 3 MUZ A24NA MUY A24NA 3 OUTDOOR UNIT STRUCTURAL PARTS ELECTRICAL PARTS AND FUNCTIONAL PARTS 9 15 17 27 26 25 24 11 13...

Page 71: ...UTDOOR FAN MOTOR PROPELLER CABINET FAN GUARD HANDLE BASE COMPRESSOR RUBBER SET COMPRESSOR STOP VALVE GAS STOP VALVE LIQUID SERVICE PORT EXPANSION VALVE COIL EXPANSION VALVE R V COIL 4 WAY VALVE VALVE...

Page 72: ...2 1 OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS 12 2 RoHS PARTS LIST RoHS compliant 1 2 15 17 12 10 11 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 3 4 5 6 7 8 16 14 18 19 9 13 2...

Page 73: ...A MUY A CABINET GRILLE PROPELLER BASE COMPRESSOR COMPRESSOR COMPRESSOR RUBBER SET STOP VALVE GAS STOP VALVE GAS STOP VALVE LIQUID SERVICE PANEL BACK PANEL EXPANSION VALVE EXPANSION VALVE COIL 4 WAY VA...

Page 74: ...74 2 OUTDOOR UNIT ELECTRICAL PARTS 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 3 5 6 7...

Page 75: ...51 E12 B10 451 E12 B11 451 E12 B12 451 1 2 3 4 5 6 7 8 G G G G G G G G G G G G G G G Symbol in Wiring Diagram Q ty unit MUZ A MUY A 09NA 12NA 15NA 17NA 15NA 17NA DEFROST DISCHARGE 2P 3P Remarks Part N...

Page 76: ...76 4 18 1 12 8 10 2 5 7 6 16 14 19 20 21 22 23 28 29 30 3 MUZ A24NA MUY A24NA 3 OUTDOOR UNIT STRUCTURAL PARTS ELECTRICAL PARTS AND FUNCTIONAL PARTS 9 15 17 27 26 25 24 11 13...

Page 77: ...FAN MOTOR PROPELLER CABINET FAN GUARD HANDLE BASE COMPRESSOR RUBBER SET COMPRESSOR STOP VALVE GAS STOP VALVE LIQUID SERVICE PORT EXPANSION VALVE COIL EXPANSION VALVE R V COIL 4 WAY VALVE VALVE COVER...

Page 78: ...o MAC 851DS Model MUZ A09 12 15 17NA MUY A15 17NA C C Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Apr 2006 No OB451 7 New publication effective Apr 2006 Specifications subject...

Page 79: ...3400 Lawrenceville Suwanee Road Suwanee Georgia 30024 Toll Free 800 433 4822 Toll Free Fax 800 889 9904 www mrslim com Specifications are subject to change without notice...

Reviews: