background image

6

7

OCH706

(3) Repair to intrinsically Safe Components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the 

permissible voltage and current permitted for the equipment in use.

Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmos-

phere. The test apparatus shall be at the correct rating.

Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in 

the atmosphere from a leak.

(4) Cabling 

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse 

environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such 

as compressors or fans.

(5) Detection of Flammable Refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks.

A halide torch (or any other detector using a naked flame) shall not be used.

(6) Leak Detection Methods

Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)

Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equip-

ment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the 

appropriate percentage of gas (25% maximum) is confirmed.

Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be 

avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.

If a leak is suspected, all naked flames shall be removed/extinguished.

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or 

isolated (by means of shut off valves) in a part of the system remote from the leak. For appliances containing flammable 

refrigerants, oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing pro-

cess.

(7) Removal and Evacuation

When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be 

used. However, for flammable refrigerants it is important that best practice is followed since flammability is a considera-

tion. The following procedure shall be adhered to:

• remove refrigerant

• purge the circuit with inert gas

• evacuate

• purge again with inert gas

• open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrig-

erants, the system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several 

times. 

Compressed air or oxygen shall not be used for purging refrigerant systems. 

For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with 

OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to 

a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, 

the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital 

if brazing operations on the pipe-work are to take place. 

Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.

(8) Charging Procedures

In addition to conventional charging procedures, the following requirements shall be followed:

•  Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines 

shall be as short as possible to minimize the amount of refrigerant contained in them.

•  Cylinders shall be kept upright.

•  Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

•  Label the system when charging is complete (if not already).

•  Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-

tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the 

site.

(9) Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its 

detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an 

oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential 

that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.

Summary of Contents for Mr.Slim SUZ-SM71VA.TH

Page 1: ...CIFICATION 10 5 NOISE CRITERIA CURVES 11 6 OUTLINES AND DIMENSIONS 12 7 WIRING DIAGRAM 13 8 REFRIGERANT SYSTEM DIAGRAM 14 9 ACTUATOR CONTROL 15 10 SERVICE FUNCTIONS 16 11 TROUBLESHOOTING 16 12 DISASSE...

Page 2: ...rminal all supply circuits must be disconnected 2 SAFETY PRECAUTION MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT WARNING This mark is for R32 refrigerant only Refrigerant type is written on nameplate of...

Page 3: ...or fire when the unit is being used serviced or disposed of Correct refrigerant is specified in the manuals and on the spec labels provided with our products We will not be held responsible for mechan...

Page 4: ...ous gases will be released 9 Do not use low temperature solder alloy in case of brazing the refrigerant pipes 10 When performing brazing work be sure to ventilate the room sufficiently Make sure that...

Page 5: ...e Refrigeration Equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guide...

Page 6: ...procedures shall be used However for flammable refrigerants it is important that best practice is followed since flammability is a considera tion The following procedure shall be adhered to remove ref...

Page 7: ...o cylinders ensure that only appropriate refrig erant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be...

Page 8: ...ur sides is open and in a sufficiently large space with out depressions 2 4 Minimum installation area If you unavoidably install a unit in a space where all four sides are blocked or there are depress...

Page 9: ...er to the spec nameplate or installation manual For the amount to be added locally refer to the installation manual Install the indoor unit so that the height from the floor to the bottom of the indoo...

Page 10: ...3 Refrigeration oil Model L 0 4 FW68S Fan motor Model RC0J60 BC Current Cooling A 0 83 Heating 0 82 Dimensions W H D mm 840 880 330 Weight kg 55 Special remarks Air flow Cooling High m h 3 426 Med 3 0...

Page 11: ...30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER FREQUENCIES Hz NC 10 Model Item SUZ SM71VA TH Smoothing capacitor C61 C62 C63 CB1 2 3 560 F 450 V Diode modu...

Page 12: ...efrigerant pipe joint Refrigerant pipe flared 9 52 Gas refrigerant pipe joint Refrigerant pipe flared 15 88 350 mm or more 100 mm or more REQUIRED SPACE Basically leave this space open Only if front a...

Page 13: ...13 OCH706 7 WIRING DIAGRAM SUZ SM71VA TH...

Page 14: ...RT68 Ambient temperature thermistor RT65 Strainer 100 Strainer 50 Strainer 100 Muffler Capillary tube 3 0 2 0 200 6 Distributer ADDITIONAL REFRIGERANT CHARGE R32 g MAX REFRIGERANT PIPING LENGTH Max Le...

Page 15: ...e fan motor turns OFF 15 seconds after the compressor has stopped running NOTE The 4 way valve reverses for 5 seconds right before start up of the compressor Sensor Purpose Actuator Compressor LEV Out...

Page 16: ...ABLE and 11 3 HOW TO PROCEED SELF DIAGNOSIS 11 1 CAUTIONS ON TROUBLESHOOTING 1 Before troubleshooting check the following items 1 Check the power supply voltage 2 Check the indoor outdoor connecting w...

Page 17: ...lly Refer to 11 5 How to check in verter compressor 13 time blink 2 5 seconds OFF DC voltage DC voltage of inverter cannot be detected normally Refer to 11 5 How to check in verter compressor Outdoor...

Page 18: ...e will appear will appear if no error history is available 4 Resetting the error history Press the F4 button Reset on the screen that shows the error history A confirmation screen will appear asking i...

Page 19: ...ear on the remote controller display if the correct voltage 8 5 12 V DC is not supplied to the remote control ler If this is the case check the remote controller wiring and indoor units OK No problems...

Page 20: ...er to the indoor unit installation Check code 4 digits or check code 2 digits Error detection attribute Address 3 digits or unit address No 2 digits When there is no error history When opposite side d...

Page 21: ...mal Remote controller switching is necessary When the problem is other than the checked remote controller Error display 2 E3 6833 6832 blink Cannot send Error display 3 ERC and data error count are di...

Page 22: ...sensor emits an intermittent buzzer sound the operation light blinks and the check code is output It takes 3 seconds at most for check code to appear 4 Point the remote controller at the sensor on th...

Page 23: ...tected by unit other than indoor unit outdoor unit etc Symptom 1 Indoor outdoor unit communication error 2 Transmitting error Outdoor unit 3 Open short of outdoor unit thermistors UP U3 U4 14 12 14 Fb...

Page 24: ...ture thermistor RT62 Measure the resistance with a tester Before measurement hold the thermistor with your hands to warm it up Refer to 11 6 TEST POINT DIAGRAM AND VOLTAGE for the chart of thermistor...

Page 25: ...rt the test run and then select the cooling mode For details or for other information about starting the test run when using remote controllers refer to the installation manual for the indoor unit or...

Page 26: ...od Start heating or cooling test run TEST RUN OPERATION Refer to 11 5 Measurement Measure the time from the start of compressor to the stop of compressor due to overcurrent Is the resistance of thermi...

Page 27: ...isconnect connector between the compressor and the intelligent power module Turn ON the power supply and start heating test run TEST RUN OPERATION Refer to 11 5 Disconnect connector between the compre...

Page 28: ...ith a hand Yes Check the outdoor fan motor Refer to Is the fuse F901 blown on the in verter P C board Check the connection of the connectors CN931 CN932 of the outdoor fan mo tor If the connection is...

Page 29: ...or the installation condition combination of specific conditions such as antennas or wiring Check the following before asking for service 1 Devices affected by the electromagnetic noise TV sets radios...

Page 30: ...Yes The refrigerant gas amount may be 60 or less than the normal amount Identify where the gas is leaking from and fix the leak No CAUTION Do not start the operation again to prevent hazards The opera...

Page 31: ...stance k Resistance k Resistance k 11 6 TEST POINT DIAGRAM AND VOLTAGE Inverter P C board SUZ SM71VA TH Fin temperature thermistor RT64 CN673 Ambient temperature thermistor RT65 CN672 Discharge temper...

Page 32: ...A TH Indicates the visible parts in the photos figures Indicates the invisible parts in the photos figures NOTE Turn OFF the power supply before disassembly OPERATING PROCEDURE PHOTOS FIGURES 1 Removi...

Page 33: ...res and the lead wires of the inverter P C board 5 Remove the screws of the P B support 6 Remove the P B support from the relay panel 7 Remove the screws of the inverter P C board 8 Remove the inverte...

Page 34: ...ead wire to the reactor and the following connectors Inverter P C board CN671 Defrost thermistor discharge temperature thermis tor and outdoor heat exchanger temperature ther mistor CN672 Ambient temp...

Page 35: ...Refer to 1 2 Remove the back panel Refer to 1 3 Remove the screws fixing the relay panel 4 Remove the relay panel 5 Remove the inverter assembly Refer to 2 6 Recover gas from the refrigerant circuit...

Page 36: ...ICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO100 8310 JAPAN Copyright 2018 MITSUBISHI ELECTRIC CORPORATION Published Dec 2018 No OCH706 Made in Japan Specifications are subject to change withou...

Reviews: