background image

5

OCH706

[2] Cautions for unit using R32 refrigerant

Basic work procedures are the same as those for conventional units using refrigerant R410A. However, pay careful 

attention to the following points.

(1) Information on servicing 

(1-1) Checks on the Area

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the 

risk of ignition is minimized. 

For repair to the refrigerating systems, (1-3) to (1-7) shall be completed prior to conducting work on the systems.

(1-2) Work Procedure

Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being 

present while the work is being performed.

(1-3) General Work Area

All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. 

Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the con-

ditions within the area have been made safe by control of flammable material.

(1-4) Checking for Presence of Refrigerant

The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is 

aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable 

for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

(1-5) Presence of Fire Extinguisher

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing 

equipment shall be available to hand.

Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

(1-6) No Ignition Sources

No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any 

sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, includ-

ing cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, 

during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around 

the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs 

shall be displayed.

(1-7) Ventilated Area

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any 

hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should 

safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

(1-8) Checks on the Refrigeration Equipment 

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all 

times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s 

technical department for assistance.

The following checks shall be applied to installations using flammable refrigerants:
•  The charge size is in accordance with the room size within which the refrigerant containing parts are installed.

•  The ventilation machinery and outlets are operating adequately and are not obstructed.

•  Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.

•  Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance 

which may corrode refrigerant containing components, unless the components are constructed of materials which are 

inherently resistant to being corroded or are suitably protected against being corroded.

(1-9) Checks on Electrical Devices

Repair and maintenance to electrical components shall include initial safety checks and component inspection proce-

dures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is 

satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an ade-

quate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.

Initial safety checks shall include that:
•  capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;

•  no live electrical components and wiring are exposed while charging, recovering or purging the system;

•  there is continuity of earth bonding 

(2) Repairs to Sealed Components 

(2-1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked 

upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment 

during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn 

of a potentially hazardous situation.

(2-2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not 

altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of 

connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.

Ensure that the apparatus is mounted securely. 

Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of prevent-

ing the ingress of flammable atmospheres. 

Replacement parts shall be in accordance with the manufacturer’s specifications.

Summary of Contents for Mr.Slim SUZ-SM71VA.TH

Page 1: ...CIFICATION 10 5 NOISE CRITERIA CURVES 11 6 OUTLINES AND DIMENSIONS 12 7 WIRING DIAGRAM 13 8 REFRIGERANT SYSTEM DIAGRAM 14 9 ACTUATOR CONTROL 15 10 SERVICE FUNCTIONS 16 11 TROUBLESHOOTING 16 12 DISASSE...

Page 2: ...rminal all supply circuits must be disconnected 2 SAFETY PRECAUTION MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT WARNING This mark is for R32 refrigerant only Refrigerant type is written on nameplate of...

Page 3: ...or fire when the unit is being used serviced or disposed of Correct refrigerant is specified in the manuals and on the spec labels provided with our products We will not be held responsible for mechan...

Page 4: ...ous gases will be released 9 Do not use low temperature solder alloy in case of brazing the refrigerant pipes 10 When performing brazing work be sure to ventilate the room sufficiently Make sure that...

Page 5: ...e Refrigeration Equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guide...

Page 6: ...procedures shall be used However for flammable refrigerants it is important that best practice is followed since flammability is a considera tion The following procedure shall be adhered to remove ref...

Page 7: ...o cylinders ensure that only appropriate refrig erant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be...

Page 8: ...ur sides is open and in a sufficiently large space with out depressions 2 4 Minimum installation area If you unavoidably install a unit in a space where all four sides are blocked or there are depress...

Page 9: ...er to the spec nameplate or installation manual For the amount to be added locally refer to the installation manual Install the indoor unit so that the height from the floor to the bottom of the indoo...

Page 10: ...3 Refrigeration oil Model L 0 4 FW68S Fan motor Model RC0J60 BC Current Cooling A 0 83 Heating 0 82 Dimensions W H D mm 840 880 330 Weight kg 55 Special remarks Air flow Cooling High m h 3 426 Med 3 0...

Page 11: ...30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER FREQUENCIES Hz NC 10 Model Item SUZ SM71VA TH Smoothing capacitor C61 C62 C63 CB1 2 3 560 F 450 V Diode modu...

Page 12: ...efrigerant pipe joint Refrigerant pipe flared 9 52 Gas refrigerant pipe joint Refrigerant pipe flared 15 88 350 mm or more 100 mm or more REQUIRED SPACE Basically leave this space open Only if front a...

Page 13: ...13 OCH706 7 WIRING DIAGRAM SUZ SM71VA TH...

Page 14: ...RT68 Ambient temperature thermistor RT65 Strainer 100 Strainer 50 Strainer 100 Muffler Capillary tube 3 0 2 0 200 6 Distributer ADDITIONAL REFRIGERANT CHARGE R32 g MAX REFRIGERANT PIPING LENGTH Max Le...

Page 15: ...e fan motor turns OFF 15 seconds after the compressor has stopped running NOTE The 4 way valve reverses for 5 seconds right before start up of the compressor Sensor Purpose Actuator Compressor LEV Out...

Page 16: ...ABLE and 11 3 HOW TO PROCEED SELF DIAGNOSIS 11 1 CAUTIONS ON TROUBLESHOOTING 1 Before troubleshooting check the following items 1 Check the power supply voltage 2 Check the indoor outdoor connecting w...

Page 17: ...lly Refer to 11 5 How to check in verter compressor 13 time blink 2 5 seconds OFF DC voltage DC voltage of inverter cannot be detected normally Refer to 11 5 How to check in verter compressor Outdoor...

Page 18: ...e will appear will appear if no error history is available 4 Resetting the error history Press the F4 button Reset on the screen that shows the error history A confirmation screen will appear asking i...

Page 19: ...ear on the remote controller display if the correct voltage 8 5 12 V DC is not supplied to the remote control ler If this is the case check the remote controller wiring and indoor units OK No problems...

Page 20: ...er to the indoor unit installation Check code 4 digits or check code 2 digits Error detection attribute Address 3 digits or unit address No 2 digits When there is no error history When opposite side d...

Page 21: ...mal Remote controller switching is necessary When the problem is other than the checked remote controller Error display 2 E3 6833 6832 blink Cannot send Error display 3 ERC and data error count are di...

Page 22: ...sensor emits an intermittent buzzer sound the operation light blinks and the check code is output It takes 3 seconds at most for check code to appear 4 Point the remote controller at the sensor on th...

Page 23: ...tected by unit other than indoor unit outdoor unit etc Symptom 1 Indoor outdoor unit communication error 2 Transmitting error Outdoor unit 3 Open short of outdoor unit thermistors UP U3 U4 14 12 14 Fb...

Page 24: ...ture thermistor RT62 Measure the resistance with a tester Before measurement hold the thermistor with your hands to warm it up Refer to 11 6 TEST POINT DIAGRAM AND VOLTAGE for the chart of thermistor...

Page 25: ...rt the test run and then select the cooling mode For details or for other information about starting the test run when using remote controllers refer to the installation manual for the indoor unit or...

Page 26: ...od Start heating or cooling test run TEST RUN OPERATION Refer to 11 5 Measurement Measure the time from the start of compressor to the stop of compressor due to overcurrent Is the resistance of thermi...

Page 27: ...isconnect connector between the compressor and the intelligent power module Turn ON the power supply and start heating test run TEST RUN OPERATION Refer to 11 5 Disconnect connector between the compre...

Page 28: ...ith a hand Yes Check the outdoor fan motor Refer to Is the fuse F901 blown on the in verter P C board Check the connection of the connectors CN931 CN932 of the outdoor fan mo tor If the connection is...

Page 29: ...or the installation condition combination of specific conditions such as antennas or wiring Check the following before asking for service 1 Devices affected by the electromagnetic noise TV sets radios...

Page 30: ...Yes The refrigerant gas amount may be 60 or less than the normal amount Identify where the gas is leaking from and fix the leak No CAUTION Do not start the operation again to prevent hazards The opera...

Page 31: ...stance k Resistance k Resistance k 11 6 TEST POINT DIAGRAM AND VOLTAGE Inverter P C board SUZ SM71VA TH Fin temperature thermistor RT64 CN673 Ambient temperature thermistor RT65 CN672 Discharge temper...

Page 32: ...A TH Indicates the visible parts in the photos figures Indicates the invisible parts in the photos figures NOTE Turn OFF the power supply before disassembly OPERATING PROCEDURE PHOTOS FIGURES 1 Removi...

Page 33: ...res and the lead wires of the inverter P C board 5 Remove the screws of the P B support 6 Remove the P B support from the relay panel 7 Remove the screws of the inverter P C board 8 Remove the inverte...

Page 34: ...ead wire to the reactor and the following connectors Inverter P C board CN671 Defrost thermistor discharge temperature thermis tor and outdoor heat exchanger temperature ther mistor CN672 Ambient temp...

Page 35: ...Refer to 1 2 Remove the back panel Refer to 1 3 Remove the screws fixing the relay panel 4 Remove the relay panel 5 Remove the inverter assembly Refer to 2 6 Recover gas from the refrigerant circuit...

Page 36: ...ICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO100 8310 JAPAN Copyright 2018 MITSUBISHI ELECTRIC CORPORATION Published Dec 2018 No OCH706 Made in Japan Specifications are subject to change withou...

Reviews: