background image

9

7.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0M

.

s

Do not carry out this test on the control wiring (low voltage circuit) terminals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0M

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of

the compressor.

2. If the insulation resistance is below 1 M

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3. After connecting the wires to the compressor, the compressor will start to warm

up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

 after the compressor is warmed

up for four hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)

To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 M

, the compressor is not faulty.

 Caution:

The compressor will not operate unless the power supply phase connection
is correct.

• Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can result in

severe damage to internal parts. Keep the power switch turned on during the op-
erational season.

s

The followings must be checked as well.

• The outdoor unit is not faulty. LED1 and LED2 on the control board of the outdoor

unit flash when the outdoor unit is faulty.

• Both the gas and liquid stop valves are completely open.
• A protective sheet covers the surface of the DIP switch panel on the control board of

the outdoor unit. Remove the protective sheet to operate the DIP switches easily.

7. Test run

7.2. Unit replacement operation

s

When reusing existing pipes that carried R22 refrigerant, replacement op-
eration must be performed before performing a test run.

• If new pipes are used, these procedures are not necessary.
• If existing pipes that carried R22 refrigerant are used for RP35-71 models, these

procedures are not necessary. (The replacement operation cannot be performed.)

Replacement operation procedures

1

Supply power.

2

Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start
replacement operation.
* The replacement operation is performed using the cooling system. Cool air will

flow from the indoor unit during the replacement operation.

* During the replacement operation,

 

TEST RUN

 

is displayed on the remote controller

and LED1 and LED2 on the control board of the outdoor unit flash together.

3

The duration of the replacement operation is determined by the length of the pip-
ing. Always perform the replacement operation for longer than the stipulated time.
* Use one of the following methods to complete the replacement operation. When

the replacement operation ends, the unit will automatically stop.

(1) Set SW8-2 from ON to OFF (when ending a replacement operation of less

than 2 hours).

• Because the replacement operation restarts each time SW8-2 is set from

OFF to ON, always perform the replacement operation for longer than the
stipulated time.
Required replacement operation times

(2) Allow the replacement operation to automatically stop after 2 hours (operation

stops while SW8-2 is still in the ON position).

• When the replacement operation has ended automatically after 2 hours of

operation, there is no need to set SW8-2 from ON to OFF; normal air condi-
tioning operation is possible with SW8-2 set to ON. However, to repeat the
replacement operation, SW8-2 first has to be set to OFF and then to ON.

* If the indoor temperature is less than 15°C, the compressor will operate inter-

mittently but the unit is not faulty.

7.3. Test run

7.3.1. Using SW4 in outdoor unit

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

* After performing the test run, set SW4-1 to OFF.
• After power is supplied, a small clicking noise may be heard from the inside of the

outdoor unit. The electronic expansion valve is opening and closing. The unit is not
faulty.

• A few seconds after the compressor starts, a clanging noise may be heard from the

inside of the outdoor unit. The noise is coming from the check valve due to the small
difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during
the test run. (To change the test run operation mode during the test run, stop
the test run by DIP switch SW4-1. After changing the test run operation mode,
resume the test run by switch SW4-1.)

7.3.2. Using remote controller

Refer to the indoor unit installation manual.

Pipe Length

Replacement  Operation Time

0 to 20 meters

30 minutes or more

21 to 30 meters

45 minutes or more

31 to 50 meters

60 minutes or more

8. Initial settings for refrigerant leakage detection function

This air conditioner (outdoor unit) can detect refrigerant leakage which may happen
during a long period of use. In order to enable the leakage detection, the following
settings are required to let the unit menorize the initial conditions (initial learning).

 Caution:

Make sure to perform the “7.Test run” and confirm the unit works without any
problems, before starting the following settings.

s

How to select the “Refrigerant Leakage Detection” mode

Detection is possible regardless the unit’s operation (ON or OFF).

1

Press 

TEST

 button for more than three seconds to switch to the maintenance

mode.
[Display 

A

MAINTENANCE

s

How to start the initial learning

2

Press 

 CLOCK 

 button and select the [GAS LEAK TEST START] (Fig. 8-2)

* The initial learning for the leakage detection is always done once after the new

installtion or the data reset.

[Display 

A

]

Remote control button positions

D

A

C

B

Operation mode

Compressor information Outdoor unit information Indoor unit information

Confirm

Activate/cancel maintenance mode

GAS LEAK
JUDGE

GAS LEAK
TEST START 

Refrigerant leakage
detection judgment

Refrigerant
leakage detection
(initial teaching)

Fig. 8-1

Fig. 8-2

Summary of Contents for Mr.Slim PUHZ-RP HA2

Page 1: ...lish INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PUHZ RP HA2 FOR INSTAL...

Page 2: ...10A to charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and...

Page 3: ...own may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may resu...

Page 4: ...low 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP100 140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional...

Page 5: ...pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more Th...

Page 6: ...lve opening method The stop valve opening method varies according to the outdoor unit model Use the appropriate method to open the stop valves 1 Gas side of RP60 140 Fig 4 5 1 Remove the cap then turn...

Page 7: ...nstalling the refrigerant piping 4 8 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 7 A Indoor unit B Outdoor unit C Multi distribu...

Page 8: ...24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V 1 A breaker with at least 3 0 mm contact separation in each poles shall be provided Use non fuse breaker NF or earth leakag...

Page 9: ...roller and LED1 and LED2 on the control board of the outdoor unit flash together 3 The duration of the replacement operation is determined by the length of the pip ing Always perform the replacement o...

Page 10: ...egins LED1 and LED2 on the control board of the outdoor unit are lit Only set the SWP switch push button type to ON if the unit is stopped How ever even if the unit is stopped and the SWP switch is se...

Page 11: ...1000 100 150 500 1000 200 300 1000 1500 300 500 1000 1500 Max 300 1000 1500 1000 1500 300 500 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2...

Page 12: ...3 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MA...

Reviews: