2. Installation location

1. Safety precautions

1.3. Before electric work

 Caution:

• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a

short circuit, overheating, or fire may result.

• When installing the power lines, do not apply tension to the cables. If the

connections are loosened, the cables can snap or break and overheating or
fire may result.

1.4. Before starting the test run

 Caution:

• Turn on the main power switch more than 12 hours before starting operation.

Starting operation just after turning on the power switch can severely dam-
age the internal parts. Keep the main power switch turned on during the op-
eration season.

• Before starting operation, check that all panels, guards and other protective

parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.

• Do not touch any switch with wet hands. Electric shock may result.

• Be sure to ground the unit. Do not connect the ground wire to gas or water

pipes, lighting rods, or telephone grounding lines. If the unit is not properly
grounded, electric shock may result.

• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and

molded case circuit breaker) with the specified capacity. If the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.

• Do not touch the refrigerant pipes with bare hands during operation. The

refrigerant pipes are hot or cold depending on the condition of the flowing
refrigerant. If you touch the pipes, burns or frostbite may result.

• After stopping operation, be sure to wait at least five minutes before turning

off the main power switch. Otherwise, water leakage or breakdown may re-
sult.

1.5. Using R410A refrigerant air conditioners

 Caution:

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to
page 5) Note the following if reusing existing pipes that carried R22 refriger-
ant.

- Replace the existing flare nuts and flare the flared sections again.
- Do not use thin pipes. (Refer to page 5)

• Store the pipes to be used during installation indoors and keep both ends of

the pipes sealed until just before brazing. (Leave elbow joints, etc. in their
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete-
rioration or compressor breakdown may result.

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil
deterioration may result.

• Do not use refrigerant other than R410A refrigerant. If another refrigerant is

used, the chlorine will cause the oil to deteriorate.

• Use the following tools specifically designed for use with R410A refrigerant.

The following tools are necessary to use R410A refrigerant. Contact your
nearest dealer for any questions.

Tools (for R410A)

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adapter

Torque wrench

Electronic refrigerant charging scale

• Be sure to use the correct tools. If dust, debris, or moisture enters the refrig-

erant lines, refrigeration oil deterioration may result.

• Do not use a charging cylinder. If a charging cylinder is used, the composi-

tion of the refrigerant will change and the efficiency will be lowered.

2.1. Refrigerant pipe (Fig. 2-1)

s

Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are
within the limits shown below.

Models

A

 Pipe length

B

 Height

C

 Number of

 (one way)

difference

bends (one way)

RP35, 50, 60, 71

Max. 50 m

Max. 30 m

Max. 15

RP100, 125, 140

Max. 75 m

Max. 30 m

Max. 15

• Height difference limitations are binding regardless of which unit, indoor or outdoor,

is positioned higher.

D

Indoor unit

E

Outdoor unit

2.2. Choosing the outdoor unit installation location

• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience

neighbors.

• Select a location permitting easy wiring and pipe access to the power source and

indoor unit.

• Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy snow

fall is anticipated, special precautions such as raising the installation location or
installing a hood on the air intake must be taken to prevent the snow from blocking
the air intake or blowing directly against it. This can reduce the airflow and a mal-
function may result.

• Avoid locations exposed to oil, steam, or sulfuric gas.
• Use the transportation handles of the outdoor unit to transport the unit. If the unit is

carried from the bottom, hands or fingers may be pinched.

2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)

The figure in parenthesis is for RP100-140 models.

D

E

C

B

A

Fig. 2-1

Fig. 2-2

RP60-140

RP35, 50

950

330+30

943 (1350)

175

600

370

800

300+23

600

150

69

500

330

Summary of Contents for Mr.Slim PUHZ-RP HA2

Page 1: ...lish INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PUHZ RP HA2 FOR INSTAL...

Page 2: ...10A to charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and...

Page 3: ...own may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may resu...

Page 4: ...low 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP100 140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional...

Page 5: ...pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more Th...

Page 6: ...lve opening method The stop valve opening method varies according to the outdoor unit model Use the appropriate method to open the stop valves 1 Gas side of RP60 140 Fig 4 5 1 Remove the cap then turn...

Page 7: ...nstalling the refrigerant piping 4 8 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 7 A Indoor unit B Outdoor unit C Multi distribu...

Page 8: ...24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V 1 A breaker with at least 3 0 mm contact separation in each poles shall be provided Use non fuse breaker NF or earth leakag...

Page 9: ...roller and LED1 and LED2 on the control board of the outdoor unit flash together 3 The duration of the replacement operation is determined by the length of the pip ing Always perform the replacement o...

Page 10: ...egins LED1 and LED2 on the control board of the outdoor unit are lit Only set the SWP switch push button type to ON if the unit is stopped How ever even if the unit is stopped and the SWP switch is se...

Page 11: ...1000 100 150 500 1000 200 300 1000 1500 300 500 1000 1500 Max 300 1000 1500 1000 1500 300 500 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2...

Page 12: ...3 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MA...

Reviews: