CAUTION
1. Keep the power voltage and capacity within the controller's specification
range. Failure to observe this could lead to damage or faults.
2. For safety purposes, always install a no-fuse breaker or earth leakage
breaker, and shut off when an error occurs or before inspecting. A large
rush current flows when the power is turned ON. Refer to Chapter 6 and
select the no-fuse breaker or earth leakage breaker.
3. For safety purposes, install a magnetic switch that shuts off when an error
occurs. If the converter unit MDS-B-CV is provided in the system, use the
converter's magnetic switch control function. The magnetic switch can be
directly driven by the MDS-B-CV.
6-3-1 Example of connection for controlling magnetic switch (MC) with MDS-B-CV/CR
The following connection example applies when the power supply unit MDS-B-CV/CVE/CR is
provided in the system.
The magnetic switch can also be controlled by the MDS-B-SVJ2/SPJ2. Refer to the respective unit's
specification manual for details.
(1) When sharing a power supply unit and power supply
Power supply
unit
MDS-B-CV/CR
L+
L−
Mitsubishi
CNC
I/F unit
MC
L11
L12
PE
L1
L2
L3
3-phase
200VAC
NFB
Intelligent
servomotor
External
emergency
stop
24VDC
Servo/spindle
drive unit
MDS-B-Vx/SP
L11
L12
MC1
PE
L1
L2
L3
L+
L−
L11
L12
AC reactor B-AL
PE
Terminator
CAUTION
1. The MDS-B-CV is a power supply regenerative type converter; an AC
reactor is required in the power supply line.
Connect the intelligent servomotor main circuit power supply on the power
supply side of the AC reactor.
2. A no-fuse breaker and contactor cannot be shared when the rated current of
the no-fuse breaker exceeds 60A.