10 - 12
10. CC-Link IE CONTROLLER NETWORK CONNECTION
10.4 PLC Side Setting
10.4 PLC Side Setting
This section describes the settings of the GOT and CC-
Link IE controller network module in the following case of
system configuration.
POINT
POINT
POINT
CC-Link IE Controller Network module
For details of the CC-Link IE Controller Network
module, refer to the following manual.
CC-Link IE Controller Network Reference
Manual
System configuration1
(Network Type: CC IE Control)
*1
The CC-Link IE Controller Network module is mounted on
slot 0 of the base unit.
The start I/O No. of the CC-Link IE Controller Network
module is set at [0].
POINT
POINT
POINT
When connecting to Q170MCPU or Q170MSCPU(-S1)
When connected to Q170MCPU or Q170MSCPU(-
S1), the start I/O No. of the CC-Link IE Controller
Network module is set to "70".
System configuration2
(Network Type: CC IE Control extended mode)
*1
The CC-Link IE Controller Network module is mounted on
slot 0 of the base unit.
The start I/O No. of the CC-Link IE Controller Network
module is set at [0].
Parameter settings (Connection to MELSEC-
Q, QS series) of System configuration1
(Network Type: CC IE Control)
(1) [Network parameter] of GX Developer
(a) Network parameter
: Necessary
: As necessary
: Not necessary
*1
When using Q170MCPU or Q170MSCPU(-S1), set it
according to the system configuration.
*2
Specify the same network No. as that of the GOT.
*3
Set the same mode setting as that of the GOT.
<CC-Link IE Controller Network module> *
1
(Use the default value for settings other than the following.)
Station No.
: 1
Mode
: Online
Network type
: CC IE Control (Control station)
Network No.
: 1
Total stations
: 2
Network range assignment :
CC-Link IE Controller Network
<GOT>
(Use the default value for settings other
than the following.)
LB0000
H
to LB00FF
H
LW00000
H
to LW000FF
H
Network type
: CC IE Control
Network No.
: 1
Station No.
: 2
Made Setting : Online (auto,reconnection)
Network range assignment :
Monitor Speed : High
LB0100
H
to LB01FF
H
LW00100
H
to LW001FF
H
■
GT Designer3 [Communication settings] of System
configuration1 (Network Type: CC IE Control)
■
[Network parameter] of GX Developer
<CC-Link IE Controller Network module> *
1
(Use the default value for settings other than the following.)
Station No.
: 1
Mode
: Online
Network type
: CC IE Control extended mode
(Control station)
Network No.
: 1
Total stations
: 2
Network range assignment :
CC-Link IE Controller Network
<GOT>
(Use the default value for settings other
than the following.)
LB0000
H
to LB00FF
H
LW00000
H
to LW000FF
H
Network type
: CC IE Control extended mode
Network No.
: 1
Station No.
: 2
Made Setting : Online (auto,reconnection)
Network range assignment :
Monitor Speed : High
LB0100
H
to LB01FF
H
LW00100
H
to LW001FF
H
Item
Set value
Setting
necessity at
GOT
connection
Network type
CC IE Control
(Control station) (fixed)
Starting I/O No.
*1
0000
H
Network No.
*2
1
Total stations
2
Group No.
0 (fixed)
Station No.
1
Mode
*3
Online
Network range assignment
Refer to (b)
Refresh parameters
(Use default value)
Interrupt settings
Interlink transmission
parameters
Routing parameters
Refer to (c)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......