– 8 –

Use Z1 and Z2 relays having the following specifications.
Operation coil
Rated voltage

:DC12V,DC24V

Power Consumption : 0.9W or less
(*1) Prepare a power supply separately according to the relay

being used. (DC12V or DC24V)

(*2) Always insert a diode on both ends of the relay coil.

Black

Brown

Diode(*2)

Power (*1)
Supply

Z1

Z2

CN 2

Lead wire

Details of each terminal

No.1

Green

Common (External ground)

No.2

Black

ON/OFF

No.3

Brown

Malfunction/normal

No.9

Red

Common (External power supply) (*1)

(3) External input specifications

(A) For level signal

1

 When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the

external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the contact
changes from ON to OFF.

2

 When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact

changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.

(B) For pulse signal

1

 Even if the ON signal is input during ON, the status will remain ON.

2

 If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the local

remote controller will be prohibited.

3

 Set the pulse width (contact ON time) to 0.5 to 1 sec.

(4) Recommended circuit example

1

 The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.

2

 The connection cable can be extended up to 10m. (Use a 0.3mm

2

 or larger wire.)

3

 Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

2. External signal output function

* External signal output requires the external I/o adapter (Model: PAC-YG10HA-E) sold separately.

(1) External output

When one or more air conditioners are running, the “ON” signal will be output and if a malfunction occurs in one or more air
conditioners, the “Malfunction” signal will be shown.

(2) External output specifications

1

 “ON” signal and “Malfunction” signal will both be shown.

(3) Recommended circuit example

1

 Each element will turn on while ON operation or a malfunction occurs.

2

 The connection cable can be extended up to 10m.

3

 The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

CN2

(A) For level signal

Red

Orange

Max.10m

CN2

X1

Run/stop or
Emergency stop

Power supply(*1)
(DC12V or DC24V)

This unit

9

5
6
7
8

X1

9

5
6
7
8

Max.10m

This unit

CN2

Power supply(*1)
(DC12V or DC24V)

X1

X2

Y1

Y2

Red

Orange
Yellow
Blue
Purple

X1
X2
Y1
Y2

Run
Stop
Prohibit
Enable

CN2

Lead wire Emergency stop/normal level signal

ON/OFF, level signal

ON/OFF, prohibit/enable pulse signal

No.5

Orange

Emergency stop/normal input

ON/OFF input

ON input

No.6

Yellow

Not used

Not used

OFF input

No.7

Blue

Not used

Not used

Local remote controller operation prohibit input

No.8

Gray

Not used

Not used

Local remote controller operation enable input

No.9

Red

External DC source “+”

Green

Max.10m

L1:Run display lamp
L2:Malfunction display lamp

This unit

Summary of Contents for G-50A

Page 1: ...ed without fail 1 2 Confirmation of parts 2 3 Outline dimensions 2 4 System diagram 3 5 Installation method 4 1 Part prepared at site 4 2 Installation method 4 6 Initial setting 5 1 Address setting method 5 2 Function selection method 5 3 IP address setting method 6 4 Group setting 6 5 Others 6 7 Test run 7 8 Example for system configuration 7 1 To control a K control model 7 9 External input outp...

Page 2: ......

Page 3: ...function Do not touch the switches with wet hands It may cause an electric shock or malfunction Do not press the switches with sharp objects It may cause an electric shock or malfunction Do not connect an AC power source to the M NET and Power DC12V terminal blocks of this device It may cause a breakdown or fire Ask your dealer or technical representative to install If incorrect installation is do...

Page 4: ...n plate fixing 3 7 Instruction book 1 If the screw enclosed for installation plate fixing cannot be used because the wall is thick prepare an M4 countersunk screw with a length matching the wall thickness Besides the above parts purchase a power supply unit PAC SC50KUA that supplies power DC12V to the central controller and to the M NET transmission line 3 Outline dimensions Installation plate 12 ...

Page 5: ...ant system No 1 unit However for Sub BC controller minimum indoor unit address that connects the lo cal refrigerant piping 50 Same address as indoor unit master unit Set to the minimum indoor unit master address in the same group 100 Address setting is unnecessary After setting all the indoor units set an arbitrary address Min address of K control indoor unit No 200 unit Address 1 50 51 100 52 100...

Page 6: ...y Connect the DC power line from the power supply unit PAC SC50KUA to the DC power supply terminal block of this device There is a 12VDC and a GND polarity Type of wire Use the cables which comply with the following specifications or equivalent M NET transmission line CVVS 1 25mm2 PVC insulated PVCsheathed shield control cable CPEVS ø1 2mm PE insulated PVC sheathed shield communication cable DC po...

Page 7: ...et to ON set the K transmission converter address Move the address and Function setting using the and keys Operation example 1 When the 3 switch was pressed 3 When the BACK SCREEN switch is pressed the screen is returned Function Selection Display OFF Not used Fixed to off OFF Not used Fixed to off OFF K transmission converter not provided ON K trahsmission converter provided OFF Operation prohibi...

Page 8: ...ng to 6 2 Malfunction log monitor function for a detailed description of the functions and settings When all the initial settings are complete initiate startup communication by holding down the and switches on the initial setting menu screen simultaneously for at least 2 seconds After a while the display shifts to the user operation menu screen Refer to the attached instruction book section 5 Init...

Page 9: ...door unit for details on the test run method 20 indoor units for control Group 21 to Group 38 K transmission converter Model PAC SC25KAA 9 External input output usage method 1 External signal input function External signal input requires the external I O adapter Model PAC YG10HA E sold separately 1 External input Emergency stop normal run stop and prohibit enable of local remote controller operati...

Page 10: ... prepared separately at the site 2 The connection cable can be extended up to 10m Use a 0 3mm2 or larger wire 3 Strip the extra cable near the connector and securely insulate the exposed section with tape etc 2 External signal output function External signal output requires the external I o adapter Model PAC YG10HA E sold separately 1 External output When one or more air conditioners are running t...

Page 11: ...tch are accessed For detailed information refer to sections 3 2 and 5 9 of the Instruction Book 4 RS232C connection function When using an RS232C port connect the cable to the RS232C connector of this device The RS232C cable is procured at the site and the connector of the cable that connects to this device is a D Sub9pin female RS 232C cable is maximum 15m When using an RS 232C cable to suppress ...

Page 12: ...OUCHI CHIYODA KU TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Reviews: