Example for system configuration

1. To control a K control model

* Set G-50A address to “000” When a K transmission converter is con-

nected. Always set to the master system controller when the address is
“000”.

* When using a group setting for the K control model, set only the indoor

unit that belongs to that group.

* Set the min.indoor unit address in the group for the K control model group

No.

* Set the master system controller function select No.4 to “OFF” (operation

prohibit transmission valid) when the K transmission controller is con-
nected.

7

Test run

* After setting the group or interlocked setting, confirm that the controller has started up, and then perform a test run.
* It may take approx. 10 minutes for local remote controller operation to be enabled after the power is turned ON. In this case, press the

ON/OFF button on the controller to enable immediate local remote controller operation.

(Test run procedure)

1. Turn ON the Power to the controller and all the units.

2. When the “INITIAL SETTING (PLEASE WAIT)” blink on the controller LCD stops, press the “

1

 ON/OFF switch” and the “tempera-

ture setting switcth  

” at the same time.

3. Confirm the run state (indoor unit outlet air temperature, cool air, confirmation, etc.) during the test run.

4. When each unit has been confirmed, stop the unit with the controller or local remote controller. Even if the units are not stopped, the

test run will stop automatically after approx. 2 hours.

* Refer to the installation manual for the connected indoor unit for details on the test run method.

20 indoor units (for control)
Group 21 to Group 38

K transmission converter
(Model:PAC-SC25KAA)

9

External input/output usage method

1. External signal input function

* External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.

(1) External input

Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air conditioners being
controlled by using a voltage (DC12V or DC24V) contact signal from an external source. (Select with the function select setting)

(2) Level signal and pulse signal (DC12V or DC24V)

No.

1

2

3

4

External signal input function

Do not use external input signal
(factory setting)

Execute emergency stop/normal with
level signal

Perform ON/OFF with level signal

Perform ON/OFF, prohibit/enable with
pulse signals.

Function

No.6

No.7

OFF

OFF

ON

ON

OFF

ON

OFF

ON

Remarks

The local remote controller ON/OFF operations, and the
controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.

The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.

Set the pulse width while the contact is ON to 0.5 to 1 sec.

(A) Level signal

Contact ON

Contact OFF

Contact ON

Contact OFF

Stop

Run

Stop

Normal

Normal

Emergency stop

(B) Pulse signal

Contact ON

Contact OFF

(Example) for ON/OFF

0.5 to 1 sec

0.5 to 1 sec

Contact ON

Contact OFF

Signal 1(run)

Signal 2(stop)

OFF

ON

OFF

*The prohibit/enable input is the same.

20 indoor units
Group 1 to Group 10

Power supply unit
(Model PAC-SC50KUA)

DC12V

M-NET

G-50A

(Master system controller)

Summary of Contents for G-50A

Page 1: ...ed without fail 1 2 Confirmation of parts 2 3 Outline dimensions 2 4 System diagram 3 5 Installation method 4 1 Part prepared at site 4 2 Installation method 4 6 Initial setting 5 1 Address setting method 5 2 Function selection method 5 3 IP address setting method 6 4 Group setting 6 5 Others 6 7 Test run 7 8 Example for system configuration 7 1 To control a K control model 7 9 External input outp...

Page 2: ......

Page 3: ...function Do not touch the switches with wet hands It may cause an electric shock or malfunction Do not press the switches with sharp objects It may cause an electric shock or malfunction Do not connect an AC power source to the M NET and Power DC12V terminal blocks of this device It may cause a breakdown or fire Ask your dealer or technical representative to install If incorrect installation is do...

Page 4: ...n plate fixing 3 7 Instruction book 1 If the screw enclosed for installation plate fixing cannot be used because the wall is thick prepare an M4 countersunk screw with a length matching the wall thickness Besides the above parts purchase a power supply unit PAC SC50KUA that supplies power DC12V to the central controller and to the M NET transmission line 3 Outline dimensions Installation plate 12 ...

Page 5: ...ant system No 1 unit However for Sub BC controller minimum indoor unit address that connects the lo cal refrigerant piping 50 Same address as indoor unit master unit Set to the minimum indoor unit master address in the same group 100 Address setting is unnecessary After setting all the indoor units set an arbitrary address Min address of K control indoor unit No 200 unit Address 1 50 51 100 52 100...

Page 6: ...y Connect the DC power line from the power supply unit PAC SC50KUA to the DC power supply terminal block of this device There is a 12VDC and a GND polarity Type of wire Use the cables which comply with the following specifications or equivalent M NET transmission line CVVS 1 25mm2 PVC insulated PVCsheathed shield control cable CPEVS ø1 2mm PE insulated PVC sheathed shield communication cable DC po...

Page 7: ...et to ON set the K transmission converter address Move the address and Function setting using the and keys Operation example 1 When the 3 switch was pressed 3 When the BACK SCREEN switch is pressed the screen is returned Function Selection Display OFF Not used Fixed to off OFF Not used Fixed to off OFF K transmission converter not provided ON K trahsmission converter provided OFF Operation prohibi...

Page 8: ...ng to 6 2 Malfunction log monitor function for a detailed description of the functions and settings When all the initial settings are complete initiate startup communication by holding down the and switches on the initial setting menu screen simultaneously for at least 2 seconds After a while the display shifts to the user operation menu screen Refer to the attached instruction book section 5 Init...

Page 9: ...door unit for details on the test run method 20 indoor units for control Group 21 to Group 38 K transmission converter Model PAC SC25KAA 9 External input output usage method 1 External signal input function External signal input requires the external I O adapter Model PAC YG10HA E sold separately 1 External input Emergency stop normal run stop and prohibit enable of local remote controller operati...

Page 10: ... prepared separately at the site 2 The connection cable can be extended up to 10m Use a 0 3mm2 or larger wire 3 Strip the extra cable near the connector and securely insulate the exposed section with tape etc 2 External signal output function External signal output requires the external I o adapter Model PAC YG10HA E sold separately 1 External output When one or more air conditioners are running t...

Page 11: ...tch are accessed For detailed information refer to sections 3 2 and 5 9 of the Instruction Book 4 RS232C connection function When using an RS232C port connect the cable to the RS232C connector of this device The RS232C cable is procured at the site and the connector of the cable that connects to this device is a D Sub9pin female RS 232C cable is maximum 15m When using an RS 232C cable to suppress ...

Page 12: ...OUCHI CHIYODA KU TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Reviews: