44
FX
3U
-32DP PROFIBUS-DP Interface Block
User’s Manual
6 Buffer Memory Allocation
6.19 Setting Error Flag [BFM #38]
6.19
Setting Error Flag [BFM #38]
BFM Access : Read / Write (Valid Value : 0 bitwise)
This BFM shows the setting error reasons. This BFM corresponds to BFM#29 Bit6. By resetting BFM#29 Bit6,
BFM#38 also resets. By writing 0 to each bit in BFM#38, each flag resets individually.
*1.
If writing "0" to BFM#1298 when the 32DP is not in data exchange mode, the 32DP keeps BFM#1309
- #1322 contents, whereas the 32DP clears them at the next mode switch into data exchange mode.
→
For details on BFM#36, refer to Section 6.17
→
For details on BFM#99, refer to Section 6.21
→
For details on BFM#299, refer to Section 6.24
→
For details on BFM#499, refer to Section 6.26
→
For details on BFM#699, refer to Section 6.28
→
For details on BFM#899, refer to Section 6.30
→
For details on BFM#1099, refer to Section 6.32
→
For details on BFM#98, refer to Section 6.20
→
For details on BFM#298, refer to Section 6.23
→
For details on BFM#1298, refer to Section 6.34
→
For details on BFM#1299, refer to Section 6.35
→
For details on BFM#1300, refer to Section 6.36
Bit No.
Description
Bit 0
ON when writing to " Not Available " or " Read Only " BFMs
Bit 1
ON when writing an incorrect value to [BFM#36 Start/Stop DP-Communication]
(Valid write value for BFM#36: 0 or 1)
Bit 2
Not Available
Bit 3
Not Available
Bit 4
ON when writing an incorrect value to [BFM#99 Cyclic Input Data Send Flag]
(Valid write value for BFM#99: 0 only)
Bit 5
ON when writing an incorrect value to [BFM#299 Cyclic Output Data Read Flag]
(Valid write value for BFM#299: 0 only)
Bit 6
ON when writing an incorrect value to [BFM#499 Acyclic Input Data Send Flag(Class1)]
(Valid write value for BFM#499: 0 only)
Bit 7
ON when writing an incorrect value to [BFM#699 Acyclic Output Data Read Flag(Class1)]
(Valid write value for BFM#699: 0 only)
Bit 8
ON when writing an incorrect value to [BFM#899 Acyclic Input Data Send Flag(Class2)]
(Valid write value for BFM#899: 0 only)
Bit 9
ON when writing an incorrect value to [BFM#1099 Acyclic Output Data Read Flag(Class1)]
(Valid write value for BFM#1099: 0 only)
Bit 10
ON when writing an incorrect value to [BFM#98 Cyclic Input Data Consistency Activate/Deactivate Flag]
(Valid write value for BFM#98: 0 or 1)
Bit 11
ON when writing an incorrect value to [BFM#298 Cyclic Output Data Consistency Activate/Deactivate Flag]
(Valid write value for BFM#298: 0 or 1)
Bit 12
*1
ON when writing an incorrect value to [BFM#1298 Reset Extended User-Diagnostic/Alarm Data Area Flag]
(Valid write value for BFM#1298: 0 only)
ON when writing "0" to BFM#1298
before the DP-Master acknowledges all the Alarm Messages
ON when writing "0" to BFM#1298 while BFM#1298 is "0"
ON when writing "0" to BFM#1298 while BFM#1309 to #1322 are already "0"
Bit 13
ON when writing an incorrect value to [BFM#1299 Alarm/Status Switch]
(Valid write value for BFM#1299: 0 or 1)
ON when BFM#1299 turns ON while BFM#35 Bit0 = 0 (DP-V1 disabled)
ON when the DP-Master does not recognize the Alarm(Status) Message from the 32DP
ON when the DIA LED is ON (Any value in BFM#28, #29, #1298 and #1300 is not "0")
ON when a process error occurs in sending a User-Diagnostic/Alarm(Status) Message
Bit 14
ON when writing an incorrect value to [BFM#1300 Diagnostic/Alarm Immediate Send Flag]
(Valid write value for BFM#1300: 1 only)
Bit 15
ON when writing an incorrect value to [BFM#25
DP Communication Status Register
]
(Valid write value for BFM#25: FEFFh only)
Summary of Contents for FX3U-32DP
Page 1: ...USER S MANUAL FX3U 32DP PROFIBUS DP Interface Block ...
Page 2: ......
Page 6: ... iv ...
Page 73: ......