The 32DP classifies the diagnostic data into two categories : Alarm Message and Status Message. When the
32DP’s DP-V1 functionality is ON (BFM#35 Bit0 = 1) and the Alarm/Status Switch is OFF (BFM#1299 Bit0 =
0), the 32DP can send a diagnostic message as a high-prioritized Alarm Message. This Alarm Message from
the 32DP needs to be acknowledged by the DP-Master. If this alarm-acknowledging step is not necessary,
the 32DP can send a diagnostic message as a low-prioritized Status Message when users set the Alarm/
Status Switch (BFM#1299 Bit0 = 1).
The content of BFM#1299 Bit0 is mapped to BFM#35 Bit2.
Note
If BFM#1299 Bit 0 turns to 1 when BFM#35 Bit0 = 0, BFM#38 Bit13 displays " BFM#1299 Setting Error."
→
For flag allocations, refer to Chapter 6
→
For details on Slave Diagnostic Data, refer to Chapter 6
5.3.1
Diagnostic Data Communication
Diagnostic Data Communication is always processed in the Data Consistency mode, regardless of the
BFM#98 setting.
→
For details on Diagnostic Data related flags, refer to Chapter 6
DP Slave
DP Slave
DP Master
PROFIBUS-DP Network
DP Slave
FX
3U
-32DP
Read
*1
Write
*2
Buffer Memory
Diagnostic/Alarm
(Status) Data Area
Diagnostic/Alarm
Immediate Send Flag
BFM #1300
The 32DP sends Alarm Message to the DP-Master
The DP-Master acknowledges Alarm Message
FROM or RBFM applied instructions,
directly specifying BFMs
TO or WBFM applied instructions,
directly specifying BFMs
*1
*2
FX
3G
/FX
3GC
/
FX
3U
/FX
3UC
/
FX5U/FX5UC PLC
ON
Diagnostic/Alarm immediate
Flag (BFM#1300)
Writing data to the
Diagnostic/Alarm Data Area
(BFM#1309 to #1322)
Write
Do not write to the
32DP's Diagnostic/
Alarm(Status) Data
Area for this
duration
Must be set ON by user program
Is automatically reset after send of data
:
: