4.8 Procedure of battery exchange

1) The power supply of FX

2N

-20GM is turned off. 

2) Remove side cover from the FX

2N

-20GM.

3) Remove battery from holder-disconnect and replace. (This must be carried out within 30 sec if the cur-

rent data held in the FX

2N

-20GM’s RAM is to be saved.)

4) Refit battery and cover.

FX

2NC

-32BL

lithium battery

5. Specification

5.1 Power supply specification

5.2 General specification

5.3 Performance specification

Item

Contents

Power supply

24V DC -15%, +10%

Allowance power 
failure time

The operation is continued to the momentary power failure is 5ms or less. 

Power consumption 

10W

Fuse

125V AC      1A

Item

Contents

Ambient temperature

0 to 55

°

C (operation). -20 to 70

°

C (storage).

Surrounding humidity 35 to 85 %, No condensation (operation). 35 to 90 % (storage).

Vibration resistance

Conforms to JIS C0040. 10 to 57Hz: Half 0.035mm amplitude,

                                        57 to 150Hz: 4.9 m/s

2

 Acceleration 

Sweep count for X, Y, Z: 10 times (80 min in each direction).

Shock resistance

Conforms to JIS C0041. 147m/s

2

 acceleration, Action time: 11ms.

3 times in each direction X, Y, Z.

Noise immunity

1,000Vp-p, 1

µ

s. 30 to 100Hz, tested by noise simulator.

Dielectric withstand 
voltage

500V AC > 1 min, tested between all points, terminal and ground.

Insulation resistance

5M

 > 500V DC, tested between all points, terminal and ground

Ground Class 

(100

 or less)

Use atmosphere

Ambient conditions to be free of corrosive gases. Dust should be minimal.

Item

Contents

Number of control 
axes

Two axes (two axes or two independent axes simultaneously)

Interpolation function

There is a straight line interpolation and a circular arc interpolation (two axes 
simultaneously). 

Application PLC

Bus connection with FX

2N

 and the FX

2NC

 series PLC. The number of I/O points 

occuupied is 8 points. An FX

2NC

-CNV-IF is necessary for the connection with 

the FX

2NC

 series PLC.

Program memory

Built-in RAM, FX

2NC

-EEPROM-16 (optional memory board) : 7.8k steps. 

Memory board with clock function cannot be used.

Battery

With built-in FX

2NC

-32BL type lithium battery.

Longevity and about three years (The guaranteed term is one year). 

Positioning unit

Command units: mm, deg, inch, pls, (relativity/absolutely)
Max command value ± 999,999 (32 bits when indirectly specifying)

Accumulation 
address

-2,147,483,648 to 2,147,483,647pulses

Speed instruction

200kHz max., 153,000cm/min (200kHz or less). Automatic trapezoidal pattern 
acceleration/deceleration (The interpolation drive is 100kHz or less).

Zero return

Manual operation or automatic operation. The DOG type machine zero return  
(The DOG search function is provided). An automatic electric zero return is 
possible by the electric starting point setting. 

* 1:When the file register is used, it is necessary to set PARA.101. 

5.4 Input specifications

*1:The selection of general purpose inputs, manual pulse generator inputs or interrupt inputs in the

parameter settings automatically adjusts the input filters.

Absolute position 
detection

The absolute position detection is possible with MR-J2 and the MR-H type 
servo motor with the ABS detection function. 

Control inputs

Operation system: FWD (manual forwarding ), RVS (manual reversal)
     ZRN (machine zero return), START (automatic start), STOP,
     Manual pulse generator (2kHz max), Single-step operation input
     (Depends upon the parameter setting).
Mechanical system: DOG (near-point signal),
     LSF (forward rotation limit), LSR (reverse rotation limit),
     Interrupt: 4 points
Servo system: SVRDY (servo ready), SVEND (servo end),
     PG0 (zero-point signal)

General purpose: The main body has X0 to X7. X10 to X67 can be input by 
using the extension block. (max I/O point: 48 points)

Control outputs

Servo system: FP (forward rotation pulse). RP (reverse rotation pulse),
CLR (counter clear).

General purpose: The main body has Y0 to Y7. Y10 to Y67 can be output by 
using the extension block. (max I/O point: 48 points)

Control method

Program method: The program is written in the FX

2N

-20GM by a special 

programming tool, and the positioning control is done. 

Program No.

O00 to O99 (two axes simultaneously), Ox00 to Ox99 and Oy00 to Oy99 (two 
independent axes), O100 (sub-task program)

Instruc-
tion

Positioning

Cod No. system (used with instruction cods)-19 types.

Sequence

LD, LDI, AND, ANI, OR, ORI, ANB, ORB, SET, RST and NOP.

Application

FNC number system-30 types.

Parameter

System setting-12 types. Positioning-27 types. I/O Control-19 types.

Settings in the program can be changed by using a special data register
(The system settings are excluded)

m cods

m00: Program stop (WAIT), m02: (End of positioning program), m01 and m03 
to m99 can be arbitrarily used. (AFTER mode and WITH mode)
m100 (WAIT) and m102 (END) are used by a sub-task. 

Device

Inputs: X0 to X67, X372 to X377   Outputs:Y0 to Y67,
Supplementary relay: M0 to M99 (general purpose), M100 to M511 (general 
purpose and battery backup area), M9000 to M9175 (special),  Pointer:P0 to 
P255, Data register: D0 to D99 (general purpose), D100 to D3999 (general 
purpose and battery backup area) (16 bits), D4000 to D6999 (file register and  

battery backup area)

*1

 D9000 to D9599 (special)

Index: V0 to V7 (16 bits), Z0 to Z7 (32 bits)

Self-diagnosis

"Parameter error", "Program error", and "External error" can be diagnosed by 
the display and the error code. 

Item

Input from general-purpose

equipment

Input from drive unit

Input 
signal 
name

Group 1

START, STOP, ZRN, FWD, RVS, LSF, LSR 

SVRDY, SVEND

Group 2

DOG 

PG0

Group 3

General-purpose input X00 to X07

-

Group 4

Manual pulse generator, interruption input

-

Circuit insulation

By photocoupler

By photocoupler

Operation indication

LED is lit while input is ON

LED is lit while input is ON

Signal voltage

24V DC ± 10% (internal power supply)

5 to 24V DC ± 10%

Input current

7mA/24V DC

7mA/24V DC (PG0 11.5mA/24V DC)

Input ON current

4.5mA or more

0.7mA or more (PG0 1.5mA or more)

Input OFF current

1.5mA or less

0.3mA or less (PG0 0.5mA or less)

Signal format

Contact input or NPN open collector transistor input.

Responset
ime

Group 1

Approx. 3msec

Approx. 3msec

Group 2

Approx. 0.5msec

Approx. 16

µ

s

Group 3

Approx. 3msec

*1

-

Group 4

Approx. 0.1ms

*1

-

Turning ON rate of 
I/O simultaneously

50% or less

Item

Contents

5.5 Output specification

Item

General-purpose output

Output to drive unit

Signal name

Y00 to Y07

FP, RP, CLR

Circuit isolation

By photocoupler

By photocoupler

Operation indication

LED is lit while output is ON

LED is lit while output is ON

External power 
supply

5 to 24V DC ± 10%

5 to 24V DC ± 10%

Load current

50mA or less

20mA or less

Open circuit leak 
current

0.1mA/24V DC or less

0.1mA/24V DC or less

Output ON voltage

0.5V max

0.5V max (CLR is 1.5V max.)

Response time

0.2ms max. for both OFF 

 ON and 

ON 

→ 

→ 

→ 

→ 

OFF.

Pulse output FP RP is 200kHz max.
Pulse output width of the CLR signal:
Approx. 20msec. 

Turning ON rate of 
I/O simultaneously

50% or less

Guidelines for the safety of the user and protection of the FX

2N

-20GM 

POSITIONING CONTROLLER

This manual has been written to be used by trained and competent personnel. This is defined
by the European directives for machinery, low voltage and EMC.

If in doubt at any stage during the installation of the FX

2N

-20GM always consult a professional

electrical engineer who is qualified and trained to the local and national standards. If in doubt
about the operation or use of the FX

2N

-20GM please consult the nearest Mitsubishi Electric

distributor. 

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment. 

All examples and diagrams shown in this manual are intended only as an aid to understand-
ing the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for
actual use of the product based on these illustrative examples. 

Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application. 

Manual number : JY992D77601

Manual revision : C

Date

: November 2005

JY992D77601C

Effective Nov. 2005

Specifications are subject to change without notice.

Summary of Contents for FX2N-20GM

Page 1: ...to both axes and switched as required The manual pulse generators must be an open collector output type The zero return operation at each start can be omitted with a servo amplifier with the absolute position ABS detection function The FX2N 20GM can be used alone When an FX2N 20GM is connected with an FX2N or FX2NC series Programmable controller hereafter call PLC reading and writing the positioni...

Page 2: ...hen power is supplied If LED is not lit check power supply voltage and current READY X LED lights when accepting an x axis instruction During pulse output or when an error occurs the LED is off READY Y LED lights when accepting a y axis drive instruction During pulse output or when an error occurs the LED is off ERROR X LED is lit or blinks when an error occurs in the positioning drive of x axis E...

Page 3: ...X2N 16EYT ESS UL The increase point is 48 points or less Assume the turning on rate to be 50 or less simultaneously 48 points may be added to the system if 50 or less are used simultaneously Extension block FX2N 20GM lock lock 1 Detach the extension cover on the right side of the FX2N 20GM 2 Insert the hooks of the extension blocks into the lock holes and gently press the units together 3 lower th...

Page 4: ...of I O points occuupied is 8 points An FX2NC CNV IF is necessary for the connection with the FX2NC series PLC Program memory Built in RAM FX2NC EEPROM 16 optional memory board 7 8k steps Memory board with clock function cannot be used Battery With built in FX2NC 32BL type lithium battery Longevity and about three years The guaranteed term is one year Positioning unit Command units mm deg inch pls ...

Page 5: ...ystem setting 12 types Positioning 27 types I O Control 19 types Settings in the program can be changed by using a special data register The system settings are excluded m cods m00 Program stop WAIT m02 End of positioning program m01 and m03 to m99 can be arbitrarily used AFTER mode and WITH mode m100 WAIT and m102 END are used by a sub task Device Inputs X0 to X67 X372 to X377 Outputs Y0 to Y67 S...

Page 6: ...C 10 Load current 50mA or less 20mA or less Open circuit leak current 0 1mA 24V DC or less 0 1mA 24V DC or less Output ON voltage 0 5V max 0 5V max CLR is 1 5V max Response time 0 2ms max for both OFF ON and ON OFF Pulse output FP RP is 200kHz max Pulse output width of the CLR signal Approx 20msec Turning ON rate of I O simultaneously 50 or less Guidelines for the safety of the user and protection...

Page 7: ... board s Connector for PLC 4 2 Operation display The state of FX2N 20GM is displayed by LED Name of LED Content POWER LED lights when power is supplied If LED is not lit check power supply voltage and current READY X LED lights when accepting an x axis instruction During pulse output or when an error occurs the LED is off READY Y LED lights when accepting a y axis drive instruction During pulse ou...

Page 8: ...ter clear General purpose The main body has Y0 to Y7 Y10 to Y67 can be output by using the extension block max I O point 48 points Control method Program method The program is written in the FX2N 20GM by a special programming tool and the positioning control is done Program No O00 to O99 two axes simultaneously Ox00 to Ox99 and Oy00 to Oy99 two independent axes O100 sub task program Instruc tion P...

Reviews: