FX1S Series Programmable Controllers
Installation Notes 3
3-4
3.3
General Specifications
Table 3.3: General Specifications
Item
Description
Operating Temperature
0 to 55 °C (32 to 131 °F)
Storage Temperature
-20 to 70 °C (-4 to 158 °F)
Operating Humidity
35 to 85% Relative Humidity, No condensation
Storage Humidity
35 to 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
Conforms to EN 68-2-6; 10 - 57 Hz: 0.075 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance
- DIN Rail Mounting
Conforms to EN 68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude
57 - 150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Shock Resistance
Conforms to EN 68-2-27: 147m/s
2
Acceleration, Action Time: 11 ms
3 times in each direction X, Y, and Z
Noise Immunity
1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
Dielectric
Withstand Voltage
AC PSU: 1500 VAC > 1 min., tested between all points, terminals, and ground
DC PSU: 500 VAC > 1 min., tested between all points, terminals and ground
Insulation Resistance
5 M
Ω
> at 500 V DC, tested between power terminals and ground
Ground
Grounding resistance 100
Ω
or less
Certification
UL/cUL (UL508)
EC Directive
EMC(EN61000-6-2, EN50081-2), LVD(EN61010-1)