FX-20P-E Handy programming panel
Startup Procedure 2
2-5
2.2.2
Parameter settings
In parameter settings, leave the latch range, the memory capacity, the file register capacity in
the default status respectively.
1) Setting the memory capacity
a) Program capacity: Select 2k steps.
Do not select any other number of steps.
If the program capacity is set to more than 2k steps, when a program is transferred to the
PLC, the message "HPP PARA. ERROR" is displayed, and the program is not written.
When using theFX
0
/FX
0S
Series PLC, make a program of less than 800 steps.
If a program of 800 steps or more is written to the FX
0
/FX
0S
Series PLC, it is ignored and
is not written.
If the program capacity is set to 2k steps, the NOP instruction is automatically set to a
program of 800 steps or more when it is read from the FX
0
/FX
0S
Series PLC.
b) File register: Do not set the file register capacity. (only when using FX
0
/FX
0S
)
If the file register capacity is set, when a program is written to the FX
0
/FX
0S
Series PLC,
the message "WRITE ERROR" is displayed, and the program is not written.
2) Setting the latch range
The latch range cannot be changed in the FX
0
/FX
0S
/FX
0N
/FX
1S
/FX
1N
Series PLC.
If the latch range is set (changed), when a program is written to the FX
0
/FX
0S
/FX
0N
/FX
1S
/
FX
1N
Series PLC, the message "COMPLETED" is displayed. Though the program is written,
the PLC ignores the set latch range.
3) Registering the entry code
The entry code can be registered.
Summary of Contents for FX-20P-E
Page 1: ...OPERATION MANUAL FX 20P E HANDY PROGRAMMING PANEL...
Page 4: ...FX 20P E Handy programming panel ii...
Page 8: ...FX 20P E Handy programming panel vi...
Page 20: ...FX 20P E Handy programming panel Notes to Users 1 1 6 1 6 Name of each part FX 20P E...
Page 120: ...FX 20P E Handy programming panel A 2 MEMO...
Page 126: ...FX 20P E Handy programming panel B 6 MEMO...
Page 127: ......