Message List 11
11-5
LADDER ERR
6607
1) Illegal FOR and NEXT designation
Nesting level deeper than 5 levels
2) One of the following commands is designated in the FOR-NEXT loop.
STL, RET, MC, MCR, IRET, SRET, FEND, END
6608
1) Illegal MC and MCR designation
2) No MCR N0
3) One of the following commands is designated in the MC-MCR loop.
SRET, IRET, I (interrupt)
6609
Other
RUNTIME ERROR *
6701
No jump destination of CJ or CALL. A label follows after the END
instruction. An independent label is in the FOR-NEXT loop or a
subroutine program.
6702
CALL nesting level deeper than 5 levels
6703
Interrupt nesting level deeper than 2 levels
6704
FOR-NEXT loop nesting level deeper than 5 levels
6705
A device other than a valid is used for an applied instruction operand.
6706
The device number or data designated as an applied instruction operand
is outside the allowable designation range.
6707
File register operation is accessed without allocating the file register area.
6708
FROM/TO instruction error.
6709
Other (No IRET or SRET or illegal FOR-NEXT loop)
Error message
Error code
Description
Summary of Contents for FX-20P-E
Page 1: ...OPERATION MANUAL FX 20P E HANDY PROGRAMMING PANEL...
Page 4: ...FX 20P E Handy programming panel ii...
Page 8: ...FX 20P E Handy programming panel vi...
Page 20: ...FX 20P E Handy programming panel Notes to Users 1 1 6 1 6 Name of each part FX 20P E...
Page 120: ...FX 20P E Handy programming panel A 2 MEMO...
Page 126: ...FX 20P E Handy programming panel B 6 MEMO...
Page 127: ......