Control circuit
45
2
Common terminals of the control circuit (SD, PC, 5, SE)
• Terminals SD (sink logic), PC (source logic), 5, and SE are common terminals (0V) for I/O signals. (All common terminals
are isolated from each other.) Do not earth (ground) these terminals. Avoid connecting terminal SD (sink logic) with 5,
terminal PC (source logic) with 5, and terminal SE with 5.
• In the sink logic, terminal SD is a common terminal for the contact input terminals (STF, STR, STP (STOP), RH, RM, RL,
JOG, RT, MRS, RES, AU, CS) and the pulse train output terminal (FM
). The open collector circuit is isolated from the
internal control circuit by photocoupler.
• In the source logic, terminal PC is a common terminal for the contact input terminals (STF, STR, STP (STOP), RH, RM, RL,
JOG, RT, MRS, RES, AU, CS). The open collector circuit is isolated from the internal control circuit by photocoupler.
• Terminal 5 is a common terminal for the frequency setting terminals (2, 1 or 4) and the analog output terminals (AM, CA
).
It should be protected from external noise using a shielded or twisted cable.
• Terminal SE is a common terminal for the open collector output terminals (RUN, SU, OL, IPF, FU). The contact input circuit
is isolated from the internal control circuit by photocoupler.
Terminal FM is provided in the FM-type inverter.
Terminal CA is provided in the CA-type inverter.
Signal inputs by contactless switches
The contact input terminals of the inverter (STF, STR, STP (STOP), RH, RM, RL, JOG, RT, MRS, RES, AU, CS) can be
controlled using a transistor instead of a contact switch as shown below.
+24 V
STF, etc
SD
Inverter
External signal input using transistor
(sink logic)
PC
R
STF, etc
+24 V
Inverter
External signal input using transistor
(source logic)