Connection of stand-alone option units
66
2.11.5
Connection of the power regeneration common
converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the inverter terminals (P/+, N/-) and the power
regeneration common converter (FR-CV) terminals as shown below so that their symbols match with each other.
The FR-CV is applicable to FR-A846-01800(55K) or lower.
After making sure that the wiring is correct, set "2" in
Pr.30 Regenerative function selection
.
NOTE
• The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1, S2/L2, and T2/L3 must
be matched.
• Use the sink logic (initial setting for the FM type) when the FR-CV is connected. It cannot be connected when the source logic
is selected.
• For the parameter details, refer to the FR-A800 Instruction Manual (Detailed).
Do not connect anything to power input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter. (E.OPT (option fault)
will occur.
Remove the jumper across terminals P/+ and P1.
Do not insert an MCCB between terminals P/+ and N/- (between terminals P/L+ and P/+ or between N/L- and N/-). Connecting the
opposite polarity of terminals N/- and P/+ will damage the inverter.
Use
Pr.178 to Pr.189 (input terminal function selection)
to assign the terminals used for the X10 signal.
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter without connecting them will
damage the power regeneration common converter.
Always connect terminal RDYB of the FR-CV to the inverter terminal where the X10 signal or the MRS signal is assigned to. Always
connect terminal SE of the FR-CV to the inverter terminal SD. Not connecting these terminals may damage the FR-CV.
R/L11
S/L21
T/L31
R2/L12
S2/L22
T2/L32
R2/L1
S2/L2
T2/L3
R/L11
S/L21
T/MC1
P/L+
U
V
W
M
FR-CV type
Power regeneration
common converter
Inverter
PC
SD
X10
∗4
RES
P24
SD
RDYB
RSO
SE
RDYA
N/L-
∗3
∗6
∗5
R/L1
S/L2
T/L3
P/+
N/-
∗1
Three-phase
AC power
supply
MCCB
MC1
Dedicated stand-alone
reactor (FR-CVL)
P1
∗2