Inverter rating
122
6.1
Inverter rating
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
The rated output capacity indicated assumes that the output voltage is 440 V.
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about
.
Value for the ND rating.
The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor
and cables) affects the rated input current.
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of
the input reactor and cables).
For the power voltage exceeding 480 V, set
Pr.977 Input voltage mode selection
. (For the details, refer to the FR-A800 Instruction Manual
(Detailed).)
UL Type 12 Enclosure-Suitable for Installation in a Compartment Handling Conditioned Air (Plenum)
For compliance with IP55, remove the protective bushes and install the recommended cable glands.
Model FR-A846-[]
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
Applicable
motor capacity
(kW)
LD
0.75 1.5
2.2
3.7
5.5
7.5
11
15
18.5 22
30
37
45
55
75
90
110 132 160
ND
(initial setting)
0.4
0.75 1.5
2.2
3.7
5.5
7.5
11
15
18.5 22
30
37
45
55
75
90
110 132
Ou
tpu
t
Rated
capacity
(kVA)
LD
1.6
2.7
3.7
5.8
8.8
12
18
22
27
33
43
53
65
81
110 137 165 198 248
ND
(initial setting)
1.1
1.9
3
4.6
6.9
9.1
13
18
24
29
34
43
54
66
84
110 137 165 198
Rated
current (A)
LD
2.1
3.5
4.8
7.6
11.5 16
23
29
35
43
57
70
85
106 144 180 216 260 325
ND
(initial setting)
1.5
2.5
4
6
9
12
17
23
31
38
44
57
71
86
110 144 180 216 260
Overload
current
rating
LD
120% 60 s, 150% 3 s (inverse-time characteristics) at ambient temperature of 40°C
ND
(initial setting)
150% 60 s, 200% 3 s (inverse-time characteristics) at ambient temperature of 40°C
Rated voltage
Three-phase 380 to 500 V
Regenerative
braking
Maximum
brake torque
10% torque/continuous
Power
sup
p
ly
Rated input
AC voltage/frequency
Three-phase 380 to 500 V 50 Hz/60 Hz
Permissible AC voltage
fluctuation
323 to 550 V 50 Hz/60 Hz
Permissible frequency
fluctuation
±5%
Rated input
current (A)
LD
2.1
3.5
4.8
7.6
11.5 16
23
29
35
43
57
70
85
106 144 180 216 260 325
ND
(initial setting)
1.5
2.5
4
6
9
12
17
23
31
38
44
57
71
86
110 144 180 216 260
Power
supply
capacity
(kVA)
LD
1.6
2.7
3.7
5.8
9
12
18
22
27
33
43
53
65
81
110 137 165 198 248
ND
(initial setting)
1.1
1.9
3
4.6
6.9
9
13
18
24
29
34
43
54
66
102 110 137 165 198
Protective
structure
IEC 60529
Dust- and water-proof type (IP55)
UL50
UL Type12
Cooling system
Self c internal fan
Forced-air-c internal fan
Approx. mass (kg)
15
15
15
15
16
17
26
26
27
27
59
60
63
64
147 150 153 189 193