No. Name
Contents
2)
*1
Network number setting
switch
3
2
0
5
9
4
8
7
6
1
3
2
0
5
9
4
8
7
6
1
3
2
0
5
9
4
8
7
6
1
NETWORK
NO.
X100
X10
X1
the third
digit
the second
digit
the first
digit
Network number setting (factory setting at time of shipping: 1)
<Setting range>
1 to 255
:Network number
Other than 1 to 255 :Setting error (The SW.E. LED turns ON) Becomes off-line
condition
Group number setting (factory setting at time of shipping: 0)
<Setting range>
0
: No specified group
1 to 9 : Group number
Enabled for PLC to PLC network
3)
*1
Group number setting
Switch
3
2
0
5
9
4
8
7
6
1
GR.NO.
Station number setting (factory setting at time of shipping: 1)
Type Setting
PLC to PLC
network
1 to 64
: Station number
Other than 1 to 64 : Setting error (The SW.E. LED turns ON)
4)
*1
Station number setting
switch
3
2
0
5
9
4
8
7
6
1
3
2
0
5
9
4
8
7
6
1
ST.NO.
X10
X1
the second
dight
the first
dight
Remote I/O
network
0
: Remote master station
Other than 0
: Setting error (The SW.E. LED turns ON)
Mode setting (factory setting at time of shipping: 0)
Mode Name
Contents
0 Online
(automatic
online return effective)
Data link with automatic online return effective
1
Not used (Setting to this turns on the SW.E. LED.)
2
Offline
Disconnects the host station.
3
Forward loop test
Checks the forward loop of the whole network
system.
4
Reverse loop test
Checks the reverse loop of the whole network
system.
5 Station-to-station
test
(master station)
6 Station-to-station
test
(slave station)
The mode for a line check between two
stations, in which the station with the smaller
number is regarded as the master station and
the other is considered the slave station.
7
Self-loopback test
Check the hardware of a module in isolation,
including the communication circuit and cables
of the transmission system.
8 Internal
self-loopback
test
Check the hardware of a module in isolation,
including the communication circuit of the
transmission system.
9
Hardware test
Check the hardware inside the network
module.
5)
*1
Mode setting switch
MODE
MODE
0:ONLINE(A.R)
2:OFFLINE
E
6
D
5
C
4
B
3
A
2
9
1
8
0F
7
A to F Not used
(Do not set the mode.)