11
-
15
CHAPTER11 PROCEDURES FOR WRITING PROGRAM TO CPU MODULE
1
2
11
4
5
6
7
8
11.2 H
igh Per
forman
ce Mod
el QCPU, Pr
ocess CPU, and
Redundant C
P
U
11.2.5
P
rocedure fo
r Boot Operat
ion
11.2.5 Procedure for Boot Operation
This section describes a procedure for boot operation.
In the following procedure,
indicates an operation on the CPU module side.
Figure 11.7 Flowchart for boot operation
YES
NO
YES
NO
Start (continued from
If the RUN/STOP switch is in RUN,
set the switch to STOP.
Set the file names of parameters,
programs, initial device values, and device
comments read from the standard ROM
or memory card in the Boot file tab
of the PLC parameter dialog box.
Set the names and execution conditions of
programs to be executed in the Program tab
of the PLC parameter dialog box (This setting
is necessary when one program is written).
Set the parameter-valid drive
with the DIP switches (SW2, SW3).
Use the standard
ROM or memory card
(except the Flash card)?
Select [Online] [Format PLC memory]
in GX Developer and format the memory.
Select [Online] [Write to PLC (Flash ROM)]
[Write to PLC (Flash ROM)] in GX
Developer and write the data to the
memory set in "Transfer from" in the Boot
file tab of the PLC parameter dialog box.
Power off the programmable controller
and then on or reset the CPU module.
Is the BOOT LED on?
End
GX Developer Version 8 Operating Manual