82
-
'19 • PAC-SM-334
E6
Indoor heat exchanger
temperature sensor anomaly
Keeps flashing 1-time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of indoor heat
exchanger temperature sensor
connector OK?
Are
characteristics of indoor
heat exchanger temperature
sensor OK?
YES
Temperature-resistance characteristic
Temperature sensor resistance (k
Ω
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
(Broken wire)
(Short-circuit)
5k
Ω
at 25
°C
Correct.
➞
Insert connector
securely.
Defective indoor heat
exchanger temperature
sensor
➞
Replace.
Defective indoor unit
control PCB
➞
Replace.
(Defective indoor unit heat
exchanger temperature
sensor input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger thermistor (Thi-R1,
R2 or R3).
3. Condition of Error displayed
• When the temperature sensor
detects -50°C or lower for
5 seconds continuously,
the compressor stops.
After 3-minutes delay, the
compressor starts again
automatically, but if this
error occurs again within
60 minutes after the initial
detection.
• Or if 70°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective indoor heat
exchanger sensor connector
• Indoor heat exchanger
temperature sensor anomaly
• Faulty indoor unit control PCB
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content