'19 • PAC-SM-334
(19) Broken wire detection on temperature sensor
(a) Outdoor unit heat exchanger temperature sersor, outdoor air temperature sensor.
If the following is detected for 5 seconds continuously within 2 minutes to 2 minutes and 20 seconds after the
compressor ON, the compressor stops. After a delay of 3 minutes, it restarts but, if the same is detected repeatedly 3
times within 40 minutes, the compressor stops with the anomalous stop. Or with in 20 seconds after power ON.
Note (1) During defrost operation and for 3 minutes after the end of defrost operation, it is not detected.
• Outdoor unit heat exchanger temperature sensor: -55°C or lower.
• Outdoor air temperature sensor: -55°C or lower.
(b) Discharge pipe temperature sensor.
If the following is detected for 5 seconds continuously within 10 minutes to 10 minutes and 20 seconds after the
compressor ON, the compressor stops. After a delay of 3 minutes, it restarts but, if the same is detected repeatedly 3
times within 40 minutes, the compressor stops with the anomalous stop.
Note (1) During defrost operation and for 3 minutes after the end of defrost operation, it is not detected.
• Discharge pipe temperature sensor: -25°C or lower.
(18) Silent mode
As “Silent mode start” signal is received from the remote control, it operates by dropping the outdoor fan tap.
Model
Outdoor fan tap (Upper limit)
FDC90, 100VNP-W
Cooling: 7th speed, Heating: 7th speed
Item