87
–
E30
E30
Unmatch connection of
indoor and outdoor unit
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is
the signal wire
connection between
indoor and outdoor units
correctly ?
YES
NO
Is
the voltage
between L1-N at terminal
block of indoor unit
220/240V?
NO
Is the
voltage
between L1-N,
L2-N and L3-N for
3-phase model and L1-N for
1-phase model at terminal
brock of outdoor unit
220/240V?
YES
YES
NO
Correct signal wiring.
Replace outdoor control
PCB.
Disconnection of wire for
power cable
→
Correct it.
Replace indoor control
PCB.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Faulty indoor control PCB
• Faulty outdoor control PCB
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content