en
6
Indoor units
* For the factory-charged refrigerant amount, refer to the spec nameplate or installation manual.
For the amount to be added locally, refer to the installation manual.
For wall mounted: 1.8 m or more
For ceiling suspended, cassette and ceiling concealed: 2.2 m or more
* There are restrictions in installation height for each model, so read the installation manual for the particular unit.
M [kg]
Amin [m²]
1.0
4
1.5
6
2.0
8
2.5
10
3.0
12
3.5
14
4.0
16
4.5
20
5.0
24
5.5
29
6.0
35
6.5
41
7.0
47
7.5
54
8.0
62
8.5
69
9.0
78
9.5
87
Wall mounted
h0 1.8 [m]
Ceiling concealed
Cassette
Ceiling suspended
h0 2.2 [m]
h0 2.2 [m]
h0 2.2 [m]
Case 1: for wall mounted, ceiling suspended, cassette and concealed
M [kg]
Amin [m²]
< 1.84
No requirements
1.84
6
2.0
6
2.5
7
3.0
9
3.5
10
4.0
11
4.5
13
5.0
14
5.5
15
6.0
17
6.5
18
7.0
20
7.5
21
8.0
22
8.5
24
9.0
25
9.5
26
Floor standing (PSA-M)
h0 = 0 [m]