en
15
Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.
Supply power (circuit breaker).
* When power is supplied, make sure that “CENTRALLY CONTROLLED” is not
displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.
* Start-up of the indoor-outdoor communication takes about 3 minutes after the
power (circuit breaker) is turned on. Start the pump-down operation 3 to 4
minutes after the power (circuit breaker) is turned ON.
After the liquid stop valve is closed, set the SWP switch on the control board of
the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and
outdoor units) start operating and refrigerant collecting operation begins. LED1
and LED2 on the control board of the outdoor unit are lit.
* Only set the SWP switch (push-button type) to ON if the unit is stopped. How-
ever, even if the unit is stopped and the SWP switch is set to ON less than 3
minutes after the compressor stops, the refrigerant collecting operation cannot
be performed. Wait until compressor has been stopped for 3 minutes and then
set the SWP switch to ON again.
Because the unit automatically stops in about 2 to 3 minutes when the refrigerant
collecting operation is completed (LED1 off, LED2 lit), be sure to quickly close the
gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is stopped, refrig-
erant collection is not properly performed. Open the liquid stop valve completely,
and then repeat step after 3 minutes have passed.
* If the refrigerant collecting operation has been completed normally (LED1 off,
LED2 lit), the unit will remain stopped until the power supply is turned off.
Turn off the power supply (circuit breaker).
* Note that when the extension piping is very long with large refrigerant amount,
it may not be possible to perform a pump-down operation. When performing
the pump-down operation, make sure that the low pressure is lowered to near
0 MPa (gauge).
Warning:
-
Circuit diagram example (Demand function)
On-site arrangement
X, Y: Relay
External input adapter (PAC-SC36NA-E)
Outdoor unit control board
Max. 10 m
Power supply for relay
0–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
Complete the circuit as shown when using the external input adapter
(PAC-SC36NA-E). (Option)
By setting SW7-1 on the control board of the outdoor unit, the energy consump-
tion (compared to the normal consumption) can be limited as shown below.
SW7-1
SW2
SW3
Energy consumption
Demand
function
ON
OFF
OFF
100%
ON
OFF
75%
ON
ON
50%
OFF
ON
0% (Stop)
SW2
SW3
1
3
CNDM
Y
X
X
Y
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
• The ability varies according to the outdoor temperature and conditions, etc.
Complete the circuit as shown when using the external input adapter
(PAC-SC36NA-E). (Option)
SW7-1 (Outdoor unit control board): OFF
SW1 ON: Low noise mode
SW1 OFF: Normal operation
Circuit diagram example (low noise mode)
On-site arrangement
External input adapter (PAC-SC36NA-E)
X: Relay
Outdoor unit control board
Max. 10 m
Power supply for relay
SW1
1
3
CNDM
X
X
1 2 3 4 5 6
* Set the refrigerant address using the DIP switch of the outdoor unit.
Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
When a Different Refrigerant System Grouping is Used.
Up to 16 refrigerant systems can be controlled as one group using the slim MA
remote controller.
Note:
.
Outdoor unit
Indoor unit
Master remote controller
Subordinate remote controller
Standard 1:1 (Refrigerant address = 00)
Simultaneous twin (Refrigerant address = 01)
Simultaneous triple (Refrigerant address = 02)
SW 1 - 3 ~ 6
SW 1 - 3 ~ 6
SW 1 - 3 ~ 6
SW1
Function table
Function
Operation according to switch setting
ON
OFF
SW1
function
settings
1 Compulsory
defrosting
Start
Normal
2 Error history
clear
Clear
Normal
3
4
5
6
Refrigerant
system ad-
dress setting
Settings for outdoor unit addresses
0 to 15
TB1
TB1
TB1
TB4
TB5
TB4
TB5
TB4
TB4
TB5
TB4
TB4
Orange
Orange
Red
Red
Brown
Brown