background image

en

15

Perform the following procedures to collect the refrigerant when moving the indoor 
unit or the outdoor unit.

  Supply power (circuit breaker).

  *   When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 

displayed  on  the  remote  controller.  If  “CENTRALLY  CONTROLLED”  is  dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

  *   Start-up of the indoor-outdoor communication takes about 3 minutes after the 

power  (circuit  breaker)  is  turned  on.  Start  the  pump-down  operation  3  to  4 
minutes after the power (circuit breaker) is turned ON.

  After the liquid stop valve is closed, set the SWP switch on the control board of 

the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and 
outdoor units) start operating  and refrigerant collecting operation begins. LED1 
and LED2 on the control board of the outdoor unit are lit.

  *   Only set the SWP switch (push-button type) to ON if the unit is stopped. How-

ever, even if the unit is stopped and the SWP switch is set to ON less than 3 
minutes after the compressor stops, the refrigerant collecting operation cannot 
be performed. Wait until compressor has been stopped for 3 minutes and then 
set the SWP switch to ON again.

  Because the unit automatically stops in about 2 to 3 minutes when the refrigerant 

collecting operation is completed (LED1 off, LED2 lit), be sure to quickly close the 
gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is stopped, refrig-
erant collection is not properly performed. Open the liquid stop valve completely, 
and then repeat step   after 3 minutes have passed.

  *   If the refrigerant collecting operation has been completed normally (LED1 off, 

LED2 lit), the unit will remain stopped until the power supply is turned off.

 Turn off the power supply (circuit breaker).

  *   Note that when the extension piping is very long with large refrigerant amount, 

it may not be possible to perform a pump-down operation. When performing 
the pump-down operation, make sure that the low pressure is lowered to near 
0 MPa (gauge).

 Warning:

-

   Circuit diagram example (Demand function)
   On-site arrangement

X, Y: Relay

  External input adapter (PAC-SC36NA-E)
  Outdoor unit control board
  Max. 10 m
  Power supply for relay

0–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the 
contact input of an ON/OFF switch is added to the CNDM connector (option) on the 
control board of the outdoor unit.

  Complete the circuit as shown when using the external input adapter 

(PAC-SC36NA-E). (Option)

  By setting SW7-1 on the control board of the outdoor unit, the energy consump-

tion (compared to the normal consumption) can be limited as shown below.

SW7-1

SW2

SW3

Energy consumption 

Demand 

function

ON

OFF

OFF

100%

ON

OFF

75%

ON

ON

50%

OFF

ON

0% (Stop)

SW2

SW3

1

3

CNDM

Y

X

X

Y

reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
•   The ability varies according to the outdoor temperature and conditions, etc.

  Complete the circuit as shown when using the external input adapter 

(PAC-SC36NA-E). (Option)

 SW7-1 (Outdoor unit control board): OFF
  SW1 ON: Low noise mode

  SW1 OFF: Normal operation

  Circuit diagram example (low noise mode)
  On-site arrangement
  External input adapter (PAC-SC36NA-E)

X: Relay

  Outdoor unit control board
  Max. 10 m
  Power supply for relay

SW1

1

3

CNDM

X

X

1 2 3 4 5 6

*  Set the refrigerant address using the DIP switch of the outdoor unit.

  Wiring from the Remote Control

This wire is connected to TB5 (terminal  board for remote controller) of the indoor 
unit (non-polar).

 When a Different Refrigerant System Grouping is Used.

Up  to  16  refrigerant  systems  can  be  controlled  as  one  group  using  the  slim  MA 
remote controller.

Note:

.

  Outdoor unit
  Indoor unit
  Master remote controller
  Subordinate remote controller
  Standard 1:1 (Refrigerant address = 00)
  Simultaneous twin (Refrigerant address = 01)
  Simultaneous triple (Refrigerant address = 02)

  SW 1 - 3 ~ 6

  SW 1 - 3 ~ 6

  SW 1 - 3 ~ 6

SW1
Function table

Function

Operation according to switch setting

ON

OFF

SW1
function 
settings

1 Compulsory 

defrosting

Start

Normal

2 Error history 

clear

Clear

Normal

3
4
5
6

Refrigerant 
system ad-
dress setting

Settings for outdoor unit addresses 
0 to 15

TB1

TB1

TB1

TB4

TB5

TB4

TB5

TB4

TB4

TB5

TB4

TB4

Orange

Orange

Red

Red

Brown

Brown

Summary of Contents for ZM200

Page 1: ...English ...

Page 2: ...en de fr nl es it el pt da sv tr ru uk bg pl cs sk hu sl ro et lv lt hr sr no ...

Page 3: ...t electric shock or fire may result any other refrigerant and do not allow air to remain in the lines The use of any refrigerant other than that specified for the system will cause case this could lead to a serious impediment to securing product safety installed water leakage electric shock or fire may result age location If the unit is installed incorrectly water leakage electric shock Warning de...

Page 4: ...g the screen display quality Caution the edge of other parts injuries for looseness cracks or other damage If such defects are left uncorrected the unit may fall down and cause damage or injuries leak out Caution pipes lightning rods or telephone grounding lines If the unit is not prop erly grounded electric shock may result may result Caution damage the internal parts Keep the main power switch t...

Page 5: ...ntilation If a refrig ing appropriate ventilation Avoid locations exposed to direct sunlight or other sources of heat Select a location from which noise emitted by the unit will not inconvenience neighbors Select a location permitting easy wiring and pipe access to the power source and indoor unit mulate Note that water may drain from the unit during operation Select a level location that can bear...

Page 6: ... Fig 2 9 Obstacles at front only Fig 2 10 When using an optional air outlet guide the clearance is 500 mm or more Obstacles at front and rear only Fig 2 11 When using an optional air outlet guide the clearance is 500 mm or more Obstacles at rear sides and above only Fig 2 12 Leave 50 mm for ZM200 250 M200 250 space or more between the units Obstacles at rear only Fig 2 13 Obstacles at rear and abo...

Page 7: ...t from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m Amin Height from the bottom of 0 125 m or less 75 or more opening Height from the bottom of 0 125 m or less Width W 0 9 m or more Height from the bottom 0 125 m or less Height H 0 15 m or more M kg ...

Page 8: ... model so read the installation manual for the particular unit M kg Amin m 1 0 4 1 5 6 2 0 8 2 5 10 3 0 12 3 5 14 4 0 16 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 8 0 62 8 5 69 9 0 78 9 5 87 Wall mounted h0 1 8 m Ceiling concealed Cassette Ceiling suspended h0 2 2 m h0 2 2 m h0 2 2 m Case 1 for wall mounted ceiling suspended cassette and concealed M kg Amin m 1 84 No requirements 1 84 6 2 0...

Page 9: ... wires etc if necessary to install the unit Use self tapping screws ø5 15 mm or less and install on site Warning cause damage or injuries rectly installed unit may fall down and cause damage or injuries mm pipes to connect the refrigerant pipes Use refrigerant pipes with the thick pipes are clean and do not contain any harmful contaminants such as sul Warning any other refrigerant and do not allow...

Page 10: ... Remove the service panel 4 screws and the cover panel front 2 screws and cover panel rear 4 screws Perform refrigerant piping connections for the indoor outdoor unit when the out door unit s stop valve is completely closed Vacuum purge air from the indoor unit and the connection piping After connecting the refrigerant pipes check the connected pipes and the indoor unit for gas leaks Refer to 4 4 ...

Page 11: ...t exceed 30 m If the pipe length exceeds 30 m charge the unit with additional R32 refrigerant according to the permitted pipe lengths in the chart below When the unit is stopped charge the unit with the additional refrigerant through the liquid stop valve after the pipe extensions and indoor unit have been vacu umized When the unit is operating add refrigerant to the gas check valve using a safety...

Page 12: ...gth Maximum pipe length ZM200 250 Liquid pipe mm O D ø9 52 ø12 7 ø15 88 Thickness t0 8 t0 8 t1 0 Gas pipe mm O D ø19 05 ø22 2 ø25 4 ø28 58 ø19 05 ø22 2 ø25 4 ø28 58 ø22 2 ø25 4 ø28 58 ø31 75 Thickness t1 0 t1 0 t1 0 t1 0 t1 0 t1 0 t1 0 t1 0 t1 0 t1 0 t1 0 t1 1 ZM200 20m 20m 50m 30m Standard size 100m 30m 100m 30m 20m 20m 50m 30m 100m 30m 100m 30m 50m 20m 50m 20m 50m 20m 50m 20m ZM250 20m 20m 50m 3...

Page 13: ...ecessary use the drain socket or the drain pan option When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In addition if the restrictions are going to be exceeded or if there are going to be combinations of indoor and outdoor units refer to installation instructions for the indoor unit for details about the ins...

Page 14: ... 6 1 Indoor unit Outdoor unit Remote controller Main switch Breaker Earth For Power For Power L1 L2 L3 N S1 S2 S3 Terminal block Indoor Outdoor connection terminal block S1 S2 S3 Service panel Clamp Clamp the cables so that they do not contact the center of the service panel or the gas valve Earth terminal Note reinstall it Caution ...

Page 15: ...ure 3 The 10 m wire is attached in the remote controller accessory S3 terminal has 24 VDC against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device 5 In multi phase appliances the colour of the neutral conductor of the supply cord if any shall be blue S1 S2 S3 S1 S2 S3 A Control Outdoor Unit 3 poles isolator Power supply Isolato...

Page 16: ...mulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdown 4 If the insulation resistance rises above 1 M the compressor is not faulty Caution The compressor will not operate unless the power supply phase connection is correct Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power swi...

Page 17: ...nt X Y Relay External input adapter PAC SC36NA E Outdoor unit control board Max 10 m Power supply for relay 0 100 of the normal consumption The demand function will be activated when a commercially available timer or the contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit Complete the circuit as shown when using the external input adapte...

Page 18: ...400 Three 50 Dimensions W H D mm 1050 1338 330 40 Sound level 1 Cooling dB A 59 59 58 59 Heating 62 62 60 62 1 Measured under rated operation frequency Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 ...

Reviews: