background image

(OHFWULFDOVSHFL¿FDWLRQV

MODEL

NTXWPH06B112A

NTXWPH09B112A

NTXWPH12B112A

NTXWPH15B112A

NTXWPH18B112A

INDOOR UNIT
Power supply (V, PHASE, Hz)

208/230, 1, 60

Min. Circuit Ampacity

(A)

1.0

Fan motor (F.L.A.)

(A)

0.65

OUTDOOR UNIT
Power supply (V, PHASE, Hz)

208/230, 1, 60

Max. Fuse size (time delay)

(A)

15

20

Min. Circuit Ampacity

(A)

10

18

Fan motor (F.L.A.)

(A)

0.50

0.93

Compressor

(R.L.A)

(A)

7.4

13.6

(L.R.A)

(A)

9.2

17.0

Control voltage

Indoor unit - Remote controller: (Wireless)

Indoor unit - Outdoor unit: DC12-24 V (Polar)

Pipe

Outside 

diameter

Minimum wall 

thickness

Insulation 

thickness

Insulation 

material

inch (mm)

For liquid

1/4 (6.35)

0.0315 (0.8)

5/16 (8)

Heat resistant 

foam plastic 

6SHFL¿F

gravity

For gas

06/09/12

3/8 (9.52)

0.0315 (0.8)

5/16 (8)

15/18

1/2 (12.7)

0.0315 (0.8)

5/16 (8)

Limits

Pipe length

NTXWPH06/09/12B112A

65 ft. (20 m) max.

NTXWPH15/18B112A

100 ft. (30 m) max.

Height difference

NTXWPH06/09/12B112A

40 ft. (12 m) max.

NTXWPH15/18B112A

50 ft. (15 m) max.

No. of bends

10 max.

Pipe length

Up to 25 ft. (7.5 m)

No additional charge is required.

Exceeding 25 ft. (7.5 m)

Additional charge is required.

(Refer to the table below.)

Refrigerant to be added

1.08 oz each 5 ft. (20 g/m)

1-3. SPECIFICATIONS

1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR 

WIRE CONNECTION

•  Power should be taken from an exclusive branched circuit.

•  Wiring work should be based on applicable technical standards.

•  Wiring connections should be made following the diagram.

•  Securely tighten screws.

Connecting wires and the ground wire

•  Use  solid  conductor  Min. AWG14  or  stranded  conductor 

Min. AWG14.

•  Use double insulated copper wire with 600 V insulation.

•  Use copper conductors only.

* Follow local electrical codes.

Power supply cable and ground wire

•  Use solid or stranded conductor.

   06/09/12 

Min. AWG14

   15/18 

Min. AWG12

•  Use copper conductors only.

*  Follow local electrical codes.

Note: 

When the indoor unit is powered from the outdoor unit, depend-

ing on local code, a disconnect switch needs to be installed to a 

power supply circuit.

•  Refrigerant adjustment... If pipe length exceeds 25 ft. (7.5 m), 

additional refrigerant (R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up 

to 25 ft. [7.5 m])

‡ 7KHXQLWKDVÀDUHGFRQQHFWLRQVRQERWKLQGRRUDQGRXWGRRU

sides.

•  Remove the valve cover from the outdoor unit, then connect 

the pipe.

•  Refrigerant pipes are used to connect the indoor and outdoor 

units.

•  Be careful not to crush or over bend the pipe in pipe bending.

1-3-2. REFRIGERANT PIPES

•  To prevent condensation, insulate the two refrigerant pipes.

•  Refrigerant pipe bending radius must be 4 in. (100 mm) or more.

 CAUTION

%HVXUHWRXVHWKHLQVXODWLRQRIVSHFL¿HGWKLFNQHVVWDEOHRQWKH

right). Excessive insulation may cause incorrect installation of 

the indoor unit, and too little insulation may cause condensate 

to form.

1-2. SELECTING THE INSTALLATION LOCATION

INDOOR UNIT 

‡ :KHUHDLUÀRZLVQRWEORFNHG

•  Where cool (or warm) air spreads over the entire room.

•  On a rigid wall to reduce the possibility of vibration.

•  Where it is not exposed to direct sunlight. Do not expose 

to direct sunlight also during the period following unpack-

ing to before use.

•  Where it can be easily drained.

•  At a distance 3 ft. (1 m) or more away from a TV and 

radio. Operation of the air conditioner may interfere with 

UDGLRRU79UHFHSWLRQ$QDPSOL¿HUPD\EHUHTXLUHGIRU

the affected device.

‡ ,QDSODFHDVIDUDZD\DVSRVVLEOHIURPÀXRUHVFHQWDQG

incandescent lights. In order to make the infrared remote 

control operate the air conditioner normally. The heat 

from the lights may cause deformation or the ultraviolet 

may cause deterioration.

• 

:KHUHWKHDLU¿OWHUFDQEHUHPRYHGDQGUHSODFHGHDVLO\

•  Where it is away from the other heat or steam source.

Note: 

Install the indoor unit high on the wall where air can 

distribute over the entire room.

REMOTE CONTROLLER 

•  Where it is convenient to operate and easily visible.

•  Where children cannot easily touch it.

‡ 6HOHFWDSRVLWLRQDERXWIWPDERYHWKHÀRRU

Check that signals from the remote controller from 

that position are received by the indoor unit (‘beep’ 

or ‘beep beep’ receiving tone sounds). Then, attach 

remote controller holder to a pillar or wall and install 

wireless remote controller.

Note: 

,QURRPVZKHUHLQYHUWHUW\SHÀXRUHVFHQWODPSVDUHXVHG

the signal from the wireless remote controller may not be 

received.

OUTDOOR UNIT

•  Where it is not overly exposed to strong winds.

‡ :KHUHDLUÀRZLVJRRGDQGGXVWOHVV

•  Where neighbours are not annoyed by operation sound 

or hot air.

•  Where rigid wall or support is available to prevent the 

increase of operation sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  If installing the unit in a location high above the ground, 

be sure to secure the unit legs.

•  Where it is at least 10 ft. (3 m) away from the antenna 

of TV set or radio. Operation of the air conditioner may 

interfere with radio or TV reception in areas where recep-

WLRQLVZHDN$QDPSOL¿HUPD\EHUHTXLUHGIRUWKHDIIHFWHG

device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or 

blowing snow. In areas with heavy snow, please install 

DFDQRS\DSHGHVWDODQGRUEDIÀHERDUGV

Note:

•  It is advisable to make a piping loop near outdoor unit 

so as to reduce vibration.

‡ )RU LQFUHDVHG HI¿FLHQF\ LQVWDOO WKH RXWGRRU XQLW LQ D

location where continuous direct sunlight or excessive 

water can be avoided as much as possible.

Note: 

When operating the air conditioner in low outside tem-

perature, be sure to follow the instructions described 

below.

•  Never install the outdoor unit in a place where its air 

inlet/outlet side may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit 

with its air inlet side facing the wall and 

DEDIÀHERDUG

on the air outlet side.

Avoid the following places for installation where air 

conditioner trouble is liable to occur.

‡ :KHUHÀDPPDEOHJDVFRXOGOHDN

•  Where there is an excessive amount of machine oil 

in the air.

• 

:KHUHRLOLVVSODVKHGRUZKHUHWKHDUHDLV¿OOHGZLWK

oily smoke (such as cooking areas and factories, in 

which the properties of plastic could be changed and 

damaged).

•  Salty places such as the seaside.

‡ :KHUHVXO¿GHJDVLVJHQHUDWHGVXFKDVKRWVSULQJ

sewage, waste water.

•  Where there is high-frequency or wireless equipment.

•  Where  there  is  emission  of  high  levels  of  VOCs, 

including phthalate compounds, formaldehyde, etc., 

which may cause chemical cracking.

Summary of Contents for Trane NTXWPH06B112A Series

Page 1: ...e unit make sure that no substance RWKHU WKDQ WKH VSHFL HG UHIULJHUDQW 5 HQWHUV WKH UHIULJHUDQW FLUFXLW Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that VSHFL HG IRU WKH V VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH V VWHP PDOIXQFWLRQ RU XQLW breakdown In the worst case this could lead to a seriou...

Page 2: ...ing to before use Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP ÀXRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from th...

Page 3: ...by drain water or damaged by frozen drain water 4 7 8 in 122 5 mm or more 3 3 8 in 85 mm or more 5 11 16 in 143 mm or more for left left rear piping using spacer 2 3 16 in 56 mm or more 5 1 4 in 132 5 mm or more 33 1 16 13 3 4 14 5 8 19 11 16 Air inlet Air inlet Air inlet Air inlet Air inlet 6 7 8 15 3 8 13 Air outlet 2 3 8 13 16 slot 1 9 16 40 840 175 500 Air inlet 390 330 349 371 Air outlet 2 10...

Page 4: ...terminal of electrical parts box 7 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 8 Firmly tighten the terminal screws After tightening verify that the wires are ti...

Page 5: ...ection to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole...

Page 6: ...HIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Power supply cord K Indoor outdoor unit connecting wire A Make ground wire a little longer than others More than 4 in 100 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its corre spondent terminal when securing the cord and or the wire to the terminal block Pipe diameter inch mm B inc...

Page 7: ...Otherwise composition of the refrigerant in the system may be changed and affect performance of the air conditioner 10 Remove gauge manifolds and replace service port caps and tighten 11 Leak test 4 2 TEST RUN 1 Insert power supply plug into the power outlet and or turn on the breaker 2 Press the E O SW once for COOL and twice for HEAT operation Test run will be performed for 30 minutes If the lef...

Page 8: ...ING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor XQLW DQG SXOO LW GRZQZDUG DQG IRUZDUG DV VKRZQ LQ WKH JXUH RQ WKH ULJKW Installation procedure 1 Install the panel assembly following the removal procedure in reverse 2 Be sure to press the positions as indicated by the arrows ...

Reviews: