background image

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following 

the procedure below so that refrigerant is not released into the atmosphere.

1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe 

side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.

3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that 

it can be easily closed fully when the pressure gauge shows 0 psi [Gauge] (0 Mpa).

4) Start the emergency COOL operation.

  To start the emergency operation in COOL mode, disconnect the power supply plug 

and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn 

on the breaker, and then press the E.O. SW once. (The emergency COOL operation 

can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure 

gauge shows (0.1 to 0 psi [Gauge] (0.05 to 0 Mpa)).

6) Stop the emergency COOL operation.

  To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer 

to operating instructions for details.

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate.

When releasing the corner part, release both left and right bottom corner part of indoor 

XQLWDQGSXOOLWGRZQZDUGDQGIRUZDUGDVVKRZQLQWKH¿JXUHRQWKHULJKW

Installation procedure

1) Install the panel assembly following the removal procedure in reverse. 

2) Be sure to press the positions as indicated by the arrows in order to attach the assembly 

completely to the unit.

3) Install the front panel and the horizontal vanes.

Upper and 

lower vanes

Unlock

 WARNING

When pumping down the refrigerant, stop the compressor before disconnecting 

the refrigerant pipes. The compressor may burst if air etc. get into it.

5.  RELOCATION AND MAINTENANCE

Removal procedure

1) Unlock the upper and lower vanes as shown in   and   using a thin instrument. 

Then, remove the horizontal vanes.

2) Remove the front panel.

5HPRYHWKHVFUHZVZKLFK¿[WKHSDQHODVVHPEO\

4) The panel assembly consists of 3 components. Remove them in the following order: 

right, left, and center bottom. To remove the right component, pull out the right top 

corner. To remove the left component, pull out the left bottom corner. To remove the 

center bottom component, detach the hook on its upper center part.

5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY

MITSUBISHI ELECTRIC TRANE HVAC US LLC

HEAD OFFICE: 1340 SATELLITE BOULEVARD, SUWANEE, GA 30024, USA

Summary of Contents for Trane NTXWPH06B112A Series

Page 1: ...e unit make sure that no substance RWKHU WKDQ WKH VSHFL HG UHIULJHUDQW 5 HQWHUV WKH UHIULJHUDQW FLUFXLW Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that VSHFL HG IRU WKH V VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH V VWHP PDOIXQFWLRQ RU XQLW breakdown In the worst case this could lead to a seriou...

Page 2: ...ing to before use Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP ÀXRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from th...

Page 3: ...by drain water or damaged by frozen drain water 4 7 8 in 122 5 mm or more 3 3 8 in 85 mm or more 5 11 16 in 143 mm or more for left left rear piping using spacer 2 3 16 in 56 mm or more 5 1 4 in 132 5 mm or more 33 1 16 13 3 4 14 5 8 19 11 16 Air inlet Air inlet Air inlet Air inlet Air inlet 6 7 8 15 3 8 13 Air outlet 2 3 8 13 16 slot 1 9 16 40 840 175 500 Air inlet 390 330 349 371 Air outlet 2 10...

Page 4: ...terminal of electrical parts box 7 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 8 Firmly tighten the terminal screws After tightening verify that the wires are ti...

Page 5: ...ection to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole...

Page 6: ...HIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Power supply cord K Indoor outdoor unit connecting wire A Make ground wire a little longer than others More than 4 in 100 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its corre spondent terminal when securing the cord and or the wire to the terminal block Pipe diameter inch mm B inc...

Page 7: ...Otherwise composition of the refrigerant in the system may be changed and affect performance of the air conditioner 10 Remove gauge manifolds and replace service port caps and tighten 11 Leak test 4 2 TEST RUN 1 Insert power supply plug into the power outlet and or turn on the breaker 2 Press the E O SW once for COOL and twice for HEAT operation Test run will be performed for 30 minutes If the lef...

Page 8: ...ING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor XQLW DQG SXOO LW GRZQZDUG DQG IRUZDUG DV VKRZQ LQ WKH JXUH RQ WKH ULJKW Installation procedure 1 Install the panel assembly following the removal procedure in reverse 2 Be sure to press the positions as indicated by the arrows ...

Reviews: