8
When relocating or disposing of the air conditioner, pump down the system follow-
ing the procedure below so that no refrigerant is released into the atmosphere.
1
Turn off the power supply (circuit breaker).
2
Connect the gauge manifold valve to the service port of the stop valve on the
gas pipe side of the outdoor unit.
3
Fully close the stop valve on the liquid pipe side of the outdoor unit.
4
Supply power (circuit breaker).
5
Perform the refrigerant collecting operation (cooling test run).
•
For the PAR-31MAA, select “Service” → “TestRun” from the main menu to
start the test run, and then select the cooling mode.
•
For details or for other information about starting the test run when using
remote controllers, refer to the installation manual for the indoor unit or the
remote controller.
6
Fully close the stop valve on the gas pipe side of the outdoor unit when the pres-
sure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm
) and quickly
stop the air conditioner.
•
Push the “ON/OFF” button on the remote controller to stop the air conditioner.
* Note that when the extension piping is very long with a large refrigerant
amount, it may not be possible to perform a pump-down operation. In this
case, use refrigerant recovery equipment to collect all of the refrigerant in the
system.
7
Turn off the power supply (circuit breaker), remove the gauge manifold valve,
and then disconnect the refrigerant pipes.
Warning:
When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes.
• If the refrigerant pipes are disconnected while the compressor is operat-
ing and the stop valve (ball valve) is open, the pressure in the refrigeration
cycle could become extremely high if air is drawn in, causing the pipes to
burst, personal injury, etc.
8. Pumping down
Outdoor model
SUZ-KA5VA4.TH
SUZ-KA35VA4.TH
SUZ-KA50VA4.TH
SUZ-KA60VA4.TH
SUZ-KA71VA4.TH
Power supply
Single phase 30 V, 50 Hz
Dimensions W × H × D
mm
800 × 550 × 85
840 × 880 × 330
Weight
kg
30
35
54
50
53
Sound level *1
Cooling
dB (A)
47
49
5
55
Heating
48
50
5
55
*1 Measured under rated operating frequency.