48
ACTUATOR CONTROL
10
SUZ-KA25VA(H).TH SUZ-KA35VA(H).TH SUZ-KA50VA.TH SUZ-KA60VA.TH SUZ-KA71VA.TH
Discharge temperature thermistor
Indoor pipe temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Purpose
Protection
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating : Defrosting
Protection
Cooling : Low ambient temperature operation
Heating:Defrosting(Heater)
Compressor
LEV
Outdoor
fan motor
Indoor
fan motor
Defrost
heater
RV-coil
Sensor
Actuator
Discharge temperature thermistor
Indoor pipe temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature
Purpose
Protection
Cooling : Coil frost prevention
Heating : High pressure protection
Heating : Defrosting
Protection
Protection
Cooling : High pressure protection
Compressor
LEV
Outdoor
fan motor
4-way
valve
Sensor
Actuator
10-3. Relation between main sensor and actuator
10-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . ON
Cooling. . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds
15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ON or OFF
ON or OFF
10-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH
SUZ-KA50VA.TH SUZ-KA60VA.TH SUZ-KA71VA.TH
OC322A--2qxp 05.10.19 3:30 PM Page 48