Mitsubishi Electric SUZ-KA09NAHZ Installation Manual Download Page 4

A

B

4. Refrigerant piping work

4.1. Refrigerant pipe (Fig. 4-1, Fig. 4-2)

► Check that the difference between the heights of the indoor and outdoor 

units, the length of refrigerant pipe, and the number of bends in the pipe are 

within the limits shown below.

Models

A

 Pipe length

(one way)

B

 Height 

difference

C

 Number of 

bends (one way)

SUZ-KA09, KA12, 

KA15

Max. 65 ft (20 m)

Max. 40 ft (12 m)

Max. 10

SUZ-KA18

Max. 100 ft (30 m)

Max. 50 ft (15 m)

Max. 10

•  Height difference limitation is defined regardless of which unit, indoor or outdoor, 

is positioned higher .

•  Refrigerant adjustment ... If pipe length exceeds 25 ft. (7.5 m), additional refriger

-

ant (R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up to 25 ft . (7 .5 m) .)

Pipe length

Up to 25 ft (7 .5 m)

No additional charge is required.

Exceeding 25 ft (7.5 m)

Additional charge is required.

(Refer to the table below .)

Refrigerant to be added 

1 .08 oz each 5 ft . (20 g/m)

•  Table below shows the specifications of pipes commercially available.

Model

Pipe

Outside 

diameter

Min . wall 

thickness

Insulation 

thickness

Insulation 

material

inch (mm)

inch (mm)

inch (mm)

SUZ-KA09

For liquid

1/4 (6 .35) 0 .0315 (0 .8)

5/16 (8)

Heat resisting 

foam plastic 

0.045 specific 

gravity

For gas

3/8 (9 .52) 0 .0315 (0 .8)

5/16 (8)

SUZ-KA12

For liquid

1/4 (6 .35) 0 .0315 (0 .8)

5/16 (8)

For gas

3/8 (9 .52) 0 .0315 (0 .8)

5/16 (8)

SUZ-KA15

For liquid

1/4 (6 .35) 0 .0315 (0 .8)

5/16 (8)

For gas

1/2 (12 .7) 0 .0315 (0 .8)

5/16 (8)

SUZ-KA18

For liquid

1/4 (6 .35) 0 .0315 (0 .8)

5/16 (8)

For gas

1/2 (12 .7) 0 .0315 (0 .8)

5/16 (8)

•  To prevent condensation, insulate the 2 refrigerant pipes.

•  Refrigerant pipe bending radius must be 4 in . (100 mm) or more

 Caution:

Be sure to use the insulation of specified thickness (table on the above). Excessive 

insulation may cause incorrect installation of the indoor unit, and too little insulation 

may cause condensate to form .

•  The unit has flared connections on both indoor and outdoor sides.

•  Remove the valve cover from the outdoor unit, then connect the pipe.

•  Refrigerant pipes are used to connect the indoor and outdoor units .

•  Be careful not to crush or over bend the pipe in pipe bending .

A

D

B

C

E

Fig. 4-1

D

 Indoor unit

E

 Outdoor unit

A

 Indoor unit

B

 Outdoor unit

4.2. Flaring work (Fig. 4-3)

1) Cut the cooper pipe as straight as possible with a pipe cutter.

2) Remove all burrs from the cut section of pipe, ensuring that precautions are taken 

to avoid getting metal shavings into the piping .

3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe.

4) Flaring work . Firmly hold copper pipe in the dimension shown in the table . Select 

A inch (mm) from the table according to the tool you use .

5) Check

• Compare the flared work.

• 

If flare is defective, cut off the section and repeat procedure.

Pipe diameter

inch (mm)

Nut

inch (mm)

A inch (mm)

Tightening torque

Clutch 

type tool 

for R410A

Clutch 

type tool 

for R22

Wing nut 

type tool 

for R22

N·m

ft·lb

(kgf·cm)

1/4 (6 .35)

1/4 (17)

0 to 0 .02

(0 to 0 .5)

0 .04 to 

0 .06 

(1 .0 to 1 .5)

0 .06 to 

0 .08

(1 .5 to 2 .0)

13 .7 to 17 .7 10 to 13

(140 to 180)

3/8 (9 .52)

3/8 (22)

34 .3 to 41 .2 25 to 30

(350 to 420)

1/2 (12 .7)

1/2 (26)

0 .08 to 

0 .10

(2 .0 to 2 .5)

49 .0 to 56 .4 36 to 42

(500 to 575)

90°

A

Fig. 4-3

Copper 

pipe

Good

No good

Tilted Uneven Burred

Burr

Copper pipe

Spare reamer

Pipe cutter

Flaring tool

Clutch type

Wing nut type

Die

Copper pipe

Flare nut

Smooth all around

Inside is shining 

without any 

scratches .

Even length all 

around

Fig. 4-2

ø1/2 (12 .7)
ø3/8 (9 .52)

ø1/4 (6 .35)

inch (mm)

en

3

VG79Y103H01_EN.indd   3

2019/07/18   18:03:43

004

Summary of Contents for SUZ-KA09NAHZ

Page 1: ... que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado POUR L INSTALLATEUR PARA EL INSTALADOR FOR INSTALLER Air Conditioners SUZ KA09 KA12 KA15 KA18NAHZ Français Español English VG7...

Page 2: ...stalling or relocating the unit make sure that no substance other than the specified refrigerant R410A enters the refrigerant circuit Any foreign substances in the refrigerant circuit can cause abnormal pressure rise or an explosion Do not discharge the refrigerant into the atmosphere Check that the refrig erant gas does not leak after installation has been completed If refrigerant leaks during in...

Page 3: ...e sulfide gas is generated such as a hot spring Where there is high frequency or wireless equipment The outdoor unit produces condensate during the heating operation Select the in stallation place to ensure to prevent the outdoor unit and or the grounds from being wet by drain water or damaged by frozen drain water 2 Selecting the installation location When the piping is to be attached to a wall c...

Page 4: ... use the insulation of specified thickness table on the above Excessive insulation may cause incorrect installation of the indoor unit and too little insulation may cause condensate to form The unit has flared connections on both indoor and outdoor sides Remove the valve cover from the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful ...

Page 5: ...urging procedures and leak test 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit 3 Run the vacuum pump 15 minutes or more 4 Check the vacuum with the gauge manifold valve then close it and shut off the vacuum pump 5 Leave as it is for one or two minu...

Page 6: ...nal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the indoor unit securely If it is not attached correctly it could result in a fire or an electric shock due to dust water etc Tighten terminal screws securely Wiring should be done so that the power lines are not subject to tension Otherw...

Page 7: ...ommunication signal line Therefore please turn off the main power supply when servicing And do not touch the S1 S2 S3 terminals when the power is energized If isolator should be used between indoor unit and outdoor unit please use 3 pole type 6 Maintenance 6 1 Gas charge Fig 6 1 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refri...

Page 8: ...gération La présence d une substance étrangère dans le circuit de réfrigération peut pro voquer une augmentation anormale de la pression voire une explosion Ne libérez pas le réfrigérant dans l atmosphère Vérifiez l absence de fuites de gaz réfrigérant une fois l installation terminée En cas de fuite de réfrigé rant pendant l installation aérez la pièce Si le réfrigérant entre en contact avec un f...

Page 9: ...ermale En présence d équipements haute fréquence ou sans fil L unité extérieure produit de la condensation lors du mode de chauffage Choisir l endroit où le climatiseur sera monté de façon à éviter à l unité extérieure et ou aux sols d être mouillés par les condensats ou endommagés par le gel des condensats 2 Choisir l emplacement de l installation Lorsque les tuyaux seront attachés à un mur conte...

Page 10: ...ntion Utilisez toujours un matériau d isolation de l épaisseur spécifiée tableau à droite Une isolation trop épaisse peut être à l origine d une installation incorrecte de l unité interne une isolation trop fine peut provoquer la formation de condensation L unité comporte des raccordements évasés sur les faces intérieure et extérieure Retirez le couvercle de vanne de l unité externe et raccordez l...

Page 11: ...t test de contrôle des fuites 1 Retirez le bouchon de l ouverture de service du robinet d arrêt du côté du tuyau de gaz de l unité externe 2 Raccordez la vanne du collecteur à jauge et la pompe à vide à l ouverture de service du robinet d arrêt du côté du tuyau de gaz de l unité externe 3 Faites fonctionner la pompe à vide pendant 15 minutes minimum 4 Contrôlez la dépression ainsi obtenue avec la ...

Page 12: ...eil intérieur à la boîte de sorties Utiliser le même bloc de sorties et la même polarité que pour l unité intérieure Pour pouvoir effectuer des révisions dans le futur laisser un peu de jeu dans le câble de connexion Les deux extrémités du câble de connexion rallonge doivent être dénudées Lorsque le câble est trop long ou lorsqu il est relié à partir du milieu dénuder le câble d alimentation en re...

Page 13: ...ls d alimentation en cuivre 3 Utiliser des fils d une intensité nominale de 600V ou plus pour les câbles d alimentation et les câbles de raccordement de l appareil intérieur l appareil extérieur 4 Installer un câble de terre plus long que les autres câbles 6 1 Charge de Gaz Fig 6 1 1 Raccorder le tuyau de gaz au port de service de la vanne d arrêt à 3 voies 2 Purger l air du tuyau raccordé au tuya...

Page 14: ...elevación anómala de la presión o una explosión No descargue el refrigerante en el ambiente Una vez acabada la instala ción compruebe que no haya fugas de gas refrigerante Si se producen fugas de refrigerante durante la instalación ventile la habitación Si el refrigerante entra en contacto con una llama podría generarse gas nocivo Si se produjeran pérdidas de gas refrigerante en un interior y entr...

Page 15: ...onas de baños termales Donde haya algún equipo inalámbrico o de alta frecuencia La unidad exterior provoca condensación durante la función de calefacción Selec cione un lugar para la instalación en el que la unidad exterior y las tomas de tierra no se humedezcan con agua de drenaje ni se dañen debido a la congelación de este agua de drenaje 2 Selección del lugar de instalación Cuando tenga que ins...

Page 16: ...de grosor especificado tabla de la derecha El uso excesivo de aislante puede causar una instalación incorrecta de la unidad interior y el uso de una cantidad insuficiente de aislante puede provocar la condensación Las unidad tiene conexiones abocinadas en los lados interior y exterior Retire la tapa de la válvula de la unidad exterior y a continuación conecte la tubería Las tuberías de refrigerant...

Page 17: ...nción situada en el lado de la tubería de gas de la unidad exterior 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vacío durante 15 minutos o más 4 Compruebe el vacío con la válvula colectora de manómetro cierre luego esta válvula y detenga ...

Page 18: ...lojen Tras apretarlos tire ligeramente de los cables para confirmar que no se muevan Atención Asegúrese de fijar firmemente el panel de servicio de la unidad exterior Si no se monta correctamente podría producirse un incendio o un electro choque a causa del polvo el agua etc Apriete firmemente los tornillos de cada terminal Realice el cableado de modo que los cables de alimentación no estén en ten...

Page 19: ...e 3 Utilice cables con un régimen nominal de 600 V o superior para los cables de la fuente de alimentación y los cables de conexión de las unidades inte rior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables 6 1 Carga de gas Fig 6 1 1 Conecte el cilindro de gas a la abertura de servicio de la válvula de parada de 3 vías 2 Purgue el aire del tubo o conducto proceden...

Page 20: ...t address telephone number on this manual before handing it to the customer VG79Y103H01 Printed in Thailand HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y103H01_cover4 indd 20 2019 06 28 18 07 18 020 ...

Reviews: