8. Installation, relocation and inspection

 Warning:

If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant 

leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.

The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and comes 

into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.

Electrical work

•  Provide an exclusive circuit for power supply of the air conditioner.

•  Be sure to observe the breaker capacity.

 Warning:

•  The customer should not install this unit. If the unit is installed incorrectly, fire, electric shock, injury due to a falling unit, water leakage, etc. 

may result.

•  Do not connect using branched outlet or an extension cord, and do not attach many loads to one electric outlet.

  A fire or electric shock may result from poor contact, poor insulation, exceeding the permissible current, etc.

  Consult your dealer.

 Caution:

•  Apply grounding

  Do not connect a grounding wire to a gas pipe, water pipe, lightning rod or ground wire of a telephone. 

  If a grounding is incorrect, it may cause an electric shock.

•  Install an earth leakage breaker depending on the place where the air conditioner is to be installed (humid place, etc.). 

  If the earth leakage breaker is not installed, it may cause an electric shock.

Inspection and maintenance

•  When the air conditioner is used for several seasons, the capacity may be lowered due to dirt inside the unit.

•  Depending upon the conditions of use, an odor may be generated or dirt, dust, etc. may prevent proper drainage.

•  It is recommended to apply inspection and maintenance (charged) by a specialist in addition to normal maintenance. Consult your dealer.

Also consider operation sound

•  Do not put an object around the air outlet of the outdoor unit. It may cause lowering of capacity or increase operating sound.

•  If abnormal sound is heard during operation, consult your dealer. 

Relocation

•  When the air conditioner is to be removed or reinstalled because of rebuilding, moving, etc., special techniques and work are required.

 Warning:

Repair or relocation should not be done by the customer.

If this is done incorrectly, it may cause a fire, electric shock, injury by dropping of the unit, water leakage, etc. Consult your dealer.

Disposal

•  To dispose of this product, consult your dealer.

If you have any question, consult your dealer.

Notes: 1.  This figure ( ) indicates GRILLE’s.

   

2.  Specifications subject to change without notice.

Guaranteed operating range

Indoor

Outdoor

Cooling Upper limit

32°C DB, 23°C WB

46°C DB, –

Lower limit

21°C DB, 15°C WB

-10°C DB, – / -15°C DB, – *1

Heating Upper limit

27°C DB, –

24°C DB, 18°C WB

Lower limit

20°C DB, –

-10°C DB, -11°C WB

*1  Depend on outdoor unit.

Units should be installed by licensed electric contractor accordingly to local code requirement.

9. Specifications

Model

SLZ-KF25VA2

SLZ-KF35VA2

SLZ-KF50VA2

SLZ-KF60VA2

Power Supply (Voltage <V>, Frequency <Hz>)

~/N, 230V, 50Hz

Rated Input (Indoor only)

<kW>

0.02

0.02

0.03

0.04

Rated Current (Indoor only)

<A>

0.20

0.24

0.32

0.43

Dimension (Height)

<mm>

245 (10)

Dimension (Width)

<mm>

570 (625)

Dimension (Depth)

<mm>

570 (625)

Fan airflow rate (Low-Middle-High)  

<m

3

/min>

6.5 - 7.5 - 8.5

6.5 - 8.0 - 9.5

7.0 - 9.0 - 11.5

7.5 - 11.5 - 13.0

Noise level (Low-Middle-High)

<dB>

25 - 28 - 31

25 - 30 - 34

27 - 34 - 39

32 - 40 - 43

Net weight

<kg>

15 (3)

BH79A234H02_en.indd   17

3/30/2016   3:54:05 PM

Summary of Contents for SLZ-KF25

Page 1: ...re acondicionado para garantizar un uso seguro y correcto MANUAL DE OPERAÇÃO Para segurança e utilização correctas leia atentamente o manual de operação antes de pôr a funcionar a unidade de ar condicionado DRIFTSMANUAL Läs denna driftsmanual noga för säkert och korrekt bruk innan luftkonditioneringen används Français Deutsch English Nederlands Español Italiano Português Svenska ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ...

Page 2: ... instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision This appliance is not intended for use by persons including chil dren with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been g...

Page 3: ...on Press to save the setting 3 RETURN button Press to return to the previous screen 4 MENU button Press to bring up the Main menu 5 Backlit LCD Operation settings will appear When the backlight is off pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen When the backlight is off pressing any button turns the backlight on and does not ...

Page 4: ...yed for explanation Fri Mode Temp Fan Room Cool Set temp Basic mode Fri Cool Mode Temp Fan Set temp 4 3 2 1 5 6 7 8 9 0 1 3 4 7 2 3 4 5 6 8 9 2 1 5 3 Appears when the On Off timer Night setback or Auto off timer func tion is enabled appears when the timer is disabled by the centralized control system 4 Appears when the Weekly timer is enabled 5 Appears while the units are operated in the energy sa...

Page 5: ...ect is selected the vane setting is set to Auto Set Temperature buttons Weekly timer ON OFF button Set Time button Sets the time Airflow button Changes up down airflow direction Mode button Changes operation mode Timer ON button Timer OFF button OFF ON button Fan Speed button Changes fan speed SET SEND button CANCEL button Up Down buttons Menu button i see button Reset button Remote controller dis...

Page 6: ...rming the initial automatic check The indoor unit beeps to confirm that the signal transmitted from the remote controller has been received Signals can be received up to approximately 7 meters in a direct line from the indoor unit in an area 45 to the left and right of the unit However illumination such as fluorescent lights and strong light can affect the ability of the indoor unit to receive sig...

Page 7: ...at does not operate may get warm or the sound of refrigerant flowing may be heard they are not malfunction The reason is that the refrigerant continuously flows into it Automatic operation According to a set temperature cooling operation starts if the room temperature is too hot and heating operation starts if the room temperature is too cold During automatic operation if the room temperature chan...

Page 8: ...ge Main menu Vane Louver Vent Lossnay High power Timer Weekly timer OU silent mode Cursor Navigating through the pages F1 F2 F3 F4 Main Main display Cursor Page Main menu Vane Louver Vent Lossnay High power Timer Weekly timer OU silent mode page Saving the settings F1 F2 F3 F4 OU silent mode Mon Tue Wed Thu Fri Sat Sun Start Stop Silent Setting display day Exiting the Main menu screen F1 F2 F3 F4 ...

Page 9: ...ification marks Outlet No 3 Outlet No 2 Remote controller setting The airflow direction of this outlet is controlled by the airflow direc tion setting of remote controller Fixed The airflow direction of this outlet is fixed in particular direction When it is cold because of direct airflow the airflow direction can be fixed horizontally to avoid direct airflow How to set the fixed up down air direc...

Page 10: ...is setting is more horizontal than the airflow direction for the Step 1 setting in order to reduce a drafty feeling The draft reduction can be set for only 1 vane Vane setting Press the SELECT button to save the settings A screen will appear that indicates the setting information is being trans mitted The setting changes will be made to the selected outlet The screen will automatically return to t...

Page 11: ...ion 1 Select Maintenance from the Main menu refer to page 8 and press the SELECT button 2 Select 3D i See sensor with the F1 or F2 button and press the SELECT button F1 F2 F3 F4 3D i See sensor Cursor Setting display Air distribution Energy saving option Seasonal airflow 3 6 2 Air distribution F1 F2 F3 F4 Air distribution Input display Cur Address Check Ref address Unit No Identify unit Check butt...

Page 12: ...ately 30 of the maxi mum occupancy rate energy saving operation equal to 1 C is performed No occupancy Auto OFF If there are no persons in the room for the set amount of time 60 180 minutes the operation is automatically stopped 2 When No occupancy energy save or Room occupancy energy save is selected Select the setting with the F4 button OFF Cooling only Heating only Cooling Heating OFF After cha...

Page 13: ...airflow Select Seasonal airflow Cooling Heating B A D C Weekly schedule Wireless remote controller The weekly schedule can be set to four operation patterns for each day of the week The settings include the on and off times and the set temperature Editing mode 1 Switching to the editing mode 1 Press the button when the unit is operating or stopped blinks Fig 1 2 Selecting the setting pattern 1 Pre...

Page 14: ...by using a heat source such as an electric heater this may warp them Do not wash the filters in hot water above 50 C as this may warp them Make sure that the air filters are always installed Operating the unit without air filters can cause malfunction Caution Before you start cleaning stop operation and turn OFF the power supply Indoor units are equipped with filters to remove the dust of sucked i...

Page 15: ...VAseries when the set room temperature is reached during cooling mode the fan operates at the lowest speed Airflow direction changes during operation or airflow direction cannot be set During heating mode the vanes automatically move to the horizontal airflow direction when the airflow temperature is low or during defrosting mode When the airflow direction is changed the vanes always move up and d...

Page 16: ...n wire connectors must match Noise is louder than specifications The indoor operation sound level is affected by the acoustics of the particular room as shown in the following table and will be higher than the noise specification which was measured in an echo free room High sound absorbing rooms Normal rooms Low sound absorbing rooms Location examples Broadcasting studio music room etc Reception r...

Page 17: ... conditions of use an odor may be generated or dirt dust etc may prevent proper drainage It is recommended to apply inspection and maintenance charged by a specialist in addition to normal maintenance Consult your dealer Also consider operation sound Do not put an object around the air outlet of the outdoor unit It may cause lowering of capacity or increase operating sound If abnormal sound is hea...

Page 18: ...nwendung verwendet werden Kinder sollten nicht mit dem Gerät spielen Die Reinigung und Wartung sollte von Kindern nicht ohne Über wachung durchgeführt werden Dieses Gerät darf von Personen einschließlich Kindern mit eingeschränkten physischen sensorischen oder mentalen Fähig keiten bzw ohne ausreichende Erfahrung und Wissen erst nach Einweisung und Anleitung zum Gebrauch des Geräts durch eine für ...

Page 19: ...EIN AUS Knopf 6 EIN AUS Lampe Diese Lampe leuchtet grün wenn die Anlage eingeschaltet ist Sie blinkt wenn die Fernsteuerung startet oder wenn ein Fehler vorliegt 7 Funktionsknopf F1 Hauptanzeige Drücken um die Funktion zu wechseln Betriebsart Hauptmenü Drücken um den Cursor nach unten zu bewegen 8 Funktionsknopf F2 Hauptanzeige Drücken um die Temperatur zu senken Hauptmenü Drücken um den Cursor na...

Page 20: ...odus Alle Symbole werden als Erklärung angezeigt Einfach Modus 3 Wird angezeigt wenn der Ein Aus Timer die Nachtabsenkung oder die Funktion Ausschalt Timer aktiviert ist wird angezeigt wenn der Timer durch das zentrale Steuerungssy stem deaktiviert wird 4 Erscheint wenn die Wochenzeituhr aktiviert ist 5 Erscheint wenn die Anlagen im Energiesparmodus betrieben werden Wird bei einigen Modellen von I...

Page 21: ...ird die Flügeleinstellung auf Auto eingestellt Tasten zum Einstellen der Temperatur Taste Wochentimer EIN AUS Taste Zeit einstellen Stellt die Uhrzeit ein Taste Luftstrom Ändert Richtung des Luftstroms nach oben unten Taste Modus Ändert Betriebsmodus Taste Timer ein Taste Timer aus Taste OFF ON Taste SET SEND Taste CANCEL Tasten Aufwärts Abwärts Menütaste Taste i see Taste Reset Zurücksetzen Displ...

Page 22: ...en bis zu etwa 7 Meter Sichtlinie vom Innengerät in einem Winkel von 45 nach links und rechts vom Gerät empfangen werden Jedoch kann der Empfang des Innengeräts durch Beleuchtung wie Leuchtstofflampen oder starkes Licht beeinträchtigt wer den Falls die Betriebslampe in der Nähe des Empfängers am Innengerät blinkt muss das Gerät über prüft werden Wenden Sie sich zwecks Wartung an Ihren Händler Beha...

Page 23: ...ge obgleich sie nicht arbeitet erwärmt oder das Ge räusch von strömendem Kältemittel hörbar wird Die Ursache liegt dar in daß das Kältemittel kontinuierlich durch die Anlage strömt Automatischer Betrieb Eine Temperatur wird eingestellt und der Kühlbetrieb beginnt wenn die Umge bungstemperatur zu hoch ist bzw der Heizbetrieb beginnt wenn sie zu niedrig ist Im automatischen Betrieb schaltet die Klim...

Page 24: ... F4 Main Main display Cursor Page Main menu Vane Louver Vent Lossnay High power Timer Weekly timer OU silent mode Marke Navigation durch die Seiten F1 F2 F3 F4 Main Main display Cursor Page Main menu Vane Louver Vent Lossnay High power Timer Weekly timer OU silent mode Seite Einstellungen speichern F1 F2 F3 F4 OU silent mode Mon Tue Wed Thu Fri Sat Sun Start Stop Silent Setting display day Hauptme...

Page 25: ... henfolge Off Aus Low Lo und High Hoch zu blättern Nur einstellbar wenn eine LOSS NAY Anlage angeschlossen ist Off Low High Off Low High Bei einigen Innenanlagen kann der Lüfter mit bestimmten Ventila tionsanlagen gekoppelt sein Drücken Sie ZURÜCK um zum Hauptmenü zurück zu kehren Horizontaler Luftstrom Abwärts Fernbedienungs Einstellung Die Luftstromrichtung dieses Aus lasses wird durch die Lufts...

Page 26: ...ist nach unten 4Die aktuelle Flügeleinstellung er scheint Wählen Sie die gewünschten Ausgänge von 1 bis 4 mit F1 oder F2 Auslass 1 2 3 4 und 1 2 3 4 alle Ausgänge Drücken Sie die Taste F3 oder F4 um die Option in der Reihen folge No setting reset Keine Einstellung Zurücksetzen Step 1 Schritt 1 Step 2 Schritt 2 Step 3 Schritt 3 Step 4 Schritt 4 Step 5 Schritt 5 und Draft reduction Zugluftreduzie ru...

Page 27: ... die Anlagen aus dessen Flü gel Vanes Sie einstellen möch ten und drücken AUSWAHL Ref address Ref Adresse Kühlmitteladresse Unit No Geräte Nr 1 2 3 4 Drücken Sie F4 um die Anlage zu bestätigen 2Ändern Sie der Reihe nach die Unit No Geräte Nr und prüfen Sie die einzelnen Geräte Drücken Sie die Taste F1 zur Aus wahl der Unit No Geräte Nr Drücken Sie eine der Tasten F2 bzw F3 um die Geräte Nr des zu ...

Page 28: ...Outlet Angle 3 6 3 Energiesparoption F1 F2 F3 F4 Energy saving option Cursor Setting display No occupancy energy save Room occupancy energy save No occupancy Auto OFF 3 Stellen Sie bei Einstellung von Direkt Indirekt jeden Luftauslass ein Wählen Sie den Luftauslass mit der Taste F1 oder F2 und än dern Sie die Einstellung mit der Taste F4 Drücken Sie nach dem Ändern der Einstellung für alle Luftaus...

Reviews: