11
7. Electrical work
Function table
Select unit number 00 [table 1]
Mode
Settings
Mode no.
Setting no.
Initial set
-
ting
setting
Power failure automatic recovery
Not available
01
1
Available
*1
2
Ο
*2
Indoor temperature detecting
Indoor unit operating average
02
1
Ο
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
Ο
Supported (indoor unit is not equipped with outdoor-air
intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
240 V
04
1
220 V, 230 V
2
Ο
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Settings
Mode no.
Setting no.
Initial set
-
ting
setting
Filter sign
100Hr
07
1
2500Hr
2
Ο
No filter sign indicator
3
Fan speed
Silent
08
1
Standard
2
Ο
High ceiling
3
Up/down vane setting
Not setting
11
1
Draft-less setting (vanes angle setup
1
)
2
Ο
Downward setting (vanes angle setup
2
)
3
3D i-See sensor positioning *3
Position
1
("
□
" stamp position, page 17)
12
1
(Position
1
)
2
Position
3
("○" stamp position, page 17)
3
Ο
Fan speed during the cooling thermostat is OFF
Setting fan speed
27
1
Stop
2
Extra low
3
Ο
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
*3 When the 3D i-See sensor corner panel position changed, change this mode. Refer to page 17.
7.4.3. How to set the fixed up/down air direction
(Only for wired remote controller)
• Only the particular outlet can be fixed to certain direction with the pro-
cedures below. Once fixed, only the set outlet is fixed every time air
conditioner is turned on. (Other outlets follow UP/DOWN air direction
setting of the remote controller.)
■
Explanation of word
• "Refrigerant address No." and "Unit No." are the numbers given to each
air conditioner.
• "Outlet No." is the number given to each outlet of air conditioner.
(Refer to the right.)
• "Up/Down air direction" is the direction (angle) to fix.
Reset
1
horizontal
2
3
4
5
Electric component box
Outlet No. 1
Outlet No. 3
Outlet No. 2
Outlet No. 4
Horizontal airflow
Remote controller setting
The airflow direction of this outlet
is controlled by the airflow direc-
tion setting of remote controller.
Fixed setting
The airflow direction of this outlet is fixed
in particular direction.
* When it is cold because of direct
airflow, the airflow direction can be fixed
horizontally to avoid direct airflow.
Downward
Note:
The outlet No. is indicated by the number of grooves on both ends of each
air outlet. Set the air direction while checking the information shown on the
remote controller display.
Air outlet identification marks
BH79A235H02_en.indd 11
4/5/2016 4:39:16 PM