VII
TROUBLESHOOTING ]
- 41 -
HWE21010
GB
6. TEST POINT DIAGRAM
SEZ-M25DA(L)2
SEZ-M35DA(L)2
SEZ-M50DA(L)2
SEZ-M60DA(L)2
SEZ-M71DA(L)2
6-1. Indoor controller board
CN01 Power supply voltage (220 - 240 VAC)
SWE Emergency
operation
J41, J42 Pair No. setting for wireless remote
controller
SW2 Capacity
setting
CN22 For MA remote controller cable
connection
(10.4 - 14.6 VDC (Between 1 and 3.))
CN51 Centralized
control
CN41 JEMA standard HA terminal A
CN4F
Float switch
CN44 Thermistor
(liquid/condenser/evaporator
temperature)
CN20 Thermistor (Inlet temperature)
CN3C Indoor-outdoor transmission
(0 - 24 VDC)
CNMF Fan motor output
1 - 4: 310 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
CNP
Drain-up mechanism output
(200
VAC)
CN2L LOSSNAY
CN90 Wireless remote controller
(*1)
Vsp
Voltage between the C626 pins
0 VDC (with the fan stopped)
1 - 6.5 VDC (with the fan in operation)
(Same with the voltage between 6 (+)
and 4 (-) of CNMF)
SW2
CN2L
J41
J42
CN51
CN41
LED2
CN22
CN3C
CN01
FUSE (6.3A 250V)
LED3
CN90
SWE
CN105
CN44
CN4F
CN20
CNP
PC626
CNMF
LED1