12
6-4. Trouble criterion of main parts
SEZ-KC25VA.W
Intake air temperature
thermistor (TH1)
Condenser/evaporator
temperature thermistor (TH5)
Measure the resistance with a tester.
(Part temperature 10
°
C ~ 30
°
C)
Pipe temperature
thermistor/liquid (TH2)
Indoor fan motor
(MF)
Check method and criterion
Part name
Normal
8k
Ω
~20k
Ω
Abnormal
Opened or short-circuited
Measure the resistance between the terminals using a tester.
(at 20˚C)
Motor terminal
or
Relay connector
Normal
Abnormal
Open or short
White-Black
261
Ω
White-Brown
White-Yellow
White-Blue
294
Ω
389
Ω
475
Ω
White
Orange
Red
Black
Brown
Yellow
Blue
1
2
4
7
5
6
Protector
Relay connector
3