Transport and storage

When you keep or use it, please fulfil the following environmental conditions.

Refer to "Restrictions on using this product at an altitude exceeding 1000 m and
up to 2000 m above sea level" in the MR-J5 User's Manual (Hardware) for using the
product at an altitude exceeding 1000 m above sea level.

8

Specifications

8.1 MR-J5-A servo amplifiers

When using 1-phase power supply in combination with the servo motor of 750 W
or higher, operate the servo amplifier at 75 % or less of the effective load ratio.

8.2 Dimensions

Without battery MR-BAT6V1SET mounted

Without connectors

E

CAUTION

Transport the products correctly according to their weights.

Stacking in excess of the specified number of products is not allowed.

Do not carry the servo motor by the cables, shaft or encoder.

Do not hold the front cover to transport servo amplifier. The servo am-
plifier may drop.

Install the servo amplifier in a load-bearing place in accordance with
the instruction manual.

Do not climb or stand on servo equipment. Do not put heavy objects on
equipment.

For further detailed information on the optional battery's transporta-
tion and handling refer to the instruction manual of the servo amplifi-
er MR-J5-A.

Environment

Condition

Ambient 
temperature

Operation

0 ˚C to 60 ˚C (non-freezing)
Class 3K3 (IEC 60721-3-3)

Transportation

-25 ˚C to 70 ˚C (non-freezing)
Class 2K3 (IEC 60721-3-2)

Storage

-25 ˚C to 70 ˚C (non-freezing)
Class 1K3 (IEC 60721-3-1)

Ambient humidity

Operation 
Transportation 
Storage

5 to 95 % RH

Ambience

Indoors (no direct sunlight); no corrosive gas, inflam-
mable gas, oil mist or dust

Altitude/
atmospheric 
pressure

Operation

Altitude: 2000 m or less

Transportation

Transportation conditions: Must 
be transported by ground/sea, or 
air at an atmospheric pressure of 
700 hPa or more

Storage

Atmospheric pressure: 700 hPa to 
1060 hPa (equivalent to the alti-
tude of -400 m to 3000 m.)

Vibration resistance

Operation

When there is continuous vibra-
tion:
10 Hz to 57 Hz, displacement 
amplitude 0.075 mm
57 Hz to 150 Hz, acceleration 
amplitude 9.8 m/s2
Class 3M1 (IEC 60721-3-3)
When there is continuous vibra-
tion:
10 Hz to 55 Hz, acceleration 
amplitude 5.9 m/s²

Transportation

2 Hz to 8 Hz, displacement ampli-
tude (half amplitude) 7.5 mm
8 Hz to 200 Hz, acceleration 
amplitude 20 m/s²
Class 2M3 (IEC/EN 60721-3-2)

Storage

2 Hz to 9 Hz, displacement ampli-
tude (half amplitude) 1.5 mm
9 Hz to 200 Hz, acceleration 
amplitude 5 m/s²
Class 1M2 (IEC 60721-3-1)

Item

MR-J5

-

ã

10A

20A

40A

60A

70A

Power 
supply

Main circuit

1-phase or 3-phase 200–240 V AC, 50/60 Hz

Control circuit

1-phase 200–240 V AC, 50/60 Hz

Interface

24 V DC, ±10 % (required current capacity: 
500 mA, including CN8 connector signals)

Control system

Sine-wave PWM control/current control 
system

Safety function (STO) accord-
ing to EN IEC 61800-5-2

EN ISO 13849-1:2015 category 3 PL e, EN 
61508 SIL 3, EN 62061 SIL CL 3, EN 61800-5-2

Expectation of the average 
time for a dangerous failure 
to occur

MTTFd ≥ 100 [years]

Effectiveness of fault 
monitoring of a system or 
subsystem

DC = 97.6 [%]

Average probability of 
dangerous failures per hour

PFH = 6.4 x 10

-9

 [1/hour]

Response time

ã

8 ms (STO input off 

o

 energy shut off )

Short-circuit current rating 
(SCCR)

3-phase 200–240 V AC: 50 kA

Item

MR-J5

-

ã

100A

200A

350A

Power 
supply

Main circuit

1-phase or 3-phase 
200–240 V AC, 
50/60 Hz

3-phase 
200–240 V AC, 
50/60 Hz

All other items are identical with previous table

Servo amplifier

W [mm]

H [mm]

D [mm]

Weight [kg]

MR-J5-10A/20A

40

168 

135 

0.8

MR-J5-40A/60A

40

168 

170 

1.0

MR-J5-70A/100A

60

168 

185 

1.4

MR-J5-200A

90

168 

195 

2.2

MR-J5-350A

90

168 

195 

 2.2

W

D

H

Summary of Contents for SERVO SYSTEM MELSERVO-J5 MR-J5-A

Page 1: ...chinery Directive 2006 42 EC EMC Directive 2014 30 EU RoHS Directive 2011 65 EU Low Voltage Directive 2014 35 EU Work safety regulations safety rules Manufacturers and owners of the machine on which a MELSERVO MR J5 A servo amplifier is used are responsible for obtaining and observing all app licable safety regulations and rules It is imperative that the notices in particular the test notices of t...

Page 2: ... the part inside the dot ted line as follows No Name Description 쐃 Display The 5 digit seven segment LED shows the servo status and alarm number 쐇 Operation section Used to perform status display diagnostics alarm and parame ter setting operations NOTE For further details on servo amplifier s display indication and the functions of the operation section please refer to the instruction manual of MR...

Page 3: ... 60A MR J5 70A MR J5 100A MR J5 200A MR J5 350A CN5 CN6 CN8 CN3 CN2 CN1A CN2L CN4 CNP2 CNP1 CNP3 PE L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 CN8 CN6 CN3 CN2 CN1A CN5 CN2L CN4 CNP2 CNP1 CNP3 PE L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 CN8 CN6 CN3 CN2 CN1A CN5 CN2L CN4 CNP1 CNP2 CNP3 L PE CN3 Pin I O 햲 Signal 햳 Positi...

Page 4: ...tion Altitude 2000 m or less햲 Transportation Transportation conditions Must be transported by ground sea or air at an atmospheric pressure of 700 hPa or more Storage Atmospheric pressure 700 hPa to 1060 hPa equivalent to the alti tude of 400 m to 3000 m Vibration resistance Operation When there is continuous vibra tion 10 Hz to 57 Hz displacement amplitude 0 075 mm 57 Hz to 150 Hz acceleration amp...

Page 5: ...nie 2014 30 EU die RoHS Richtlinie 2011 65 EU die Niederspannungsrichtlinie 2014 35 EU und die Arbeitsschutzvorschriften das Arbeitsschutzgesetz Der Hersteller und der Eigentümer der Maschine in der der MELSERVO Ser voverstärker MR J5 A betrieben wird sind für die Beschaffung und Einhal tung aller anwendbaren sicherheitsrelevanten Vorschriften und Bestimmungen verantwortlich Beachten Sie unbedingt...

Page 6: ...ßer dem die Konfiguration des Teils innerhalb der gepunkteten Linie wie folgt Nr Bezeichnung Beschreibung 쐃 Anzeigefeld Fünfstellige 7 Segment LED zur Anzeige des Servostatus der Alarmcodes und Parameter 쐇 Bedientasten Zum Einstellen der Statusan zeige der Diagnosefunktion der Alarmanzeige und der Parameter HINWEIS Weitere Einzelheitenzuden angezeigtenDatenundden Funktionender Bedientasten finden ...

Page 7: ...CN4 CNP2 CNP1 CNP3 PE L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 MR J5 60A MR J5 70A MR J5 100A MR J5 200A MR J5 350A CN5 CN6 CN8 CN3 CN2 CN1A CN2L CN4 CNP2 CNP1 CNP3 PE L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 CN8 CN6 CN3 CN2 CN1A CN5 CN2L CN4 CNP2 CNP1 CNP3 PE L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 L1 L2 L3 N P3 P4 P C D L11 L21 U V W PE CNP1 CNP2 CNP3 C...

Page 8: ...einstrah lung keine ätzenden oder brennbaren Gase kein Ölnebel oder Staub Aufstellhöhe Luftdruck Betrieb Max 2000 m über NN 햲 Transport Muss zu Land Wasser oder Luft mit einem Luftdruck von mind 700 hPa transportiert werden Lagerung 700 hPa bis 1060 hPa entspricht einer Höhe von 400 m bis 3000 m Vibrationsfestigkeit Betrieb Bei ständiger Vibration 10 Hz bis 57 Hz Verschiebungs amplitude 0 075 mm 5...

Reviews: